How-To Guide

Siemens ET 200SP DI 16x24VDC ST Digital Input Module

Complete setup guide for the 16-channel 24VDC sink digital input module: ET 200SP system assembly, BaseUnit selection, field wiring, TIA Portal configuration, input delay settings, diagnostics, and LED troubleshooting.

Get a Quote on the 6ES7131-6BH01-0BA0
16 Input Channels
24VDC Rated Voltage
Sink (PNP) P-Reading Input
ET 200SP SIMATIC Platform

How-To Guide  ·  Siemens ET 200SP  ·  Digital Input Configuration

6ES7131-6BH01-0BA0: Installation, Wiring, TIA Portal Configuration, and Diagnostics Guide

ET 200SP Platform  ·  DI 16x24VDC ST  ·  Sink Input (P-Reading)  ·  TIA Portal / STEP 7

The 6ES7131-6BH01-0BA0 is a 16-channel 24VDC sink (PNP, P-reading) digital input module for the Siemens SIMATIC ET 200SP distributed I/O platform. It connects to a SIMATIC S7-1500 or S7-1200 controller via a PROFINET or PROFIBUS interface module (IM 155-6 PN or IM 155-6 DP). The ET 200SP system uses a modular design: BaseUnit, I/O module, and color-coded labeling strips. The module is suitable for connection of switches and 2-wire sensors in accordance with IEC 61131, type 3. It supports configurable input delay from 0.05 to 20 ms per channel (plus an additional 30 to 500 µs depending on cable length), wire-break diagnostics (module-by-module), and supply voltage monitoring. This guide covers ET 200SP system assembly, BaseUnit wiring, TIA Portal configuration, and LED diagnostics — all specifications verified against Siemens publication A5E03573442-AG (02/2019) and product datasheet 6ES7131-6BH01-0BA0 (updated 02/2026).

1. Module Overview

The 6ES7131-6BH01-0BA0 is a 16-point sink digital input module for the ET 200SP platform. It reads 24VDC discrete signals using P-reading (sink/PNP) inputs and maps them into 2 bytes of input data (1 bit per channel). The module supports per-channel input delay selection from 0.05 to 20 ms, per-module diagnostics for wire break and supply voltage loss, and is suitable for connection of switches and 2-wire sensors per IEC 61131, type 3. The module color code is CC00 and requires BaseUnit type A0 with mechanical coding element Type A.

The module has hardware functional status from FS02, firmware version V0.0 (no firmware update possible), and supports I&M data I&M0 to I&M3. It does not support isochronous mode, counter mode, oversampling, or MSI mode. It is suitable for operation on PROFINET R1 interface modules. The module is not suitable for safety functions.

Catalog Number Breakdown

CodeMeaningValue
6ES7Product familySIMATIC S7 I/O
131Module typeET 200SP digital input module
6BH01Variant16-channel, 24VDC, standard (ST)
0BA0VersionHardware / firmware generation

A 10-unit package variant is also available: 6ES7131-6BH01-2BA0 (identical module, sold in package unit of 10 units).

Key Specifications

ParameterValueSource
Article Number6ES7131-6BH01-0BA0Manual §6.1 / Datasheet
Product Type DesignationDI 16x24VDC STDatasheet p.1
Number of Digital Inputs16Manual §2.1 / Datasheet p.2
Source/Sink Input TypeP-reading (PNP / sink)Datasheet p.2
Input Characteristic per IEC 61131, Type 3YesDatasheet p.2
Input Voltage Rated (DC)24 VDatasheet p.2
Signal “0” Voltage Range−30 to +5 VDatasheet p.2
Signal “1” Voltage Range+11 to +30 VDatasheet p.2
Input Current for Signal “1” (typ.)2.5 mADatasheet p.2
2-Wire Sensor Quiescent Current (max.)1.5 mADatasheet p.2
Supply Voltage L+ Rated (DC)24 VDatasheet p.1
Supply Voltage L+ Permissible Range19.2 – 28.8 V DCDatasheet p.1
Reverse Polarity ProtectionYesDatasheet p.1
Current Consumption (max.)90 mADatasheet p.1
Power Loss (typ.)1.7 WDatasheet p.1 / Manual §6.1
24 V Encoder SupplyNoDatasheet p.1
Address Space2 bytes input + 2 bytes QI (Quality Information, optional)Datasheet p.2 / Manual §4.3
Input Delay (parameterizable per channel)None / 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms (default: 3.2 ms) + additional 30 to 500 µs depending on line lengthManual §4.1 / Datasheet p.2
0→1 Transition Delaymin. 0.05 ms, max. 20 msDatasheet p.2
1→0 Transition Delaymin. 0.05 ms, max. 20 msDatasheet p.2
Cable Length Shielded (max.)1,000 mDatasheet p.2
Cable Length Unshielded (max.)600 mDatasheet p.2
DiagnosticsWire break (module-by-module, optional 25–45 kΩ protective resistor for mechanical contacts), supply voltage monitoring, group error; no short-circuit detection; no per-channel diagnostics LEDDatasheet p.2 / Manual §5
LEDsPWR (green), DIAG (green/red), 16× channel status (green, .0 to .15)Manual §5.1
Potential Separation — Between ChannelsNoDatasheet p.2
Potential Separation — Channels to Backplane BusYesDatasheet p.2
Potential Separation — Channels to Electronics PowerNoDatasheet p.3
Isolation Test Voltage707 V DC (type test)Datasheet p.3
Operating Temperature (horizontal)−30 to +60 °C (below 0 °C as of FS02)Manual §6.1 / Datasheet p.3
Operating Temperature (vertical)−30 to +50 °C (below 0 °C as of FS02)Manual §6.1 / Datasheet p.3
Max. Altitude5,000 m per datasheet; manual specifies 2,000 m standard, higher on request. Restrictions apply above 2,000 m.Datasheet p.3 / Manual §6.1
Dimensions (W × H × D)15 × 73 × 58 mmManual §6.1 / Datasheet p.3
Weight (approx.)28 gDatasheet p.3
BaseUnit Type RequiredBU type A0Datasheet p.1 / Manual §6.1
Mechanical Coding ElementType ADatasheet p.2
Color Code (labeling)CC00Datasheet p.1
Hardware Functional StatusFrom FS02Datasheet p.1
Firmware VersionV0.0 (no firmware update possible)Datasheet p.1
I&M DataYes; I&M0 to I&M3Datasheet p.1
Isochronous ModeNoDatasheet p.1
Suitable for PROFINET R1 IMsYesDatasheet p.1
Suitable for Safety FunctionsNoDatasheet p.3
CertificationsCE, UKCA, UL, KC, RCM, EAC, FM, CCC-Ex, ATEX, IECExDatasheet p.3–4
Maritime ApprovalsABS, Bureau Veritas, DNV, Lloyd’s Register, NK, RINA, RMRS, CCS, KRDatasheet p.4

Version Dependencies

The following table shows the version dependencies for key functions, taken directly from the module manual (Table 2-1, page 12).

FunctionHW VersionFW VersionTIA PortalSTEP 7 V5.xPROFINET IO GSDPROFIBUS DP GSD
I&M data (I&M0 to I&M3)FS01V0.0.0+V14+ with HSP 0222V5.5 SP3+ with HSP 0229 V7.0YesYes
Configuration in RUNFS01V0.0.0+V14+ with HSP 0222V5.5 SP3+ with HSP 0229 V7.0YesYes
Value status (QI)FS01V0.0.0+V14+ with HSP 0222V5.5 SP3+ with HSP 0229 V7.0YesYes

Engineering Software Compatibility

SoftwareMinimum Version
STEP 7 TIA PortalV14 or higher (with HSP 0222)
STEP 7 V5.xV5.5 SP3 or higher (with HSP 0229 V7.0)
PCS 7V8.1 SP1 or higher
PCS neoFrom V1.0.0
PROFINET GSDGSDML V2.3
PROFIBUS GSDOne GSD file each, Revision 3 and 5 and higher
ET 200SP vs Allen-Bradley POINT I/O The ET 200SP is Siemens' equivalent of Allen-Bradley's POINT I/O (1734) platform. Both are modular distributed I/O systems with separate terminal bases and I/O modules. ET 200SP uses BaseUnits (like terminal bases) and communicates via PROFINET to S7 controllers, while POINT I/O uses terminal bases and communicates via EtherNet/IP to Logix controllers.

2. Hardware Installation

The ET 200SP system uses 35 mm DIN rail mounting. The station is assembled left to right: interface module first, then BaseUnits with I/O modules snapped in, and terminated with a server module at the right end. Each I/O module mounts into a BaseUnit — the BaseUnit provides the backplane connection, terminal wiring points, and field power distribution via the self-assembling P1, P2, and AUX voltage buses. Per the module manual (section 3.1): the load group of the module must begin with a light-colored BaseUnit, and only digital modules with BaseUnit type A0 should be used during commissioning.

System Assembly Order

PositionComponentExample
1 (leftmost)Interface ModuleIM 155-6 PN ST (6ES7155-6AU01-0BN0) for PROFINET, or IM 155-6 DP for PROFIBUS
2 – NBaseUnit + I/O Module pairsLight-colored BU type A0 to start a potential group + DI 16x24VDC ST (6ES7131-6BH01-0BA0); dark-colored BU type A0 for additional modules in the same potential group
Last (rightmost)Server Module6ES7193-6PA00-0AA0 (required to terminate the backplane bus)

Installation Steps

  1. Mount the IM 155-6 PN interface module on a 35 mm DIN rail. Snap the interface module onto the rail until the locking clip engages. The interface module provides the PROFINET connection to the S7-1500 or S7-1200 controller and distributes backplane power to all I/O modules in the station.
  2. Mount a light-colored BaseUnit (BU type A0) to the right of the interface module. The light-colored BaseUnit starts a new potential group. It interrupts the three self-assembling voltage buses (P1, P2, AUX) from the left neighbor, so L+ and M must be wired at this BaseUnit. The BaseUnit includes a 2.5 A fuse for the L+ supply (per manual Figure 3-1). Slide it onto the rail and press until it clicks.
  3. Install the mechanical coding element (Type A) into the BaseUnit. The DI 16x24VDC ST requires mechanical coding element Type A (per datasheet p.2). This prevents incorrect module insertion — only modules with a matching coding key can be plugged in.
  4. Snap the DI 16x24VDC ST module into the BaseUnit. Align the module with the BaseUnit guides and press firmly until it clicks into place. The module engages the backplane connector automatically.
  5. Attach the color identification label. The module uses color code CC00. Insert the corresponding color-coded label into the label slot on the module front (per manual Figure 2-1, callout 8). Labeling strips, color identification labels, and reference identification labels must be ordered separately (manual §2.1).
  6. Mount additional BaseUnits for subsequent I/O modules. Use dark-colored BaseUnits for modules that should share the same field power potential group as the first BaseUnit. A dark-colored BaseUnit takes the potential of the self-assembling voltage buses P1, P2, and AUX from the left neighbor. Use a new light-colored BaseUnit to start a new potential group with independent L+ and M supply.
  7. Terminate the station with a server module. The server module (6ES7193-6PA00-0AA0) must be installed at the rightmost position. It terminates the ET 200SP backplane bus. The station will not operate without it.
BaseUnit Color and Potential Groups Per the module manual (section 4.2): a potential group consists of directly adjacent I/O modules within an ET 200SP station that are supplied via a common supply voltage. A potential group begins with a light-colored BaseUnit through which the required voltage is supplied. The light-colored BaseUnit interrupts the three self-assembling voltage buses P1, P2, and AUX to the left neighbor. All additional I/O modules in the potential group are plugged into dark-colored BaseUnits, which take the potential of the P1, P2, and AUX buses from the left neighbor. A potential group ends with the last dark-colored BaseUnit before the next light-colored BaseUnit or server module in the station configuration. The first BaseUnit in every station must be light-colored.

3. Wiring

Terminal Assignments — BU Type A0, 1-Wire Connection

The DI 16x24VDC ST module uses a BU type A0 BaseUnit with 16 input terminals arranged in two columns (left and right). This is a 1-wire connection — each field signal connects to a single terminal on the BaseUnit. Per the manual’s block diagram (Figure 3-1, page 14): even-numbered channels (CH0, CH2, CH4, CH6, CH8, CH10, CH12, CH14) connect on the left column at pins 1, 3, 5, 7, 9, 11, 13, 15, and odd-numbered channels (CH1, CH3, CH5, CH7, CH9, CH11, CH13, CH15) connect on the right column at pins 2, 4, 6, 8, 10, 12, 14, 16. Field power (L+ and M) is supplied to the dedicated supply terminals on the light-colored BaseUnit and distributed via the backplane to dark-colored neighbors.

Pin (Left)FunctionPin (Right)Function
1DI₀ — Channel 02DI₁ — Channel 1
3DI₂ — Channel 24DI₃ — Channel 3
5DI₄ — Channel 46DI₅ — Channel 5
7DI₆ — Channel 68DI₇ — Channel 7
9DI₈ — Channel 810DI₉ — Channel 9
11DI₁₀ — Channel 1012DI₁₁ — Channel 11
13DI₁₂ — Channel 1214DI₁₃ — Channel 13
15DI₁₄ — Channel 1416DI₁₅ — Channel 15

The BaseUnit also provides dedicated terminals for L+ (24 V DC supply, fused at 2.5 A on the light-colored BaseUnit per manual Figure 3-1) and M (ground return). These are separate from the 16 signal input pins. The light-colored BaseUnit feeds L+ and M to the module via filter connection supply voltage terminals. The block diagram (manual Figure 3-1) shows the filter connection (callout 5) operates only when a light-colored BaseUnit is present.

Connection Variants

The DI 16x24VDC ST supports multiple connection variants depending on the BaseUnit configuration. Per the manual’s technical specifications (section 6.1, page 25):

Connection TypeBaseUnit RequiredNotes
1-wire connectionBU type A0Standard wiring — one signal wire per channel. L+ and M supplied at light-colored BaseUnit. Shown in manual Figure 3-1.
2-wire connectionBU type A0 + Potential isolation moduleSeparate L+ feed per channel via potential isolation module.
3-wire connectionBU type A0 + Potential isolation moduleFor 3-wire sensors requiring L+, signal, and M per channel.
4-wire connectionBU type A0 + Potential isolation moduleFor 4-wire sensors with additional wire for shielding or test signals.

Sink (P-Reading) Wiring

P-reading (sink) inputs require the field device to switch the positive voltage to the input terminal. When the field device closes, current flows from L+ (24 V DC) through the device and into the module input. The return path is through M (ground) on the BaseUnit backplane. The typical input current for signal “1” is 2.5 mA (per datasheet page 2).

FromToDescription
L+ (24 V DC supply)Field device (one side)Positive leg of the 24 V DC field supply (infeed only with light-colored BaseUnit)
Field device (other side)DI terminal (pin 1 – 16)Signal wire into the module input channel
M (0 V)BaseUnit M terminalReturn path via BaseUnit backplane

Typical Field Device Wiring Examples

Field DeviceContact TypeWiringNotes
Pushbutton (Start)Normally Open (NO)L+ → PB → DI pinInput ON when pressed
Pushbutton (Stop / E-Stop)Normally Closed (NC)L+ → PB → DI pinInput ON normally; OFF when pressed (fail-safe)
3-Wire PNP Proximity SensorPNP sourcing outputL+ → BN; BK → DI pin; BU → MPNP sensors are directly compatible with P-reading inputs
2-Wire Proximity Sensor2-wire DCL+ → sensor (+); sensor (−) → DI pinQuiescent current must be ≤ 1.5 mA per datasheet spec (IEC 61131 Type 3)
Limit SwitchNO or NCL+ → switch → DI pinUse NC for safety-critical applications (fail-safe)
Overload Relay (95–96)NCL+ → 95 → 96 → DI pinInput ON = normal; OFF = tripped (fail-safe)
Wire-Break Detection and Parallel Resistor Per the module manual (section 3.1, page 15): when wire-break detection is configured, the module requires a low quiescent current at the digital input in case of a “0” signal for monitoring. The parallel connection of a resistor with 25 kΩ to 45 kΩ is required so that this quiescent current can flow when mechanical transducer contacts are open. If wire-break detection is disabled in the configuration, no parallel connection of the resistor is required. Connect the resistor in parallel across each mechanical transducer contact that will be monitored. Solid-state sensors with active outputs do not require the resistor.

4. TIA Portal Configuration

The 6ES7131-6BH01-0BA0 is configured in Siemens STEP 7 (TIA Portal) V14 or higher with HSP 0222 for PROFINET IO, or STEP 7 V5.5 SP3 or higher with HSP 0229 V7.0 for PROFIBUS DP. The module can also be configured with PCS 7 V8.1 SP1 or higher, or PCS neo from V1.0.0 (per datasheet page 1). Three configurations are possible per the manual (section 4.1): central operation with an ET 200SP CPU, distributed operation on PROFINET IO, or distributed operation with PROFIBUS DP.

Adding the Module in TIA Portal

  1. In TIA Portal, open your project and navigate to Devices & Networks → double-click your ET 200SP station to open Device Configuration.
  2. In the device view, the station rack shows the interface module and any existing modules. Click an empty slot to the right of the last module.
  3. In the Hardware Catalog panel on the right, expand DI → locate DI 16x24VDC ST (order number 6ES7131-6BH01-0BA0) and drag it onto the empty slot, or double-click to add it.
  4. The module appears in the slot. TIA Portal automatically assigns input addresses (default: process image of inputs, 2 bytes).
  5. Click the module to select it, then open the Properties panel below to configure parameters.

Configuration Options (GSD File)

The module can be configured in two ways via the GSD file. Per the manual (Table 4-2, section 4.3, page 19):

ConfigurationShort Designation / Module NameTIA Portal VersionPROFINET IO GSDPROFIBUS DP GSD
1 x 16-channel without value statusDI 16x24VDC ST V0.0V14, SP1+ with HSP 0222YesYes
1 x 16-channel with value status (QI)DI 16x24VDC ST V0.0, QIV14, SP1+ with HSP 0222YesNo

Module Parameters

All parameters are set per-module or per-channel in the Properties → Module Parameters tab. The following table lists all configurable parameters with their options and defaults, taken directly from the module manual (Table 4-1, pages 16–17).

ParameterOptionsDefaultScope (PROFINET IO / PROFIBUS DP)Reassign in RUNNotes
Diagnostics: No supply voltage L+Enable / DisableDisableModule / ModuleYesGenerates diagnostic alarm (error code 11H) if L+ supply voltage is missing or below threshold. Per manual §5.3.
Diagnostics: Wire breakEnable / DisableDisableModule / ModuleYesDetects open circuit on input wiring (error code 6H). Requires 25–45 kΩ parallel resistor on mechanical contacts. Per manual §3.1 and §5.3.
Channel activatedEnable / Disable (per channel)EnableChannel / ChannelYesDisabling a channel removes it from processing. Useful for unused inputs to suppress diagnostics. Per manual §4.2.
Input delayNone / 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms3.2 msChannel / Module1YesFilter time applied to both 0→1 and 1→0 transitions. Changes to the signal are only detected if they are constantly pending longer than the set input delay time (manual §4.2). The actual delay includes an additional 30 to 500 µs depending on cable length (datasheet p.2).
Potential groupUse potential group of left module (dark-colored BU) / Enable new potential group (light-colored BU)Use potential group of left moduleModule / ModuleNoMust correspond to the physical BaseUnit color. Per manual §4.2.

1 Per manual footnote 2 (page 17): with a PROFIBUS GSD configuration, input delay is a module-level parameter (applies to all channels equally) due to the limited parameter length of 4 bytes. The per-channel setting can be used via data record 128 if needed (see Appendix A).

Address Space

The module occupies 2 bytes of input address space in the process image input (PII), optionally extended to 4 bytes when value status (Quality Information / QI) is enabled. Per manual section 4.3 and Figure 4-1 (page 20):

ByteBitsDescription
IB aBit 0 – Bit 7Channels 0 – 7 (DI₀ to DI₇)
IB a+1Bit 8 – Bit 15Channels 8 – 15 (DI₈ to DI₁₅)
IB a+2Bit 0 – Bit 7QI value status for channels 0 – 7 (QI0 to QI7) — only when QI enabled
IB a+3Bit 8 – Bit 15QI value status for channels 8 – 15 (QI8 to QI15) — only when QI enabled

The starting address a is automatically assigned by TIA Portal based on slot position. You can manually override it in the module Properties → I/O Addresses tab. In the S7-1500 process image, inputs are accessed as I a.x (e.g., I 0.0 for channel 0 if the base address is 0).

Evaluating Value Status (QI)

Per manual section 4.3 (page 19): when value status (QI) is enabled, an additional 2 bytes are allocated in the input address space. Bits 0 to 15 in these bytes are assigned to channels 0 to 15 and provide information about the validity of the digital value:

QI Bit ValueMeaning
1No fault is present on the channel
0Channel is deactivated or there is a fault on the module

If a fault occurs on a channel with this module, the value status for all channels is set to 0. Value status with QI is available only via PROFINET IO GSD — it is not supported with PROFIBUS DP GSD (per manual Table 4-2).

Input Delay Recommendations

Input DelayUse Case
0.05 – 0.1 msHigh-speed signals, encoder feedback, externally debounced sensors
0.4 – 1.6 msClean electronic signals — PNP proximity sensors, photoelectric sensors
3.2 ms (Default)General purpose; good balance of speed and noise rejection for most sensors
12.8 msMechanical contacts — limit switches, relay auxiliary contacts
20 msPushbuttons, toggle switches, very noisy electrical environments
Runtime Parameter Changes Per the module manual (Appendix A, page 28): all parameters except “Potential group” can be reassigned while the CPU is in RUN mode. Use the “WRREC” instruction to transfer parameters via data record 128. The parameters set in STEP 7 are not changed in the CPU by WRREC, so the original STEP 7 parameters will be valid again after a restart. If errors occur when transferring parameters with WRREC, the module continues operation with the previous parameter assignment and the STATUS output parameter contains a corresponding error code.
Data Record 128 Structure Per the manual (Appendix A, pages 29–30): the parameter data record uses the same structure for both PROFIBUS DP and PROFINET IO. Channel 0 includes the diagnostics enable for the entire module. Each channel occupies 2 bytes in the data record. The header (Byte 0) contains the version information and the parameter data length per channel = 2 bytes.
TIA Portal vs. Studio 5000 If you are familiar with Allen-Bradley, TIA Portal is the Siemens equivalent of Studio 5000 Logix Designer. The ET 200SP station appears in the Device Configuration view the same way a POINT I/O adapter appears in the I/O tree in Studio 5000. Module parameters are set in the Properties panel rather than the Module Properties dialog, and input addresses are automatically assigned based on slot order.

5. Diagnostics & Troubleshooting

LED Indicators

The 6ES7131-6BH01-0BA0 has three types of LEDs per manual section 5.1 and Figure 5-1 (page 21): one DIAG LED (green/red) for module diagnostics at the top of the module, 16 channel status LEDs (green, labeled .0 through .15) in the lower section, and one PWR LED (green) for supply voltage status at the bottom.

DIAG LED (green/red) — Manual Table 5-1

StateMeaningAction
OffBackplane bus supply of the ET 200SP not OKCheck that the ET 200SP station is fully assembled with all BaseUnits seated and the server module installed. Verify the interface module is powered and communicating.
Flashing (green)Module parameters not assignedDownload the TIA Portal project to the interface module. Verify the module catalog number matches the configured slot in Device Configuration.
On steady (green)Module parameters assigned — operating normallyNormal operation — no action required.
Flashing (green/red alternating)Module diagnostics is available — at least one diagnostic alarm is activeOpen TIA Portal → Online & Diagnostics → Diagnostics buffer to read the active alarm. Check for wire break or missing supply voltage based on enabled diagnostic parameters.

Channel Status LEDs (.0 – .15) — green — Manual Table 5-2

StateMeaning
OffProcess signal = 0 (channel input is in signal state “0” / OFF)
On (green)Process signal = 1 (channel input is in signal state “1” / ON)

PWR LED (green) — Manual Table 5-3

StateMeaningAction
OffMissing supply voltage L+Check L+ wiring at the light-colored BaseUnit terminal. Verify 24 V DC supply is energized and within 19.2–28.8 V range (per datasheet).
On (green)Supply voltage L+ presentNormal operation — no action required.

Diagnostic Interrupts — Manual Section 5.2

The DI 16x24VDC ST digital input module supports diagnostic interrupts. Per the manual (section 5.2, page 23), a diagnostics alarm is generated and the DIAG LED flashes on the module for each diagnostics event. The module generates a diagnostic interrupt for the following events:

  • Wire break
  • Parameter assignment error
  • Supply voltage missing

You can read out the diagnostics alarms in the diagnostics buffer of the CPU and evaluate the error codes with the user program.

Diagnostic Alarms and Error Codes — Manual Table 5-4

Diagnostics AlarmError CodeMeaningSolution
Wire break6HImpedance of transducer circuit too high; wire break between the module and sensor; channel not connected (open)Use a different transducer type or modify the wiring (e.g., use cables with larger cross-section). Connect the cable. Disable diagnostics on unused channels, or connect a resistor of 25 kΩ to 45 kΩ parallel to the transducer contacts. (Manual §5.3)
Parameter assignment error10HThe module cannot evaluate the parameters for the channel; incorrect parameter assignmentCorrect the parameter assignment. Verify the module catalog number and hardware version match the configuration in TIA Portal. Re-download the project. (Manual §5.3)
Supply voltage missing11HMissing or insufficient supply voltage L+Check supply voltage L+ on the BaseUnit. Check BaseUnit type — verify it is the correct color for the potential group. (Manual §5.3)

Common Faults and Resolutions

SymptomLikely CauseResolution
DIAG LED flashing green, no dataModule not parameterized — project not downloadedDownload the TIA Portal project to the interface module (Online → Download to device). Verify the slot assignment matches the physical position.
DIAG LED offBackplane bus supply of the ET 200SP not OK (per manual Table 5-1)Verify the station is fully assembled: all BaseUnits seated, server module installed, interface module powered. Check backplane connectors are properly engaged.
PWR LED offNo supply voltage L+ at BaseUnit (per manual Table 5-3)Verify 24 V DC is wired to the L+ and M terminals of the light-colored BaseUnit. Check the supply fuse (2.5 A on BaseUnit per manual Figure 3-1) and wiring continuity. Supply must be within 19.2–28.8 V range.
Channel LED off but field device is activatedWiring fault or insufficient voltageMeasure voltage at the DI terminal with respect to M — must be ≥11 V for signal “1” (per datasheet: signal “1” range is +11 to +30 V). Check for broken wires, loose terminal connections, or reversed connections.
Channel LED on but tag reads 0 in TIA PortalModule inhibited or CPU in STOP modeVerify the CPU is in RUN mode. Check that the module is not inhibited in Device Configuration. Confirm the input address in the program matches the assigned address in TIA Portal.
All 16 channels read 0No field supply voltageCheck L+ supply to the BaseUnit. Verify the BaseUnit type is light-colored (starts potential group). Confirm M (ground) is connected at the BaseUnit.
Wire-break alarm on unused channelsWire-break diagnostics enabled on channels with no field wiringIn TIA Portal, disable wire-break diagnostics or deactivate unused channels (Channel activated = Disable) for channels with no field wiring. Per manual §4.1.
DIAG LED flashing green/redActive diagnostic alarm (per manual Table 5-1)Read the diagnostics buffer in TIA Portal Online & Diagnostics view. Address the specific alarm (wire break, parameter error, or supply voltage) per Table 5-4 in the manual.
Incorrect module cannot be insertedMechanical coding element mismatchThe DI 16x24VDC ST requires coding element Type A (per datasheet p.2). Verify the correct coding element is installed in the BaseUnit. Only modules with matching mechanical coding can be inserted.

6. Related ET 200SP Modules

The ET 200SP platform includes several digital input module variants to match different channel counts and feature requirements:

Catalog NumberDesignationChannelsKey Difference
6ES7131-6BF01-0AA0DI 8x24VDC BA8Basic variant — reduced feature set
6ES7131-6BF01-0BA0DI 8x24VDC ST8Standard 8-channel version with diagnostics
6ES7131-6BH01-0BA0DI 16x24VDC ST16This guide — 16-channel standard with diagnostics
6ES7131-6BH01-2BA0DI 16x24VDC ST (10-pack)16Identical module, sold in package unit of 10 units (per manual §2.1)

7. Related Guides

GuideDescription
ET 200SP DI 8x24VDC / DQ 8x24VDC GuideInstallation and wiring guide for the 8-channel digital input and output modules in the ET 200SP family.
Allen-Bradley 1734-IB8 POINT I/O GuideEquivalent distributed I/O platform from Allen-Bradley — compare ET 200SP with POINT I/O for 24VDC sink digital input applications.

Reference Documentation

The following Siemens publications were used as the primary data sources for this guide. All technical specifications, terminal assignments, parameter tables, LED states, and diagnostic codes were extracted directly from these manufacturer documents.

PublicationDescriptionDownload
A5E03573442-AG (02/2019)Digital input module DI 16x24VDC ST (6ES7131-6BH01-0BA0) Manual — 32 pages covering properties, wiring/block diagram, parameters/address space, interrupts/diagnostic alarms, technical specifications, and parameter data recordPDF
6ES7131-6BH01-0BA0 DatasheetSiemens product datasheet for the DI 16x24VDC ST module — 4 pages, last modified 02/2026. Includes updated technical specifications, approvals, certifications, and ambient conditions.PDF
ET 200SP BaseUnits ManualManual for ET 200SP BaseUnits — covers BU types, potential groups, terminal assignments, and dimension drawingsPDF
ET 200SP IM 155-6 PN ST ManualManual for the IM 155-6 PN ST interface module — covers PROFINET configuration, station setup, and commissioningPDF

Need a 6ES7131-6BH01-0BA0 or Other ET 200SP Modules?

PLC Exchange stocks Siemens ET 200SP I/O modules with a 2.5-year warranty and same-day shipping. Get pricing in a few hours.