Manual · Publication A5E03573442 · Siemens AG

SIMATIC ET 200SP DI 16x24VDC ST Digital Input Module Manual

This manual covers the SIMATIC ET 200SP Digital Input Module DI 16x24VDC ST (6ES7131-6BH01-0BA0). It describes the module properties, wiring, parameter configuration, address space, interrupts, diagnostic alarms, and technical specifications. The module provides 16 digital inputs at 24 V DC for the ET 200SP distributed I/O system. It can be configured with STEP 7 (TIA Portal) or with a GSD file for PROFINET IO or PROFIBUS DP.

Download PDF
16 channels Digital Inputs
24 V DC Supply Voltage
0.05 ms to 20 ms Input Delay Range
28 g Module Weight

Document Preview

Open the full PDF in a new tab  · Publication A5E03573442

Specifications

General

Article number 6ES7131-6BH01-0BA0
Product type designation DI 16x24VDC ST
HW functional status From FS02
Firmware version V0.0
Usable BaseUnits BU type A0
Color code CC00
I&M data Yes; I&M0 to I&M3

Engineering

STEP 7 TIA Portal, as of version V14
STEP 7, as of version V5.5 SP3
PCS 7, as of version V8.1 SP1
FW update possible No

Supply Voltage

Rated value (DC) 24 V
Permissible range, lower limit (DC) 19.2 V
Permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Current consumption, max. 90 mA
Power loss, typ. 1.7 W

Digital Inputs

Number of digital inputs 16
Input type Sink input (PNP, P-reading)
Input characteristic curve IEC 61131, type 3
Rated input voltage (DC) 24 V
Voltage for signal 0 -30 to +5 V
Voltage for signal 1 +11 to +30 V
Input current for signal 1, typ. 2.5 mA
Input delay (parameterizable) 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms
2-wire sensor permissible quiescent current, max. 1.5 mA

Cable Length

Shielded, max. 1 000 m
Unshielded, max. 600 m

Address Space

Inputs per module 2 bytes; + 2 bytes for QI information

Ambient Conditions

Horizontal installation, min. -30 °C
Horizontal installation, max. 60 °C
Vertical installation, min. -30 °C
Vertical installation, max. 50 °C
Installation altitude above sea level, max. 2 000 m

Dimensions and Weight

Width 15 mm
Height 73 mm
Depth 58 mm
Weight, approx. 28 g

Isolation

Isolation tested with 707 V DC (type test)
Between channels and backplane bus Yes
Between channels No
Between channels and power supply of the electronics No

Catalog Number Format

How to read an Allen-Bradley SIMATIC ET 200SP catalog number. Each position encodes a specific configuration attribute.

Position
Meaning
Example
Article number, 1 unit
DI 16x24VDC ST, number in package unit: 1
6ES7131-6BH01-0BA0
Article number, 10 units
DI 16x24VDC ST, number in package unit: 10
6ES7131-6BH01-2BA0

Communication Protocols

Supported industrial networks and field buses for the products covered by this publication.

PROFINET IO GSD file GSDML V2.3; supports configuration with STEP 7 TIA Portal V14 or higher PROFIBUS DP GSD file Revision 3 and 5 or higher; parameter length 4 bytes with PROFIBUS GSD configuration

Document Contents

Full PDF covers the following topics in detail:

  • Preface
  • Documentation guide
  • Product overview and module properties
  • Connecting: wiring and block diagram
  • Parameters and address space configuration
  • Interrupts and diagnostic alarms
  • Technical specifications
  • Appendix: Parameter data record structure (data record 128)

In-Stock Products Covered by This Document

Every product below is in stock at our Charlotte, NC warehouse and covered by this publication. Ships same-day (orders before 4 PM ET) with 2.5-year warranty included.

Frequently Asked Questions

How many digital inputs does the DI 16x24VDC ST module provide?
The module provides 16 digital inputs operating at 24 V DC. Inputs are sink type (PNP, P-reading) and conform to IEC 61131, type 3.
What input delay values can be configured per channel?
Input delay is configurable per channel with the following values: 0.05, 0.1, 0.4, 0.8, 1.6, 3.2, 12.8, and 20 ms. An additional delay of 30 to 500 µs depending on line length also applies.
What diagnostic interrupts does the module support?
The module generates diagnostic interrupts for three events: wire break, parameter assignment error, and missing supply voltage. The DIAG LED flashes when a diagnostics event occurs.
What resistor is required when wire-break detection is enabled?
When wire-break detection is configured, a resistor of 25 kΩ to 45 kΩ must be connected in parallel to each mechanical transducer contact so that the required quiescent current can flow when contacts are open.
Which BaseUnit type is required for this module?
The DI 16x24VDC ST requires BU type A0. For 2-wire, 3-wire, and 4-wire connections, a Potential isolation module must be added alongside the BU type A0.
How can module parameters be changed while the system is in RUN mode?
Parameters can be reassigned in RUN using the WRREC instruction to transfer data record 128 to the module. Parameters set in STEP 7 are not permanently overwritten and become valid again after a CPU restart.
What are the operating temperature limits for horizontal and vertical mounting?
For horizontal installation, the operating temperature range is -30 °C to 60 °C. For vertical installation, the range is -30 °C to 50 °C.