How-To Guide · Siemens SIMATIC ET 200SP · Distributed I/O System
ET 200SP: System Architecture, Module Selection, Configuration, and Migration Guide
Platform: SIMATIC ET 200SP · Up to 32 I/O modules · PROFINET IO / PROFIBUS DP · TIA Portal / STEP 7
The SIMATIC ET 200SP is Siemens’ compact, high-density distributed I/O system for PROFINET IO and PROFIBUS DP networks. It is the modern successor to the ET 200S and provides a modular architecture built from four primary components: an interface module (IM), BaseUnits for wiring and power distribution, I/O modules for field signal processing, and a server module for backplane termination. With the IM 155-6 PN ST interface module a station takes up to 32 I/O modules and 512 bytes of I/O data (the IM 155-6 PN/2 HF raises this to 64 modules), and the platform handles digital, analog, and specialty I/O in a compact, cabinet-mounted (IP20) design. This guide covers the complete ET 200SP platform — system architecture, interface module and BaseUnit selection, all I/O module types, power supply design, PROFINET configuration in TIA Portal, DIN rail installation, LED troubleshooting, and a detailed migration path from the older ET 200S (6ES7193-4xxx, 6ES7151-3xxx, 6ES7138-4xxx series) to the current ET 200SP (6ES7193-6xxx, 6ES7155-6xxx series).
1. What Is the ET 200SP?
The ET 200SP is Siemens’ distributed I/O platform within the SIMATIC product family. It connects to the higher-level controller over PROFINET IO or PROFIBUS DP (depending on the interface module) and provides field-level signal conditioning for digital inputs, digital outputs, analog inputs, analog outputs, and specialty modules (communication, technology, motor starters). Siemens describes the design as scalable, so a station can be sized to local requirements, from a few modules up to the maximum configuration of the interface module (32 I/O modules with the IM 155-6 PN ST).
The ET 200SP is designed for cabinet-mounted distributed I/O applications where field devices (sensors, actuators, valves, motor starters) need to be connected close to the process rather than wired back to a central controller. Typical installations include:
- Manufacturing lines — conveyor I/O, packaging stations, assembly cells
- Process automation — valve terminal control, analog measurement, temperature monitoring
- Building automation — HVAC control, lighting, energy monitoring
- Water/wastewater — pump stations, remote valve control, level measurement
Key Platform Advantages
| Feature | Benefit |
| Compact footprint | 15 mm and 20 mm BaseUnits for I/O modules, 30 mm BaseUnits for motor starters |
| Push-in terminals | Tool-free wiring on BaseUnits for faster installation |
| Color-coded BaseUnits | Light and dark colors visually separate potential (voltage) groups |
| Hot-swappable I/O modules | Remove and replace modules without disconnecting field wiring (wiring stays on the BaseUnit). With an ST interface module, only one I/O module at a time. |
| Selectable BusAdapter | Choose the PROFINET connection (RJ45, FastConnect, or M12 on the IM 155-6 PN ST; fiber-optic BusAdapters on the IM 155-6 PN/2 HF) |
| Up to 32 modules / 512 bytes | Per station with the IM 155-6 PN ST (up to 64 modules with the IM 155-6 PN/2 HF) |
ET 200SP vs. Allen-Bradley POINT I/O
The ET 200SP is Siemens’ equivalent of Allen-Bradley’s POINT I/O (1734) platform. Both are modular distributed I/O systems with separate terminal bases and I/O modules. ET 200SP uses BaseUnits and communicates via PROFINET to S7 controllers, while POINT I/O uses terminal bases and communicates via EtherNet/IP to Logix controllers. If you work with both platforms, see our
1734-TB POINT I/O Terminal Base Guide for the Allen-Bradley equivalent.
2. System Architecture
Every ET 200SP station is assembled from four component types, mounted left to right on a 35 mm DIN rail. The interface module connects to the controller network, BaseUnits provide field wiring terminals and power distribution, I/O modules process field signals, and a server module terminates the backplane bus at the right end.
Four-Component Breakdown
| Component | Position | Function | Example Part Numbers |
| Interface Module (IM) |
Leftmost |
Network connection to the controller (PROFINET IO or PROFIBUS DP). One per station. The PROFINET connection is made through a plug-in BusAdapter (e.g. 6ES7193-6AR00-0AA0, BA 2xRJ45). |
6ES7155-6AU01-0BN0 (IM 155-6 PN ST), 6ES7155-6AA01-0BN0 (IM 155-6 PN ST bundle with BusAdapter BA 2xRJ45 and server module) |
| BaseUnit (BU) |
Positions 2 through N |
DIN rail mounting, push-in wiring terminals, power distribution via self-assembling P1/P2/AUX voltage buses. One BaseUnit per I/O module. |
6ES7193-6BP00-0DA0 (BU15-P16+A0+2D, light), 6ES7193-6BP00-0BA0 (BU15-P16+A0+2B, dark) |
| I/O Module |
Plugs into each BaseUnit |
Field signal processing: digital inputs/outputs, analog inputs/outputs, specialty (communication, technology). Snaps into the BaseUnit without tools. |
6ES7131-6BH01-0BA0 (DI 16x24VDC), 6ES7132-6BH01-0BA0 (DQ 16x24VDC) |
| Server Module |
Rightmost |
Terminates the ET 200SP backplane bus and completes the station. It must also be configured in the last slot (slot 33 with 32 modules). A missing server module causes a station stop. Included with the IM 155-6 PN ST. |
6ES7193-6PA00-0AA0 |
Station Assembly Order
- Interface Module (leftmost). Mount the IM 155-6 on the DIN rail. Connect the PROFINET cable via the BusAdapter (RJ45 or M12) and supply 24 V DC power.
- BaseUnit + I/O Module pairs. Slide BaseUnits onto the DIN rail to the right of the interface module, one per I/O slot. The first 24 V DC I/O module must sit on a light-colored BaseUnit so its potential group has a supply infeed. Subsequent BaseUnits can be dark-colored (same potential group) or light-colored (new potential group).
- Snap I/O modules into BaseUnits. Each I/O module clicks into its BaseUnit, engaging the backplane connector automatically. The modules are self-coding: the first time a module is plugged in, part of its coding element clicks into the BaseUnit, so a different module type cannot be plugged into that slot afterward.
- Server Module (rightmost). Install the server module at the last position to terminate the backplane bus. A missing server module causes a station stop.
Hot-Swap Advantage
Because all field wiring connects to the BaseUnit (not the I/O module), you can replace a failed I/O module without disconnecting any wires. Pull the old module out of the BaseUnit and plug a matching one in. With the IM 155-6 PN ST only one I/O module may be removed at a time while the station is running (single hot swapping); removing more than one causes a station stop. Pulling a module drops its outputs, and digital output modules may only be removed or inserted with the load switched off.
3. Interface Modules
The interface module is the head of every ET 200SP station. It provides the network connection (PROFINET IO or PROFIBUS DP), distributes power from the 24 V DC supply to the backplane, and handles all communication with the upstream controller. Two PROFINET interface modules are compared below: the IM 155-6 PN ST (Standard, 6ES7155-6AU01-0BN0, also sold as the bundle 6ES7155-6AA01-0BN0) and the IM 155-6 PN/2 HF (High Feature, 6ES7155-6AU01-0CN0). Note that 6ES7155-6AA01-0BN0 is an ST module, not an HF module.
IM 155-6 PN ST vs. IM 155-6 PN/2 HF
| Attribute | IM 155-6 PN ST | IM 155-6 PN/2 HF |
| Article Number | 6ES7155-6AU01-0BN0 (module with server module); 6ES7155-6AA01-0BN0 (bundle with BusAdapter BA 2xRJ45 and server module) | 6ES7155-6AU01-0CN0 |
| Max I/O Modules | 32 ET 200SP + 16 ET 200AL | 64 ET 200SP + 16 ET 200AL |
| Max I/O Data | 512 bytes per station (max. 256 bytes each for input and output per module), dependent on configuration | 1440 bytes per station (max. 288 bytes each for input and output per module), dependent on configuration |
| BusAdapters | BA 2xRJ45, BA 2xFC, BA 2xM12 | BA 2xRJ45, BA 2xFC, BA 2xSCRJ, BA SCRJ/RJ45, BA SCRJ/FC, BA 2xLC, BA LC/RJ45, BA LC/FC |
| Media Redundancy | MRP (client); MRPD no | MRP; MRPD no |
| IRT | Yes, 250 µs to 4 ms in 125 µs frame | Yes |
| Isochronous Mode | No | Yes (bus cycle min. 250 µs) |
| Shared Device | Yes, max. 2 IO controllers | Yes, max. 4 IO controllers |
| Hot Swapping | Single hot swapping (one I/O module at a time) | Multi hot swapping |
| System Redundancy S2 | No | Yes |
| I&M Data | I&M0 to I&M3 | I&M0 to I&M3 |
| Power Supply | 24 V DC, 19.2–28.8 V | 24 V DC (SELV/PELV), 19.2–28.8 V |
| Engineering | STEP 7 (TIA Portal) V14 or higher; STEP 7 V5.5 SP4 or higher | STEP 7 (TIA Portal) V15.1 or higher; other tools via GSD file |
| Best For | Standard stations up to 32 modules | Larger stations, isochronous mode, fiber-optic connection, S2 system redundancy |
BusAdapter Selection
The IM 155-6 PN ST uses a selectable BusAdapter that plugs into the front of the interface module. This allows you to choose the PROFINET connection independently from the interface module itself. The ET 200SP is an IP20 system intended for installation in a control cabinet, whichever BusAdapter is used.
| BusAdapter | Connection | Use Case |
| BA 2xRJ45 (6ES7193-6AR00-0AA0) | 2 x RJ45 sockets | Standard RJ45 bus connectors |
| BA 2xFC (6ES7193-6AF00-0AA0) | 2 x FastConnect terminals for direct connection of the bus cable (no RJ45 plug) | Field-terminated cables without plugs |
| BA 2xM12 | 2 x M12 (D-coded), screw-type or push-pull connectors | Standard M12 or push-pull bus connectors (IM 155-6 PN ST; not listed for the IM 155-6 PN/2 HF) |
4. BaseUnit Selection
Every I/O module in the ET 200SP requires a BaseUnit. The BaseUnit mounts to the DIN rail, provides push-in wiring terminals for field connections, and carries the self-assembling backplane bus (P1, P2, and AUX voltage rails) that distributes power across the station. Choosing the correct BaseUnit is critical — the width, color, terminal type, and AUX configuration must match the I/O module being installed.
BaseUnit Widths
| Width | Designation | Typical Use |
| 15 mm | BU15 | BU types A0/A1 for digital I/O and many analog, communication and technology modules. The module label shows which BU type it needs. |
| 20 mm | BU20 | BU types B0, B1, C0, C1, D0, F0 and U0 for the modules that require them, including type U0 for AC modules (up to 230 V per process terminal). |
| 30 mm | BU30-MSx | ET 200SP motor starters only (BU30-MS1 to MS10). |
Light vs. Dark BaseUnits
The ET 200SP uses a color-coded system to manage potential (voltage) groups within a station. This is one of the most important concepts in ET 200SP system design:
| BaseUnit Color | Function | Voltage Bus Behavior |
| Light-colored | Starts a new potential group | Interrupts the P1, P2, and AUX voltage buses from the left neighbor. Requires its own L+ and M wiring for the field supply. |
| Dark-colored | Continues the existing potential group | Passes the P1, P2, and AUX voltage buses through from the left neighbor. No separate L+ and M wiring needed — power comes from the preceding light-colored BaseUnit. |
First 24 V DC Module Needs a Light-Colored BaseUnit
The first 24 V DC I/O module in the station must sit on a light-colored BaseUnit so it has a supply infeed. (As of IM firmware V3.x a dark BaseUnit is allowed in slot 1 only for AC modules that do not use the P1/P2 voltage buses, such as the DI 4x120..230VAC ST and DQ 4x24..230VAC/2A ST.)
AUX Terminals
Some BaseUnit variants include AUX (auxiliary) terminals that provide additional potential distribution points. On the BU15 type A0 with AUX terminals these are 10 internally bridged terminals for individual use up to 24 V DC/10 A, or as protective-conductor terminals. BaseUnits are available with and without AUX terminals — select based on your wiring requirements.
BaseUnit and BusAdapter Part Numbers
| Article Number | Type | Width | Color | Stock |
| 6ES7193-6BP00-0DA0 | BaseUnit BU15-P16+A0+2D | 15 mm | Light (new potential group) | Quote |
| 6ES7193-6BP00-0BA0 | BaseUnit BU15-P16+A0+2B | 15 mm | Dark (continues potential group) | 5 in stock |
| 6ES7193-6AR00-0AA0 | BusAdapter BA 2xRJ45 (for the interface module, not a BaseUnit) | – | – | 2 in stock |
Push-In Terminals
ET 200SP BaseUnits for I/O modules use push-in terminals. Strip 8 to 10 mm, then insert the wire as far as it will go (solid wires and ferrules push straight in; for flexible wire without a ferrule, open the terminal first by pressing the spring release with a screwdriver). To release a wire, press the spring release with the screwdriver and pull the wire out. Spring releases are color-coded: red = P1, blue = P2. Supply terminals on BU15 BaseUnits are rated 24 V DC, max. 10 A per potential group; check the BaseUnits manual for the rating of each BU type (only specific BU20 types, e.g. type U0, carry up to 230 V).
5. I/O Module Overview
The ET 200SP platform offers a wide range of I/O modules for every application. Modules snap into BaseUnits and are organized by function: digital input (DI), digital output (DQ), analog input (AI), analog output (AQ), and specialty modules. The I/O modules are self-coding: on first insertion part of the module’s coding element clicks into the BaseUnit, so a different module type cannot be plugged into that slot afterward.
Digital Input Modules (DI)
| Article Number | Designation | Channels | Voltage | Key Features |
| 6ES7131-6BH01-0BA0 | DI 16x24VDC ST | 16 | 24 V DC | Standard 16-channel, sink (P-reading), input delay 0.05–20 ms, wire-break diagnostics. 3 in stock. |
| 6ES7131-6BF01-0BA0 | DI 8x24VDC ST | 8 | 24 V DC | Standard 8-channel, input delay 0.05–20 ms, wire-break diagnostics |
For a detailed guide on the DI 16x24VDC ST module including wiring diagrams, TIA Portal configuration, and LED diagnostics, see our ET 200SP DI 16x24VDC Installation Guide.
Digital Output Modules (DQ)
| Article Number | Designation | Channels | Voltage | Key Features |
| 6ES7132-6BH01-0BA0 | DQ 16x24VDC/0.5A ST | 16 | 24 V DC | Standard 16-channel, 0.5 A per channel. 1 in stock. |
| 6ES7132-6BF01-0AA0 | DQ 8x24VDC/0.5A BA | 8 | 24 V DC | Basic 8-channel, 0.5 A per channel |
| 6ES7132-6BD20-0BA0 | DQ 4x24VDC/2A ST | 4 | 24 V DC | High-current 4-channel, 2 A per channel |
Analog Input Modules (AI)
| Article Number | Designation | Channels | Signal Types | Key Features |
| 6ES7134-6HD01-0BA1 | AI 4xU/I 2-wire ST | 4 | Voltage / Current | 4-channel analog input, voltage or current, with 2-wire transmitter support |
| 6ES7134-6GD01-0BA1 | AI 4xI 2-/4-wire ST | 4 | Current | 4-channel current input; check the Siemens data sheet for ranges |
| 6ES7134-6JD00-0CA1 | AI 4xRTD/TC 2/3/4-wire HF | 4 | RTD / Thermocouple / Resistance | High-feature temperature measurement module, 2/3/4-wire RTD, thermocouple |
Analog Output Modules (AQ)
| Article Number | Designation | Channels | Signal Types | Key Features |
| 6ES7135-6HD00-0BA1 | AQ 4xU/I ST | 4 | Voltage / Current | 4-channel analog output, voltage (e.g. 0–10 V, ±10 V) or current (e.g. 4–20 mA). 2 in stock. |
In Stock at PLC Exchange — ET 200SP I/O Modules
We carry a growing selection of ET 200SP modules, all with a 2.5-year warranty and free UPS Ground shipping:
6. ET 200S vs. ET 200SP — Migration Guide
If you are searching for ET 200S part numbers such as 6ES7193-4CD30-0AA0, 6ES7151-3BA23-0AB0, or 6ES7138-4FB04-0AB0, you are looking at the older ET 200S platform. The ET 200S has been superseded by the ET 200SP, which is the current Siemens distributed I/O system. While the ET 200S is still supported, Siemens is actively directing new projects to the ET 200SP.
Looking for ET 200S Parts?
PLC Exchange carries the
newer ET 200SP platform, which is the direct successor to the ET 200S. The ET 200SP offers a smaller footprint, push-in terminals, higher I/O density, and full support in current TIA Portal versions. If you are maintaining an existing ET 200S system and considering a migration, or starting a new project, the ET 200SP is the recommended path forward.
Contact us for migration assistance.
Platform Comparison
| Attribute | ET 200S (Legacy) | ET 200SP (Current) |
| Part Number Prefix | 6ES7193-4xxx (terminal modules), 6ES7151-3xxx (interface), 6ES7138-4xxx (I/O) | 6ES7193-6xxx (BaseUnits), 6ES7155-6xxx (interface), 6ES713x-6xxx (I/O) |
| Module Width | Varies by module | 15 / 20 mm BaseUnits for I/O, 30 mm for motor starters |
| Terminal Type | Screw or spring-clamp terminal modules | Push-in terminals on BaseUnit (tool-free) |
| Max Modules per Station | Up to 63 (varies by IM) | 32 with IM 155-6 PN ST, 64 with IM 155-6 PN/2 HF |
| Max I/O Data | Varies by interface module | 512 bytes per station with IM 155-6 PN ST (1440 bytes with IM 155-6 PN/2 HF), dependent on configuration |
| Potential Group Management | Power module (PM-E) starts each group | Color-coded BaseUnits (light = new group, dark = continue) |
| Network | PROFINET IO, PROFIBUS DP | PROFINET IO, PROFIBUS DP |
| PROFINET Connector | Fixed on interface module | Selectable BusAdapter (RJ45, M12, FC) |
| Configuration Software | Depends on interface module (STEP 7 V5.x / GSD) | IM 155-6 PN ST 6AU01: TIA Portal V14 or higher (HSP 205), STEP 7 V5.5 SP4 or higher with HSP 0241 V4 |
| Hot-Swap I/O | Yes (separate terminal and electronic modules) | Yes (module separates from BaseUnit, wiring stays). Single hot swapping with ST interface modules, multi hot swapping with HF. |
| Isochronous Mode | Depends on interface module | Not with IM 155-6 PN ST; yes with IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0) |
| Status | Legacy platform | Current platform |
Common ET 200S to ET 200SP Part Number Mapping
| ET 200S (Legacy) | Description | ET 200SP Replacement | Description |
| 6ES7151-3BA23-0AB0 | IM 151-3 PN HIGH FEATURE (Interface Module) | 6ES7155-6AU01-0BN0 | IM 155-6 PN ST (Interface Module) |
| 6ES7193-4CD30-0AA0 | Terminal module TM-P15C23-A0 (for a power module) | 6ES7193-6BP00-0DA0 | BaseUnit BU15-P16+A0+2D (light, starts potential group) |
| 6ES7193-4CA70-0AA0 | Fast Connect terminal module TM-E15N24-A1 (5 pieces) | 6ES7193-6BP00-0BA0 | BaseUnit BU15-P16+A0+2B (dark, continues potential group) |
| 6ES7138-4FB04-0AB0 | 4 F-DO PROFIsafe electronics module (ET 200S fail-safe output) | ET 200SP F-DQ module | ET 200SP fail-safe digital output; select the type for the safety application |
| 6ES7131-4BD01-0AA0 | 4DI DC24V (ET 200S) | 6ES7131-6BH01-0BA0 | DI 16x24VDC ST (ET 200SP) |
| 6ES7132-4BD01-0AA0 | 4DO DC24V (ET 200S) | 6ES7132-6BH01-0BA0 | DQ 16x24VDC/0.5A ST (ET 200SP) |
| 6ES7134-4FB01-0AB0 | 2AI U (ET 200S) | 6ES7134-6HD01-0BA1 | AI 4xU/I 2-wire ST (ET 200SP) |
| 6ES7135-4GB01-0AB0 | 2AO I (ET 200S) | 6ES7135-6HD00-0BA1 | AQ 4xU/I ST (ET 200SP) |
Migration Considerations
- Hardware is not interchangeable. ET 200S terminal modules and electronic modules cannot be used in an ET 200SP station, and vice versa. Migration requires replacing the entire station: interface module, BaseUnits, I/O modules, and server module.
- Wiring is different. ET 200S uses screw or spring-clamp terminal modules. ET 200SP uses push-in BaseUnits. All field wiring must be re-terminated during migration.
- Software migration. If your existing project uses STEP 7 V5.x, the IM 155-6 PN ST (6ES7155-6AU01-0BN0) can be configured with STEP 7 V5.5 SP4 or higher with HSP 0241 V4, or with TIA Portal V14 or higher (HSP 205). Some functions need newer engineering versions; check the interface module manual.
- Address mapping. I/O addresses will change during migration. Update all PLC program references (inputs, outputs, diagnostics) to match the new module address assignments.
- Potential groups. ET 200S uses PM-E power modules to start potential groups. ET 200SP uses light-colored BaseUnits. Map your existing power module positions to light-colored BaseUnit positions in the new layout.
7. Technical Specifications
| Parameter | Value |
| Article Number | 6ES7155-6AU01-0BN0 |
| Network | PROFINET IO |
| PROFINET Connector | Selectable BusAdapter (BA 2xRJ45, BA 2xFC, BA 2xM12) |
| Max I/O Modules | 32 |
| Address Space per Station | 512 bytes max., dependent on configuration |
| Address Space per Module | 256 bytes max. each for input and output data |
| Supply Voltage | 24 V DC (SELV/PELV) |
| Supply Voltage Range | 19.2–28.8 V DC, reverse polarity protected |
| Current Consumption | 450 mA rated, 550 mA max. |
| IRT / Shared Device | IRT yes (250 µs to 4 ms); shared device yes (max. 2 IO controllers) |
| Isochronous Mode | No |
| Hot Swapping | Single hot swapping |
| I&M Data | I&M0 to I&M3 |
| Media Redundancy | MRP Client |
BaseUnit Specifications
| Parameter | BU15 (15 mm) | BU20 (20 mm) | BU30 (30 mm) |
| Width | 15 mm | 20 mm | 30 mm |
| Terminal Type | Push-in | Push-in | Push-in |
| Max Voltage | 24 V DC / 10 A (all BU15 types) | Type-dependent: 24 V DC, or up to 230 V AC on BU20 types for AC modules (e.g. U0) | Motor starter BaseUnits (BU30-MSx): 24 V DC and 500 V AC infeed variants |
| Supply Current (L+) | Max. 10 A per potential group | See BaseUnits manual for the BU type | See BaseUnits manual for the BU type |
| Wire Size Range | 0.14–2.5 mm² (AWG 26–14) | See BaseUnits manual for the BU type | See BaseUnits manual for the BU type |
| DIN Rail | 35 mm (EN 60715) | 35 mm (EN 60715) | 35 mm (EN 60715) |
| Color Variants | Light + Dark | Type-dependent (light and dark types) | – |
| AUX Variants | With / Without AUX | Type-dependent | – |
| Voltage Buses | P1, P2, AUX (self-assembling) | Type-dependent | Motor starter infeed (see BaseUnits manual) |
General Station Limits
| Parameter | Value |
| Max I/O Modules per Station | 32 |
| Max I/O Data per Station | 512 bytes with IM 155-6 PN ST (max. 256 bytes each for input and output per module), dependent on configuration |
| Station Max Width | Depends on module mix (15–30 mm per slot) |
| DIN Rail Mounting | 35 mm × 7.5 mm or 35 mm × 15 mm (EN 60715), or SIMATIC system rail |
| Operating Temperature | −30 to +60 °C (horizontal), −30 to +50 °C (vertical) for the IM 155-6 PN ST (current data sheet). The lowest-rated module in the station sets the limit. |
| Relative Humidity | 10% to 95% in operation, without condensation or icing |
8. Power Supply & Wiring
The ET 200SP requires 24 V DC power (SELV/PELV) for both the interface module (backplane electronics) and the field-side I/O modules. Power enters the station at two points: the interface module power terminals and each light-colored BaseUnit that starts a potential group.
Power Supply Requirements
| Supply Point | Voltage | Purpose | Notes |
| Interface Module (IM) Power | 24 V DC (19.2–28.8 V) | Powers the backplane bus electronics, PROFINET controller, and LED indicators | Connect directly to a dedicated 24 V DC supply. Reverse polarity protected. |
| Light-Colored BaseUnit L+ / M | 24 V DC (max. 10 A per potential group) | Powers field-side I/O for the potential group (all modules up to the next light-colored BaseUnit) | Each light-colored BaseUnit needs its own L+ and M infeed, protected externally by a 24 V DC/10 A miniature circuit breaker (type B or C). |
| Dark-Colored BaseUnit | N/A (passed through) | Receives field power from the preceding light-colored BaseUnit via the self-assembling P1/P2/AUX buses | No separate power wiring required. |
Voltage Group Concept
A potential group (also called a voltage group) consists of all directly adjacent I/O modules that share a common field supply voltage. The potential group:
- Begins at a light-colored BaseUnit, which interrupts the P1, P2, and AUX voltage buses from the left and requires its own L+ and M infeed.
- Continues through consecutive dark-colored BaseUnits, which pass the P1, P2, and AUX buses through from the left neighbor.
- Ends at the last dark-colored BaseUnit before the next light-colored BaseUnit or server module.
Separate Potential Groups for Mixed Voltages
Start a new potential group with a light-colored BaseUnit wherever the supply changes; a light-colored BaseUnit isolates the new group from the module on its left. Voltages above SELV/PELV are only permitted on BaseUnit types designed for them (e.g. BU type U0 for AC modules), and must never be fed onto the P1/P2 voltage buses.
Wiring Best Practices
| Practice | Details |
| Wire gauge | 0.14–2.5 mm² (AWG 26–14) for BU15 push-in terminals |
| Strip length | 8 to 10 mm for push-in terminals |
| Ferrules | DIN 46228 ferrules with plastic sleeve, 8 or 10 mm long |
| Supply fusing | Protect each potential-group L+ infeed with a 24 V DC/10 A miniature circuit breaker (type B or C). The BaseUnit has no user fuse. |
| Shielded cable | Use shielded cable for analog signals. The ET 200SP shield connection accessory gives low-impedance contacting of the cable shields. |
9. PROFINET Configuration
The ET 200SP station appears as a PROFINET IO device on the network. The upstream controller (S7-1500, S7-1200, etc.) acts as the PROFINET IO controller and manages the ET 200SP station. Configuration is performed in TIA Portal (STEP 7).
Basic TIA Portal Setup
- Create a new project in TIA Portal and add your controller (e.g., S7-1500 CPU).
- Open Devices & Networks view. The controller appears with its PROFINET interface.
- Add the ET 200SP station. From the Hardware Catalog, expand Distributed I/O → ET 200SP → Interface modules. Drag the IM 155-6 PN ST (or HF) onto the network view.
- Connect to the controller. Draw a PROFINET connection from the controller’s PROFINET port to the ET 200SP interface module. TIA Portal automatically assigns an IP address and device name.
- Open the Device View of the ET 200SP station by double-clicking the interface module. This shows the station rack with empty slots.
- Add I/O modules. From the Hardware Catalog, drag digital, analog, or specialty modules into the station slots. TIA Portal automatically assigns I/O addresses.
- Configure module parameters. Select each module and configure its properties (input delays, diagnostics, channel activation) in the Properties panel.
- Assign the PROFINET device name. Each ET 200SP station needs a unique PROFINET device name. Set this in the IM properties, then assign it to the physical device using Online → Assign PROFINET device name.
- Download to the controller. Compile the project and download to the CPU. The controller will establish the PROFINET connection to the ET 200SP station.
PROFINET Device Name Assignment
Before the controller can communicate with the ET 200SP station, the physical interface module must be assigned a PROFINET device name that matches the name configured in the TIA Portal project. This is done once during commissioning:
| Method | When to Use |
| TIA Portal → Online → Assign PROFINET device name | Standard commissioning. Requires PG/PC connected to the same PROFINET network. |
| SIEMENS PRONETA | Standalone PROFINET network analysis tool: shows the topology and lets you change device names and IP addresses without TIA Portal. |
| Device replacement with topology (LLDP) | When a topology is configured, the IO controller assigns the name to a replacement IM from the neighbor relationships. All devices involved must support LLDP and the configured topology must match the actual one. The device name is also stored on the BusAdapter. |
IP Address Planning
Each ET 200SP station requires a unique IP address on the PROFINET network. Plan your IP address scheme before commissioning. A common practice is to reserve a subnet for I/O devices (e.g., 192.168.1.100–192.168.1.199) and assign stations sequentially.
10. Installation & Mounting
The ET 200SP mounts on standard 35 mm DIN rail per EN 50022. The station is assembled left to right and requires proper mechanical assembly before power-up.
Installation Steps
- Mount the DIN rail. Use a 35 × 7.5 mm or 35 × 15 mm rail to EN 60715 (or a SIMATIC system rail). Ground the rail separately unless it is mounted on grounded, zinc-plated mounting plates. Where the station sees increased vibration and shock, fasten the rail about every 200 mm. Keep at least 20 mm free above the station and 10 mm at the left and right ends for installing and removing modules.
- Install the interface module. With the supply voltage off, hook the IM 155-6 onto the rail and swivel it back until the rail release clicks into place. Screw the BusAdapter onto the front of the interface module (3 to 3.5 mm screwdriver).
- Install BaseUnits. Mount each BaseUnit on the rail to the right of the interface module (or the previous BaseUnit) and slide it left until it latches. Place a light-colored BaseUnit at the start of each potential group.
- Install the server module. Hook the server module (6ES7193-6PA00-0AA0) onto the rail to the right of the last BaseUnit, swivel it back, and slide it left until it latches onto the last BaseUnit. It completes the station and also holds 3 spare fuses.
- Wire field connections. Connect field wiring to the BaseUnit push-in terminals. Wire the L+ and M supply at each light-colored BaseUnit.
- Plug in I/O modules. Insert each I/O module parallel into its BaseUnit until both latches click. Coding is automatic: the coding element on each I/O module transfers to the BaseUnit the first time the module is plugged in, so the slot then only accepts a matching module.
- Apply color identification labels (optional). The module-specific color identification labels are ordered as accessories; the color code printed on each module tells you which label it takes.
- Connect PROFINET and power. Connect the PROFINET cable to the BusAdapter and plug the 24 V DC connector into the interface module.
Server Module Required
The server module (6ES7193-6PA00-0AA0) must be installed at the right end of every ET 200SP station and configured in the last slot. A missing server module causes a station stop, and the interface module flags it with the ERROR/MAINT LED error code for slot 65.
Mounting Orientation
| Orientation | Operating Temperature | Notes |
| Horizontal (standard) | −30 to +60 °C | DIN rail horizontal, modules facing forward. Preferred orientation for maximum thermal rating. |
| Vertical | −30 to +50 °C | DIN rail vertical. Derate maximum temperature by 10 °C due to reduced convection. |
11. Troubleshooting
Interface Module LED Indicators
| LED | State | Meaning |
| RUN | On | Station exchanging data with the IO controller |
| RUN | Flashing | Interface module not configured, deactivated, or starting up |
| RUN / ERROR / MAINT | All off | Supply voltage at the interface module missing or too low |
| ERROR | Flashing | Group error, configured structure differs from actual, invalid configuration, or I/O module parameter error |
| MAINT | On | Maintenance demanded |
| ERROR + MAINT | Flash sequence | Configuration error code: more than one I/O module pulled, or missing server module / backplane bus fault (error location 65) |
| RUN + ERROR + MAINT | All flashing, LK1/LK2 also flashing | Node flash test |
| RUN + ERROR + MAINT | All flashing, LK1/LK2 not flashing | Hardware or firmware defective: run a firmware update, then replace the interface module if it persists |
| PWR | Off | Supply voltage not present or too low |
| LK1 / LK2 (BusAdapter) | On | Ethernet link to a communication partner |
| LK1 / LK2 (BusAdapter) | Off | No Ethernet link -- check the bus cable to the switch / IO controller |
I/O Module LED Indicators
| LED | State | Meaning |
| DIAG | Solid green | Module parameters assigned |
| DIAG | Flashing green | Module not yet parameterized — TIA Portal project not downloaded |
| DIAG | Flashing red | Module diagnostics available (e.g. wire break, supply voltage missing, parameter error) |
| DIAG | Off | Backplane bus supply of the ET 200SP not OK -- check BaseUnit and server module seating |
| PWR | Solid green | Field supply voltage (L+) present at BaseUnit |
| PWR | Off | No field supply voltage — check L+ and M wiring at the light-colored BaseUnit |
| Channel LEDs | Solid green | Channel active (DI: input signal “1”; DQ: output energized) |
| Channel LEDs | Off | Channel inactive (DI: signal “0”; DQ: output de-energized) |
Common Problems and Solutions
| Symptom | Likely Cause | Solution |
| No LEDs on interface module | No 24 V DC supply to the IM | Verify 24 V DC wiring to the IM power connector. Check the external supply protection. Measure voltage at the IM terminals (must be 19.2–28.8 V). |
| RUN LED flashing, no communication | PROFINET device name not assigned or IP conflict | RUN flashing means the IM is not configured, deactivated, or still starting up. Assign the PROFINET device name using TIA Portal (Online → Assign PROFINET device name) and download the configuration. Verify no IP address conflicts on the network. |
| RUN, ERROR and MAINT all flashing (LK not flashing) | Hardware or firmware defect | Run a firmware update; if it persists, replace the interface module. |
| I/O module DIAG LED off | Backplane bus not OK | Verify all BaseUnits are fully seated on the DIN rail. Check that the server module is installed at the right end. Re-seat the affected BaseUnit and module. |
| PWR LED off on I/O module | No field supply voltage at BaseUnit | Verify 24 V DC is wired to L+ and M on the light-colored BaseUnit for this potential group. Check the external supply protection. Verify wire continuity. |
| Modules detected but no I/O data | CPU in STOP mode or project mismatch | Verify the CPU is in RUN mode. Compile and download the TIA Portal project. Ensure the hardware configuration matches the physical station. |
| Wrong module detected in slot | Module does not match TIA Portal configuration | Replace the module with the correct article number, or update the TIA Portal project to match the physical module. Check mechanical coding element. |
| Intermittent communication drops | Loose PROFINET cable or BusAdapter, network congestion | Re-seat the BusAdapter. Check PROFINET cable (RJ45 or M12) for damage. Verify network switch port LED. Check for excessive broadcast traffic. |
| Diagnostic alarm: supply voltage missing | L+ supply dropped below 19.2 V or lost | Measure voltage under load at the BaseUnit. Check for voltage drop on long cable runs. Upgrade power supply or add a closer supply point. |
12. Related Guides & Resources
Related PLC Exchange How-To Guides
Siemens Reference Documentation
| Document | Content |
| ET 200SP System Manual (A5E03576849-AN, 11/2023) | Complete system documentation covering station assembly, wiring, potential groups, and commissioning |
| IM 155-6 PN ST Equipment Manual (A5E03576904-AE, 10/2020) | Interface module configuration, PROFINET setup, LED states, and diagnostics |
| IM 155-6 PN/2 HF Manual (A5E03915895-AH, 10/2018) | High Feature interface module 6ES7155-6AU01-0CN0: properties, functions, technical specifications |
| ET 200SP BaseUnits Equipment Manual (A5E03727049-AN, 06/2025) | BaseUnit types, terminal assignments, potential group rules, dimension drawings |
| Siemens data sheets (6ES7155-6AU01-0BN0, 6ES7155-6AA01-0BN0) | Current technical specifications of the IM 155-6 PN ST and the IM 155-6 PN ST bundle |
Need ET 200SP Modules?
PLC Exchange stocks Siemens ET 200SP interface modules, BaseUnits, digital I/O, and analog I/O. All products ship with a 2.5-year warranty and free UPS Ground shipping. Get pricing in a few hours.