This operating instructions manual covers the SIMATIC HMI Comfort Panels product line, published by Siemens AG in July 2022. It addresses mounting, connecting, commissioning, operation, maintenance, and technical specifications for twelve panel models ranging from 4-inch to 22-inch display sizes. The manual applies to key panels, touch panels, and the combined Key and Touch panel variant, all configured using WinCC software within the TIA Portal framework. It is intended for users, commissioning engineers, and maintenance personnel.

Download PDF
4" to 22" Display Sizes Covered
12 Panel Models
07/2022 Publication Date
24 V DC Supply Voltage

Document Preview

Open the full PDF in a new tab  · Publication A5E36770603

Specifications

Display and Enclosure

Display type High-resolution TFT widescreen with 16 million colors, wide viewing angle, completely dimmable
4" model enclosure Plastic enclosure
7" and larger enclosure Aluminum pressure enclosure
Mounting formats Landscape and portrait (portrait for touch models only)

Interfaces

PROFINET (4" models) 1 x PROFINET interface (X1), 10/100 Mb
PROFINET (7", 9", 12" models) 1 x PROFINET interface (X1), 10/100 Mb
PROFINET (15", 19", 22" models) X1: 10/100 Mb; X3: 10/100/1000 Mb (gigabit)
PROFIBUS 1 x PROFIBUS DP interface (X2), Sub-D RS422/485
USB host (Type A) 1 x X61 on 4" models; 2 x X61/X62 on 7" and larger models
USB device (Type Mini-B) 1 x on Comfort V1/V1.1 devices (X60)
Audio X90 Audio Line OUT (not available on KP400 Comfort and KTP400 Comfort)
Power supply connector X80, 24 V DC

Mounting and Installation

Permitted mounting cutout material thickness 2 mm to 6 mm for IP65 or Front face only Type 4X/Type 12 (indoor use only)
Permissible deviation from plane at mounting cutout ≤ 0.5 mm
Permissible surface roughness at seal area ≤ 120 µm (Rz 120)
Approved inclination from vertical Up to +/-35° (self-ventilated)
Extended range, 7" to 15" devices Vertical landscape up to +55 °C, or landscape at up to 40° inclination up to 40 °C, when USB load is 100 mA max. per port, the +24 V DC PROFIBUS connection is unused, and humidity conforms to the climate diagram
Clearance above and below mounting cutout At least 50 mm
Clearance left and right of mounting cutout At least 15 mm
Clearance behind rear panel At least 10 mm
Mounting screw torque (4" model) 0.2 Nm
Mounting screw torque (7" to 22" models) 0.5 Nm
Power supply cable max cross-section 1.5 mm²
Power supply connector screw torque 0.5 to 0.6 Nm

Memory

Internal memory contents Operating system, project file, license keys, user administration, recipes, other data
Memory card slots 2 slots: one for user data (SD IO/HC or MMC format), one for system memory card
System memory card requirement SIMATIC HMI Memory Card ≥ 2 GB only
Data log storage frequency Approximately 0.2 Hz

Device Variants by Version

Comfort V1 features Display sizes 4"...22", audio double socket, USB Mini-B socket, Windows CE 6
Comfort V1.1 features Display sizes 7"...12", audio OUT, USB Mini-B socket, Windows CE 6
Comfort V2 features Display sizes 15"...22", audio OUT, no USB Mini-B socket, Windows Embedded Compact 2013

EMC Standards

Interference emission EN 61000-6-4:2019
Immunity EN 61000-6-2:2019

Communication Protocols

Supported industrial networks and field buses for the products covered by this publication.

PROFINET Devices with 7\" or larger displays have an internal switch, so a ring topology can be set up without an external switch (use X1 on 15\" and larger). 15\" and larger models add a gigabit PROFINET interface (X3, 10/100/1000 Mb). PROFIBUS DP Sub-D RS422/485 interface (X2) present on all Comfort Panel models. TCP/IP / Ethernet PROFINET (LAN) interface used for configuration PC connection, project transfer, Sm@rtServer remote access, and Web Server functionality.

Certifications & Compliance

Possible approvals listed in section 8.2; the device itself is approved as shown on its rear panel labels CE: EMC Directive 2014/30/EU, Explosion protection Directive 2014/34/EU, RoHS Directive 2011/65/EU UKCA marking UL approval (E116536 or E222109): 7 to 12 in devices to UL 61010-1 / UL 61010-2-201; all other devices to UL 508; Class I, Division 2, Group A, B, C, D T4 or Class I, Zone 2, Group IIC T4 FM Approval: Class I, Division 2, Group A, B, C, D T4; Class I, Zone 2, Group IIC T4 ATEX/UKEX/IECEx approval for devices with Ex marking (II 3 G Ex ec IIC T4 Gc; II 3 D Ex tc IIIC T70 °C Dc) IEC 61010-2-201 and/or IEC 61131-2 RCM Australia/New Zealand, KC (Korea), EAC Marine approvals: ABS, BV, DNV, LRS, RINA, Class NK, KR, CCS

Document Contents

Full PDF covers the following topics in detail:

  • Preface: purpose, scope, basic knowledge required, naming conventions
  • Chapter 1: Overview: product description, scope of delivery, device design, interfaces, accessories, software add-ons
  • Chapter 2: Safety instructions: general safety, security management, data protection, usage notes, hazardous area use
  • Chapter 3: Mounting and connecting the device: installation location, mounting cutout, mounting clips, wiring, power supply, controller connection, USB and printer connection
  • Chapter 4: Commissioning the device: firmware and software, memory concept, memory card management, Control Panel parameterization, network and transfer settings, UPS
  • Chapter 5: Commissioning a project: operating modes, data transfer, backup and restore, OS update, add-on and license key management
  • Chapter 6: Operating a project: function keys, direct keys, value input, infotext, language setting
  • Chapter 7: Maintenance and care: cleaning, spare parts, recycling
  • Chapter 8: Technical information: certifications, EMC, mechanical and climatic conditions, dimension drawings, technical specifications, interface descriptions, controller communication, WinCC scope of functions
  • Appendix A: Technical Support: troubleshooting, system alarms, manufacturer information
  • Appendix B: Markings and symbols
  • Appendix C: Abbreviations and Glossary

Frequently Asked Questions

Which HMI device models does this manual cover?
The manual covers twelve SIMATIC HMI Comfort Panel models: KP400 Comfort (6AV2124-1DC01-0AX0), KTP400 Comfort (6AV2124-2DC01-0AX0), KP700 Comfort (6AV2124-1GC01-0AX0), TP700 Comfort (6AV2124-0GC01-0AX0), KP900 Comfort (6AV2124-1JC01-0AX0), TP900 Comfort (6AV2124-0JC01-0AX0), KP1200 Comfort (6AV2124-1MC01-0AX0), TP1200 Comfort (6AV2124-0MC01-0AX0), KP1500 Comfort, TP1500 Comfort, TP1900 Comfort, and TP2200 Comfort. Display sizes range from 4 inches to 22 inches.
What software is required to configure the Comfort Panels?
All Comfort Panel models are configured using WinCC software integrated into the Totally Integrated Automation (TIA) Portal. Devices are configurable as of WinCC V11; the manual description relates to V14 or higher.
What PROFINET interfaces are available and what are their speeds?
The 4-inch models have one PROFINET interface (X1) at 10/100 Mb. The 7\", 9\", and 12\" models also have one PROFINET interface (X1) at 10/100 Mb. Devices with 15\" displays or larger have two PROFINET interfaces: X1 at 10/100 Mb and an additional gigabit X3 interface at 10/100/1000 Mb.
What are the memory card requirements for the system memory card slot?
Only a SIMATIC HMI Memory Card with a capacity of 2 GB or greater may be used as the system memory card. All other memory cards are not recognized as a system memory card by the HMI device. The standard memory card slot accepts commercially available SD (IO/HC) or MMC format cards, though Siemens recommends the SIMATIC HMI Memory Card for data consistency.
What are the permitted mounting positions and temperature limits for the Comfort Panels?
All HMI devices support landscape mounting. Touch models also support portrait mounting. The device is self-ventilated and approved for inclined mounting at angles up to +/-35° from the vertical. For 7\" to 15\" devices, vertical landscape mounting at up to +55 °C and inclination up to 40° from vertical at up to 40 °C are permitted when USB load does not exceed 100 mA per port and the 24 V DC PROFIBUS interface connection is not used.
What uninterruptible power supply (UPS) devices are supported?
The HMI devices support SITOP DC UPS modules as of a rated power value of 6 A, connected to the USB port of the HMI device. On a power failure the HMI device is shut down in a controlled manner after a buffer time. The UPS add-on must be transferred as an option; no license key is required.
What software add-ons are available for the Comfort Panels?
Available add-ons include WinCC /Sm@rtServer (remote HMI access and Web Server), WinCC /Audit (audit trail and electronic signature), WinCC /ProDiag (plant and machine monitoring), UPS with USB support, PDF Viewer, Word Viewer, Excel Viewer, Media Player, Internet Explorer, and a printer driver for PostScript, HTML, and PDF output. Pre-installed add-ons (PDF Viewer, Word Viewer, Excel Viewer, Media Player, Internet Explorer) require no license key.