Equipment Manual · Publication A5E03576904 · Siemens AG

SIMATIC ET 200SP IM 155-6 PN ST Interface Module Equipment Manual

This equipment manual covers the SIMATIC ET 200SP IM 155-6 PN ST interface module (6ES7155-6AU01-0BN0). It describes module properties, wiring, parameters, diagnostics, and technical specifications for connecting the ET 200SP distributed I/O system to PROFINET IO. Engineers use this manual alongside the ET 200SP system manual when commissioning or maintaining an ET 200SP station.

Download PDF
6ES7155-6AU01-0BN0 Article Number
32 Max I/O Modules per Station
512 bytes Max I/O Data per Station
10/2020 Edition

Document Preview

Open the full PDF in a new tab  · Publication A5E03576904

Specifications

Supply Voltage

Rated value (DC) 24 V
Permissible range, lower limit (DC) 19.2 V
Permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Short-circuit protection Yes
Mains buffering / stored energy time 10 ms

Input Current and Power

Current consumption (rated value) 450 mA
Current consumption, max. 550 mA
Inrush current, max. 3.7 A
I²t 0.09 A²·s
Infeed power to backplane bus 4.5 W
Power loss, typical 1.9 W

Hardware Configuration

Max. ET 200SP I/O modules 32
Max. ET 200AL modules 16
Max. submodules per station 256
Max. address space per module (input/output) 256 bytes
Max. address space per station 512 bytes
Max. backplane bus length (without interface module) 1 m

PROFINET Interface

Number of PROFINET interfaces 1 (2-port integrated switch)
Transmission speed 100 Mbit/s full duplex (100BASE-TX)
10 Mbps Yes; for Ethernet services
Autonegotiation Yes
Autocrossing Yes
IRT send cycle range 250 µs to 4 ms in increments of 125 µs
Max. IO controllers with shared device 2
PROFINET system redundancy (S2) No
MRP Yes
MRPD No
Compatible BusAdapters BA 2xRJ45, BA 2xFC, BA 2xM12

Isolation

Between PROFINET and all other circuits Yes; 1 500 V AC
Isolation test voltage 707 V DC (type test)
Potential difference between circuits Safety extra low voltage SELV

Ambient Conditions

Operating temperature, horizontal installation 0 °C to 60 °C
Operating temperature, vertical installation 0 °C to 50 °C
Max. installation altitude above sea level 5 000 m

Mechanical

Width 50 mm
Height 117 mm
Depth 74 mm
Weight (approx., without BusAdapter) 147 g

Engineering Software

STEP 7 TIA Portal, minimum version V14
STEP 7 classic, minimum version V5.5 SP4
PROFINET GSD version V2.3

Communication Protocols

Supported industrial networks and field buses for the products covered by this publication.

PROFINET IO (RT) PROFINET IO Device; real-time communication supported from firmware V1.0.0 PROFINET IO (IRT) Isochronous real-time; send cycles 250 µs to 4 ms in 125 µs increments; requires topological configuration PROFINET MRP Media redundancy for ring topology; MRPD not supported PROFIenergy Supported (from interface module firmware V1.0.0) SNMP Supported as an Ethernet service LLDP Used for topology-based device replacement without programming device TCP/IP Open IE communication supported

Certifications & Compliance

Security Level 1 according to Security Level 1 Test Cases V1.1.1 Network loading class 2

Document Contents

Full PDF covers the following topics in detail:

  • Preface
  • Chapter 1: Guide
  • Chapter 2: Product overview
  • Chapter 3: Wiring
  • Chapter 4: Parameters/address space
  • Chapter 5: Interrupts, diagnostics, error, and system messages
  • Chapter 6: Compatibility
  • Chapter 7: Technical specifications
  • Appendix A: Dimension drawing

In-Stock Products Covered by This Document

Every product below is in stock at our Charlotte, NC warehouse and covered by this publication. Ships same-day (orders before 4 PM ET) with 2.5-year warranty included.

Frequently Asked Questions

What is the article number of the IM 155-6 PN ST interface module covered in this manual?
The module covered is 6ES7155-6AU01-0BN0 (IM 155-6 PN ST interface module and server module). A bundle version that includes the BusAdapter BA 2xRJ45 is available under article number 6ES7155-6AA01-0BN0.
How many I/O modules can be connected to a single IM 155-6 PN ST station?
A maximum of 32 I/O modules can be operated per station. The station also supports up to 16 ET 200AL modules via ET-Connection and a maximum of 512 bytes of I/O data.
Which BusAdapters are compatible with the IM 155-6 PN ST?
Three BusAdapter types are compatible: BA 2xRJ45 for standard RJ45 connectors, BA 2xFC for direct connection of the bus cable, and BA 2xM12 for standard M12 or push-pull connectors.
What PROFINET IO functions does the IM 155-6 PN ST support?
The module supports an integrated 2-port switch, isochronous real-time communication (IRT), media redundancy (MRP), shared device (up to 2 IO controllers), prioritized startup, PROFIenergy, module-internal Shared Input/Shared Output (MSI/MSO), device replacement without programming device, configuration control, and station extension via ET-Connection.
What is the minimum update time for PROFINET IO communication?
The minimum update time is 1 ms. For IRT communication, send cycles between 250 µs and 4 ms in increments of 125 µs are supported.
What LED indicators are present on the IM 155-6 PN ST interface module?
The interface module has RUN (green), ERROR (red), MAINT (yellow), and PWR (green, supply voltage) LEDs. Two green link LEDs (LK1 and LK2) on the BusAdapter show the PROFINET port status.
What is the maximum reaction time of the IM 155-6 PN ST that must be considered when calculating fail-safe module reaction times?
The maximum reaction time of the interface module is the configured update time plus 400 µs, but at least 1.4 ms. This value must be included when calculating the overall reaction times of fail-safe modules.