How-To Guide

Siemens SINAMICS G120 CU240E-2 PN Control Unit

Complete setup guide for the SINAMICS G120 CU240E-2 PN control unit: Power Module assembly, control terminal wiring, PROFINET configuration, basic commissioning with BOP-2 or Startdrive, LED status indicators, and fault diagnostics. All specifications verified against the Siemens Operating Instructions (A5E34259001B AA, Edition 04/2014, FW V4.7).

Get a Quote on the 6SL3244-0BB12-1FA0
PROFINET IO Communication
6 DI / 2 AI / 3 DO / 2 AO I/O Count
V/f & Vector Control Modes
G120 / SINAMICS Platform

How-To Guide  ·  Siemens SINAMICS G120  ·  Drive Control Unit Setup

SINAMICS G120 CU240E-2 PN: Installation, Wiring, and Commissioning Guide

6SL3244-0BB12-1FA0 · CU240E-2 PN · PROFINET IO / EtherNet/IP · Startdrive / BOP-2

The 6SL3244-0BB12-1FA0 is a SINAMICS G120 CU240E-2 PN control unit with PROFINET IO and EtherNet/IP communication. It snaps onto a G120 Power Module (PM230, PM240, PM240-2, PM250, PM260, or PM340) to form a complete frequency inverter for 3-phase AC motor control. The CU240E-2 PN features 6 digital inputs, 2 analog inputs, 3 digital outputs (1 relay + 1 transistor + 1 relay), 2 analog outputs, and dual PROFINET ports (X150 P1/P2) with integrated 2-port switch for line topology. The control unit supports V/f control, sensorless vector control, and can be commissioned using a BOP-2 (Basic Operator Panel), IOP (Intelligent Operator Panel), STARTER, or Startdrive (TIA Portal). This guide covers Power Module assembly, control terminal wiring, PROFINET network setup, basic commissioning, and LED/fault diagnostics — all specifications sourced directly from the Siemens Operating Instructions (A5E34259001B AA, Edition 04/2014, FW V4.7) and List Manual (A5E33839529, Edition 09/2020, FW V4.7 SP13).

1. Control Unit Overview

Each SINAMICS G120 inverter comprises a Control Unit and a Power Module (Operating Instructions, Section 3.1, page 23). The Control Unit controls and monitors the Power Module and the connected motor. The Power Modules are available for motors with a power range of 0.37 kW to 250 kW. An optional operator panel (BOP-2 or IOP) snaps onto the top of the Control Unit for local operation and commissioning.

The CU240E-2 Control Units have, in comparison to the CU240B-2, an extended terminal strip with integrated safety functions. The CU240E-2 variants differ with regard to the type of fieldbus and the scope of the integrated safety functions (Operating Instructions, Table 3-2, page 24).

CU240E-2 Technical Data

The following specifications are from the CU240E-2 Technical Data table (Operating Instructions, Section 12.2, pages 305–307).

FeatureDetails
Fieldbus InterfacePROFINET IO, EtherNet/IP — dual RJ45 ports (X150 P1 and P2) with integrated 2-port switch (Section 4.4.3, page 65)
Operating VoltageSupply from Power Module, or external 24 VDC via terminals 31/32 (20.4…28.8 VDC, PELV per EN 61800-5-1, Class 2). Power supply is electrically isolated from the control terminals. (Section 12.2, page 305)
Current ConsumptionMax 0.5 A (Section 12.2, page 305)
Power Loss5.0 W (plus power loss of output voltages) (Section 12.2, page 305)
Digital Inputs6 (DI 0–DI 5); low < 5 V, high > 11 V; 30 V max input; 5.5 mA current consumption; electrically isolated; PNP/NPN switchable; SIMATIC-compatible; 10 ms response time (for debounce time p0724 = 0) (Section 12.2, page 305)
Pulse Input1 (DI 3); max frequency 32 kHz (Section 12.2, page 305)
Analog Inputs2 (AI 0, AI 1); differential input; switchable: 0…10 V, 0/4…20 mA, or −10…+10 V; 12-bit resolution; 13 ms ± 1 ms response time. AI 0 can also be configured as additional digital input: low < 1.6 V, high > 4.0 V (Section 12.2, page 305)
Digital Outputs3 (DO 0, DO 1, DO 2): DO 0 = relay output (NC/NO/COM); DO 1 = transistor output (protection against incorrect voltage polarity); DO 2 = relay output (NC/NO/COM); all 30 V DC, max 0.5 A resistive load; 2 ms update time (Section 12.2, page 306)
Analog Outputs2 (AO 0, AO 1); 0…10 V or 0…20 mA; reference potential “GND”; 16-bit resolution; 4 ms update time (Section 12.2, page 306)
Temperature SensorPTC (short-circuit monitoring 22 Ω, switching threshold 1650 Ω) or KTY84 (short-circuit monitoring < 50 Ω, wire break > 2120 Ω); temperature switch with isolated contact (Section 12.2, page 306)
Fail-Safe Digital Input1 (DI 4 and DI 5 form the fail-safe digital input when basic safety functions are enabled); 30 V max, 5.5 mA; response time: typical 5 ms + debounce (p9651), worst case 15 ms + debounce; typical 6 ms if debounce = 0, worst case 16 ms if debounce = 0 (Section 12.2, page 306)
Safety PFH5 × 10−8 (Probability of Failure per Hour) (Section 12.2, page 306)
Output Voltages+24 V out (terminal 9): 18…28.8 V, max 200 mA, referred to GND (terminal 28); reference for terminals 1, 9, 12, and 26; also reference for terminals 5, 7, and 16 via DI COM1 (terminal 69) and terminals 6, 8, and 17 via DI COM2 (terminal 34). +10 V out (terminal 1): 9.5…10.5 V, max 10 mA (Section 4.4.5.1, page 69; Section 12.2, page 305)
Setpoint Resolution0.01 Hz (Section 12.2, page 305)
USB InterfaceMini-B (for STARTER or Startdrive connection) (Section 12.2, page 306)
Memory CardSD/MMC slot for parameter backup, firmware update, and drive cloning (Section 4.4.2, page 64; Section 3.2, page 25)
Dimensions (W × H × D)73 × 199 × 39 mm (depth valid when mounted on Power Module) (Section 12.2, page 306)
Weight0.49 kg (Section 12.2, page 306)
Operating Temperature0…55 °C (without operator panel); 0…53 °C (PN without operator panel, side-by-side mounting, PM input > 480 V); 0…50 °C (with operator panel installed) (Section 12.2, page 307)
Storage Temperature−40…70 °C (Section 12.2, page 307)
Relative Humidity< 95%, condensation not permissible (Section 12.2, page 307)
Operator PanelBOP-2 (6SL3255-0AA00-4CA1) or IOP (6SL3255-0AA00-4JA0) — snaps onto CU top port; degree of protection with BOP-2: IP55; with IOP: IP54 or UL Type 12 (Section 3.5, page 39)

Compatible Power Modules

The CU240E-2 can be combined with all G120 Power Modules (Operating Instructions, Table 3-4, page 25). The CU240B-2 cannot be combined with the PM340.

Power ModuleInput VoltagePower Range (LO)Notes
PM2303 AC 380–480 V0.37…90 kW (IP20)Pump and fan applications; DC braking only; frame sizes FSA…FSF (Section 3.3, page 26)
PM2403 AC 380–480 V0.37…250 kWStandard applications; dynamic braking via external braking resistor; frame sizes FSA…FSGX (Section 3.3, page 27)
PM240-23 AC 380–480 V0.55…15 kW (IP20)Compact frame; external braking resistor connection; frame sizes FSA…FSC (Section 3.3, page 27)
PM2503 AC 380–480 V7.5…90 kWRegenerative braking (energy feedback to line supply); frame sizes FSC…FSF (Section 3.3, page 27)
PM2603 AC 660–690 V11…55 kWRegenerative braking with sine-wave filter; frame sizes FSD…FSF (Section 3.3, page 27)
PM3401 AC 200–240 V0.12…0.75 kWSingle-phase input; dynamic braking via external braking resistor; frame size FSA only (Section 3.3, page 26)
Control Unit vs Power Module The G120 is a modular system. The Control Unit (CU240E-2 PN) handles motor control algorithms, I/O, and communication. The Power Module (PM230, PM240, etc.) handles the power electronics — AC input, DC bus, IGBT inverter, motor output. You order them separately and snap the CU onto the PM. Different CU variants provide different fieldbus options; the PM determines the power rating and voltage class. (Operating Instructions, Section 3.1, page 23)

2. Hardware Installation

Install components in the following order per the G120 Operating Instructions (Section 4.1, page 41): accessories first, then the Power Module, then the Control Unit.

Attaching the Control Unit to the Power Module

The procedure for connecting Power Modules and Control Units is described in Operating Instructions Section 4.4.1 (page 63):

  1. De-energise the Power Module. Disconnect the AC supply and verify zero voltage at the input terminals. Wait the discharge time specified on the warning labels (Section 1.1, page 13).
  2. Locate the lugs at the rear of the Control Unit in the matching recesses of the Power Module.
  3. Mount the Control Unit onto the Power Module so that it audibly snaps into place. The CU must be fully seated for the internal bus connector to make contact.
  4. To remove the CU: press the release button on the Power Module and withdraw the Control Unit straight forward.
  5. Attach the operator panel (optional): BOP-2 or IOP snaps onto the port at the top of the Control Unit. Power is supplied by the CU — no separate wiring required. Degree of protection with BOP-2: IP55; with IOP: IP54 or UL Type 12 (Section 3.5, page 39).

CU240E-2 Front Panel Interfaces

To access the interfaces at the front of the Control Unit, lift the Operator Panel (if installed) and open the front doors (Operating Instructions, Section 4.4.2, page 64).

ItemDescription
Memory card slotSD/MMC memory card for parameter backup, firmware update, and series commissioning (Section 4.4.2 item 1)
Terminal strips (upper & lower)All control I/O wiring; see Section 3 Terminal Wiring below (Section 4.4.2 item 2)
DIP switches (AI0/AI1)Switch analog inputs between current (I: 0/4…20 mA) and voltage (U: −10/0…10 V) (Section 4.4.2 item 9)
Status LEDsRDY (green/red), BF (red/yellow), LNK1/LNK2 (green) — PROFINET (Section 4.4.2 item 7)
USB portMini-B connector for STARTER or Startdrive PC connection (Section 4.4.2 item 8)
Fieldbus interface (bottom)Dual RJ45 ports X150 P1 and P2 for PROFINET IO / EtherNet/IP; pin 1 = RX+, pin 2 = RX−, pin 3 = TX+, pin 6 = TX− (Section 4.4.3, page 65)
Operator panel port (top)Connection for BOP-2 or IOP — CU supplies power (Section 4.4.2 item 10)
Capacitor Discharge After disconnecting AC power, wait until the discharge time specified on the warning labels has elapsed before working on the drive or Power Module. Internal DC bus capacitors retain lethal voltage. Verify 0 V DC at the DC bus terminals with a voltmeter before touching any internal components. (Operating Instructions, Section 1.1, page 13)

3. Terminal Wiring

All control wiring connects to the CU240E-2 terminal strip. Power wiring (L1/L2/L3 input and U/V/W motor output) connects directly to the Power Module terminals — not to the Control Unit. The CU240E-2 terminal strip is shown in the Operating Instructions, Section 4.4.5.1 (page 69).

CU240E-2 Control Terminal Pinout

Terminal assignments from the CU240E-2 terminal strip diagram (Operating Instructions, Section 4.4.5.1, page 69). Note: the CU240E-2 has an extended terminal strip compared to the CU240B-2, adding terminals for AI 1, AO 1, DI 4, DI 5, DO 1, DO 2, and DI COM2.

TerminalLabelFunction
1+10V OUT10 V reference output for external potentiometer; 9.5…10.5 V, max 10 mA; referred to GND (terminal 2)
2GNDReference ground for terminals 1, 9, 12, and 26
3AI 0+Analog input 0 positive; −10…+10 V or 0/4…20 mA (switchable via DIP switch)
4AI 0−Analog input 0 reference
5DI 0Digital input 0; reference via DI COM1 (terminal 69)
6DI 1Digital input 1; reference via DI COM2 (terminal 34)
7DI 2Digital input 2; reference via DI COM1 (terminal 69)
8DI 3Digital input 3 (also usable as pulse input, max 32 kHz); reference via DI COM2 (terminal 34)
9+24V OUT24 V output (18…28.8 V), max 200 mA; referred to GND (terminal 28); for powering digital inputs
10AI 1+Analog input 1 positive; −10…+10 V or 0/4…20 mA (switchable via DIP switch)
11AI 1−Analog input 1 reference
12AO 0+Analog output 0; 0…10 V or 0…20 mA; 16-bit resolution; referred to GND (terminal 13)
13GNDReference ground for AO 0
14T1 MOTORMotor temperature sensor positive (PTC / KTY84 / bimetallic)
15T2 MOTORMotor temperature sensor negative
16DI 4Digital input 4 (reserved for safety function when basic safety functions are enabled); reference via DI COM1 (terminal 69)
17DI 5Digital input 5 (reserved for safety function when basic safety functions are enabled); reference via DI COM2 (terminal 34)
18DO 0 NCDigital output 0 — normally closed relay contact
19DO 0 NODigital output 0 — normally open relay contact
20DO 0 COMDigital output 0 — relay common; max 0.5 A, 30 V DC
21DO 1+Digital output 1 — transistor output positive; max 0.5 A, 30 V DC; protection against incorrect voltage polarity
22DO 1−Digital output 1 — transistor output negative
23DO 2 NCDigital output 2 — normally closed relay contact
24DO 2 NODigital output 2 — normally open relay contact
25DO 2 COMDigital output 2 — relay common; max 0.5 A, 30 V DC
26AO 1+Analog output 1; 0…10 V or 0…20 mA; 16-bit resolution; referred to GND (terminal 27)
27GNDReference ground for AO 1
28GNDReference ground for terminal 9 (+24V OUT)
31+24V INOptional external 24 V supply positive; 20.4…28.8 V; PELV per EN 61800-5-1; keeps CU powered when PM is de-energised
32GND INReference for terminal 31; 0 V must be connected to PE via low-resistance connection
34DI COM2Digital input common 2 (reference for terminals 6, 8, and 17)
69DI COM1Digital input common 1 (reference for terminals 5, 7, and 16)

Default Terminal Assignments (PROFINET, Default Setting 7)

The factory setting for CU240E-2 Control Units with PROFIBUS or PROFINET interface is Default Setting 7: “Switch over between fieldbus and jogging using DI 3” (Operating Instructions, Section 4.4.5.2, page 71, and Section 4.4.5.3, page 74). The function of the fieldbus interface depends on DI 3.

TerminalInputDefault Function (Setting 7, DI 3 = High — Fieldbus Active)
3/4AI 0No function (speed setpoint via fieldbus PROFIdrive telegram 1)
5DI 0No function
6DI 1No function
7DI 2Acknowledge fault
8DI 3Switchover control (high = fieldbus / low = jog)
10/11AI 1No function
16DI 4No function
17DI 5No function
12/13AO 0Speed actual value (0…10 V)
21/22DO 1Alarm
18/19/20DO 0Fault
23/24/25DO 2No function
26/27AO 1Current actual value (0…10 V)

When DI 3 = low (fieldbus not active), the defaults change: DI 0 = Jog 1, DI 1 = Jog 2. Inverter receives control signals via PROFIdrive telegram 1 when DI 3 = high (fieldbus active). (Operating Instructions, Section 4.4.5.2, page 71)

PROFINET Ports (X150)

The CU240E-2 PN has two RJ45 connector sockets for PROFINET IO at the lower side of the Control Unit (Operating Instructions, Section 4.4.3, page 65).

PortConnectorFunction
X150 P1RJ45PROFINET IO / EtherNet/IP port 1; connect to PROFINET switch or PLC port. Pin 1: RX+, Pin 2: RX−, Pin 3: TX+, Pin 6: TX−
X150 P2RJ45PROFINET IO / EtherNet/IP port 2; integrated 2-port switch supports line (daisy-chain) topology

Wiring Guidelines

Cable routing and shielding requirements from Operating Instructions, Section 4.5.2 (pages 78–80):

  • Route all power cables (line supply, motor, braking resistor) separately from signal and data cables. Maintain a minimum clearance of 25 cm.
  • Signal and data cables may only cross non-filtered power cables at right angles.
  • Use shielded motor cables and shielded signal/data cables.
  • Connect cable shields to the grounded enclosure at both ends with a large surface area connection.
  • Use the shield connection plate of the Control Unit as strain relief.
  • Terminal strip wiring accepts solid or flexible cable: 0.5…1.5 mm²; strip length 9 mm (Section 4.4.6, page 77).
  • If signal cables exceed 30 m, connect an overvoltage protection element between the terminal and the associated reference potential (Section 4.4.6, page 77).
CU240E-2 PN 24 V Short-Circuit Warning The CU240E-2 PN and CU240E-2 PN-F Control Units can be damaged if ALL three of the following conditions occur simultaneously: (1) a short-circuit at the 24 V output on terminal 9 while the inverter is operational, (2) the ambient temperature is at the upper permitted limit, and (3) an external 24 V supply is connected to terminals 31/32 at the upper voltage limit. To prevent damage, ensure all three conditions do not occur at the same time. (Operating Instructions, Section 4.4.5.1, page 70, NOTICE)

4. Commissioning & Basic Parameters

The CU240E-2 PN can be commissioned using the following tools (Operating Instructions, Section 3.5, page 39):

Commissioning Tools

ToolOrder NumberMethod
BOP-2 (Basic Operator Panel)6SL3255-0AA00-4CA1Snaps onto CU top port; two-line display; guided basic commissioning
IOP (Intelligent Operator Panel)6SL3255-0AA00-4JA0Snaps onto CU top port; plain-text menu display; application wizards
STARTER6SL3072-0AA00-0AG0 (DVD)PC software; connects via USB, PROFIBUS, or PROFINET; full parameter access; trace function
Startdrive6SL3072-4CA02-1XG0 (DVD)TIA Portal add-in; connects via USB or PROFINET; full parameter access; drive wizard
SINAMICS PC Inverter Connection Kit 26SL3255-0AA00-2CA0USB cable (3 m) for connecting PC to inverter

Key Commissioning Parameters

The following parameters are used during quick commissioning (Operating Instructions, Section 5.4, pages 90–99). Set p0010 = 1 to enter quick commissioning mode.

ParameterDescriptionTypical Setting
p0003User access level1 = Standard, 2 = Extended, 3 = Expert, 4 = Service (password protected)
p0010Commissioning parameter filter1 = Quick commissioning; 0 = Ready to run
p0100Motor data units / power standard0 = kW (IEC); 1 = HP (NEMA)
p0304Motor rated voltageFrom motor nameplate (V)
p0305Motor rated currentFrom motor nameplate (A)
p0307Motor rated powerFrom motor nameplate (kW or HP)
p0308Motor rated power factor (cosφ)From motor nameplate
p0310Motor rated frequency50 Hz or 60 Hz (from motor nameplate)
p0311Motor rated speedFrom motor nameplate (rpm)
p1080Minimum speed0 rpm (application-dependent)
p1082Maximum speedMotor nameplate speed (rpm)
p1120Ramp-up time10 s default; adjust for application
p1121Ramp-down time10 s default; adjust for application
p3900End quick commissioning1 = calculate motor model and finish; 2 = finish without motor ID; 3 = finish with motor ID at standstill

Quick Commissioning Steps (BOP-2)

Procedure from Operating Instructions, Section 5.4.1 (pages 90–94):

  1. Apply power to the drive. The RDY LED is temporarily orange after power-on. Once it turns green or red, it signals the inverter state (Section 11.1, page 284).
  2. Set p0010 = 1 (quick commissioning mode). On the BOP-2: scroll to p0010, press P to edit, set to 1, press P to confirm.
  3. Enter motor nameplate data: set p0304 (voltage), p0305 (current), p0307 (power), p0308 (cosφ), p0310 (frequency), and p0311 (speed).
  4. Set speed limits: p1080 (minimum speed) and p1082 (maximum speed).
  5. Set ramp times: p1120 (ramp-up) and p1121 (ramp-down).
  6. End quick commissioning: set p3900 = 1. The drive calculates the motor model and writes all parameters. p0010 automatically returns to 0.
  7. Perform a test run with no load on the motor shaft. Verify direction of rotation and ramp behaviour.

PROFINET Configuration

PROFINET communication setup is described in Operating Instructions, Chapter 7.1 (pages 116–120).

  1. Assign a PROFINET device name using Startdrive, STARTER, or a PROFINET configuration tool (e.g., TIA Portal “Accessible devices”). The device name must match the name assigned in the PLC project (Section 7.1.2, page 118; Section 7.1.3, page 118).
  2. Set the IP address via the PROFINET IO controller during commissioning, or configure a fixed IP address on the drive using parameters p8912 (IP address) / p8913 (subnet mask).
  3. Select the I/O telegram in the PLC project. The G120 supports standard telegrams (e.g., Telegram 1: speed setpoint + control word / status word) and PROFIdrive profile telegrams (e.g., Telegram 352 for conveyor applications) (Section 7.1.4, page 119).
  4. Verify link status. The LNK LED(s) on the CU will illuminate green steady on each active PROFINET port. The BF LED will be off once PROFINET data exchange is established (Section 11.1, Table 11-2, page 284).
BOP-2 Navigation (Appendix A.4, pages 349–352) On the BOP-2, press the Up / Down keys to scroll through parameters. Press P to enter edit mode. Use Up / Down to change the value. Press P again to confirm. Press Fn to toggle the display between the parameter number and its current value.
Motor Nameplate Data Is Required The drive must be programmed with accurate motor nameplate data (voltage, current, power, cosφ, frequency, speed) before running. Incorrect values can cause motor overheating, nuisance trips, or poor torque performance. Read all values directly from the motor nameplate — never estimate. (Operating Instructions, Section 5.1, page 83)

5. Diagnostics & Troubleshooting

CU240E-2 PN LED Status Indicators

LED states from Operating Instructions, Section 11.1 (pages 284–285). The RDY LED is temporarily orange after power-on. Two flashing rates are used: slow flashing (2 s period) and quick flashing.

Inverter Diagnostics (Table 11-1, page 284)

RDY LEDBF LEDMeaning
GREEN — onNot relevantThere is presently no fault; drive ready
GREEN — slow flashCommissioning or reset to factory settings in progress
RED — onYELLOW — variable frequencyFirmware update in progress
RED — slow flashRED — slow flashInverter waits until the power supply is switched off and switched on again after a firmware update
RED — fast flashNot relevantThere is presently a fault
RED — fast flashRED — fast flashIncorrect memory card or unsuccessful firmware update

PROFINET Communication Diagnostics (Table 11-2, page 284)

LNK LEDMeaning
GREEN — onThe communication via PROFINET is in order
GREEN — slow flashDevice naming is active
OffNo communication via PROFINET

Safety Function Diagnostics (Table 11-5, page 285)

SAFE LEDMeaning
YELLOW — onOne or more safety functions are enabled, but not active
YELLOW — slow flashOne or more safety functions are active; no safety function faults have occurred
YELLOW — rapid flashThe converter has detected a safety function fault and initiated a STOP response

Common Faults and Alarms

The following are the most common faults and alarms from the Operating Instructions, Section 11.5 (pages 295–301). Fault codes use the format Fxxxxx (faults) and Axxxxx (alarms). Faults require acknowledgement; alarms disappear once the cause is removed (Section 11.3, page 287; Section 11.4, page 290).

CodeDescriptionCorrective Action
F30001OvercurrentCheck motor data and commissioning. Check motor connection (Y/Δ). Check power cable connections for short-circuit or ground fault. Increase acceleration ramp (p1120). Reduce load. (page 300)
F30002DC-link voltage overvoltageIncrease ramp-down time (p1121). Set rounding times (p1130, p1136). Activate DC-link voltage controller (p1240, p1280). Check line voltage (p0210). (page 300)
F30003DC-link voltage undervoltageCheck line voltage (p0210). Check supply connections. (page 300)
F30004Inverter overtemperatureCheck whether fan is running. Check ambient temperature is in permissible range. Check motor load. Reduce pulse frequency. (page 300)
F30005I2t inverter overloadCheck rated currents of motor and Power Module. Reduce current limit (p0640). Reduce p1341 for U/f operation. (page 300)
F30011Line phase failureCheck the inverter’s input fuses. Check the motor feeder cables. (page 301)
F30015Motor cable phase failureCheck motor cables. Increase ramp-up or ramp-down time (p1120). (page 301)
F30021Ground faultCheck power cable connections. Check motor. Check brake connection cables and contacts. (page 301)
F30035Overtemperature, intake airCheck whether fan is running. Check fan filter elements. Check ambient temperature is in permissible range. (page 301)
F30036Overtemperature, inside areaCheck whether fan is running. Check fan filter elements. Check ambient temperature is in permissible range. (page 301)
F07011Motor overtemperatureReduce motor load. Check ambient temperature. Check wiring and connection of sensor at terminals 14–15. (page 297)
F07801Motor overcurrentCheck current limits (p0640). For vector control: check current controller (p1715, p1717). For U/f: check current limiting controller (p1340…p1346). Increase acceleration ramp (p1120) or reduce load. (page 298)
F07807Short-circuit detectedCheck inverter connection on motor side for any phase-phase short-circuit. Rule out interchanged line and motor cables. (page 298)
F07900Motor blockedCheck that motor can run freely. Check torque limits (r1538 and r1539). Check “Motor blocked” parameters (p2175, p2177). (page 298)
F08501Setpoint timeout (PROFINET)Check PROFINET connection. Set the controller into RUN mode. If fault occurs repeatedly, check monitoring time (p2044). (page 299)
A07400DC-link voltage maximum controller activeIncrease ramp-down times. Deactivate Vdc_max control if not needed (p1240 = 0 for vector, p1280 = 0 for U/f). (page 298)
A05000–A05006Power Module overtemperatureCheck ambient temperature, load conditions, duty cycle, and fan operation. (page 297)
A50001PROFINET configuration errorA PROFINET controller is attempting to connect with an incorrect configuration telegram. Check whether “Shared Device” is activated (p8929 = 2). (page 301)

Acknowledging Faults

You have multiple options to acknowledge a fault (Operating Instructions, Section 11.4, page 291):

  1. Identify and resolve the root cause of the fault before clearing.
  2. Via operator panel: acknowledge using the BOP-2 or IOP.
  3. Via digital input: toggle the digital input assigned to “Acknowledge fault” (default DI 2, terminal 7 in default settings 7 and 12).
  4. Via PROFINET: set bit 7 in PROFIdrive control word 1 (r2090.7).
  5. Power cycle: switch the inverter power supply off and on again. Some faults detected during inverter-internal monitoring of hardware and firmware can only be acknowledged by power cycling.
  6. If the fault reappears immediately, the root cause has not been resolved.

6. Related G120 Control Units

The CU240B-2 and CU240E-2 Control Unit families, with order numbers from Operating Instructions, Table 3-1 and Table 3-2 (page 24). The CU240E-2 has an extended terminal strip and integrated safety functions compared to the CU240B-2.

Order NumberVariantFieldbusSafety Functions
6SL3244-0BB00-1BA1CU240B-2USS, Modbus RTU
6SL3244-0BB00-1PA1CU240B-2 DPPROFIBUS DP
6SL3244-0BB12-1BA1CU240E-2USS, Modbus RTUBasic functions (STO)
6SL3244-0BB13-1BA1CU240E-2 FUSS, Modbus RTUExtended functions (STO, SS1, SLS)
6SL3244-0BB12-1PA1CU240E-2 DPPROFIBUS DPBasic functions (STO)
6SL3244-0BB13-1PA1CU240E-2 DP-FPROFIBUS DPExtended functions (STO, SS1, SLS)
6SL3244-0BB12-1FA0CU240E-2 PNPROFINET IO, EtherNet/IPBasic functions (STO) — this guide
6SL3244-0BB13-1FA0CU240E-2 PN-FPROFINET IO, EtherNet/IPExtended functions (STO, SS1, SLS)

7. Related Guides

GuideDescription
PowerFlex 525 Installation GuideAllen-Bradley VFD installation — compare G120 with PowerFlex 525 architecture including terminal wiring and keypad commissioning.
ET 200SP DI 16x24VDC GuideSiemens distributed I/O that connects to the same PROFINET network as the G120 CU240E-2 PN.

Reference Documentation

The following Siemens publications were used as the source for all technical specifications in this guide. Every value in this guide was extracted directly from these documents — no AI memory was used for any technical data.

PublicationDescriptionDownload
G120 CU240B/E-2 Operating InstructionsSINAMICS G120 Converter with the CU240B-2 and CU240E-2 Control Units, Operating Instructions, Edition 04/2014, FW V4.7, A5E34259001B AA. Primary source for all hardware specs, terminal assignments, commissioning procedures, LED diagnostics, and fault codes.PDF
G120 CU240B-2/CU240E-2 List ManualSINAMICS G120 Control Units CU240B-2/CU240E-2, List Manual, Edition 09/2020, FW V4.7 SP13, A5E33839529. Complete parameter descriptions and function diagrams.PDF

Need a SINAMICS G120 Control Unit or Power Module?

PLC Exchange stocks SINAMICS G120 control units and power modules with a 2.5-year warranty and same-day shipping. Get pricing in a few hours.