Installation Instructions · Publication DRIVES-IN001 · Rockwell Automation
Wiring and Grounding Guidelines for PWM AC Drives
This installation instructions publication from Rockwell Automation covers wiring and grounding for pulse-width modulated (PWM) AC drives. It addresses wire and cable selection, power distribution system configurations, grounding practices, EMI mitigation, reflected wave effects, and motor cable length restrictions. The document applies to PowerFlex 4, 4M, 40, 400, 520-Series, 70, 700, 700H, 700L, 700S, 753, 755, 755T, 1336 PLUS II, 1336 IMPACT, 1305, and 160 drives. It is intended for qualified personnel who plan and design PWM AC drive installations.
Download PDFDocument Preview
Open the full PDF in a new tab · Publication DRIVES-IN001
Specifications
Recommended Cable Design Types
| Type 1: max wire size | 2 AWG; 600V, 90 °C XHHW2/RHW-2; 4 tinned copper conductors with XLPE insulation |
|---|---|
| Type 2: max wire size | 2 AWG; 600V, 90 °C RHH/RHW-2; 4 tinned copper conductors with XLPE plus one shielded pair of brake conductors |
| Type 3: max wire size | 500 MCM AWG; Tray-rated 600V, 90 °C RHH/RHW-2; 3 tinned copper conductors with XLPE and 3 bare copper grounds, PVC jacket |
| Type 4: max wire size | 500 MCM AWG; Tray-rated 600V, 90 °C RHH/RHW-2; for water/caustic/crush-resistance; Class I and II, Division I and II locations |
| Type 5: max wire size | 500 MCM AWG; Tray-rated 2000V, 90 °C; 3 tinned copper conductors with XLPE and 3 bare copper grounds, PVC jacket; 690V applications |
Temperature Rating Requirements
| Ambient 50 °C (122 °F) | Use 90 °C (194 °F) wire (required for UL) |
|---|---|
| Ambient 40 °C (104 °F) | Use 75 °C (167 °F) wire (required for UL) |
| Wire gauge basis | Requirements and recommendations based on 75 °C (167 °F) rating; do not reduce gauge when using higher temperature wire |
Ground Conductor Configuration
| Drives up to and including 200 Hp (150 kW) | Cable with one ground conductor |
|---|---|
| Drives larger than 200 Hp (150 kW) | Cable with three ground conductors, spaced symmetrically around power conductors |
| Ground conductor rating | Must be rated for full drive ampacity |
DH+ / Remote I/O Cable Length vs. Communication Rate
| 57.6 Kbps | 3048 m (10,000 ft) maximum |
|---|---|
| 115.2 Kbps | 1524 m (5000 ft) maximum |
| 230.4 Kbps | 762 m (2500 ft) maximum |
Recommended Signal Wire: Analog and Encoder
| Standard analog I/O | 0.750 mm² (18 AWG), twisted pair, 100% shield with drain; 300V, 75…90 °C |
|---|---|
| Remote pot | 0.750 mm² (18 AWG), 3-conductor, shielded |
| Encoder/Pulse I/O < 30.5 m (100 ft) | 0.196 mm² (24 AWG), individually shielded |
| Encoder/Pulse I/O 30.5…152.4 m (100…500 ft) | Signal: 0.196 mm² (24 AWG) individually shielded; Power: 0.750 mm² (18 AWG) |
| Encoder/Pulse I/O 152.4…259.1 m (500…850 ft) | Signal: 0.196 mm² (24 AWG) individually shielded; Power: 0.750 mm² (18 AWG); Combined: 0.750 mm² (18 AWG) individually shielded pair |
AC Line Impedance Thresholds (General Rules)
| Drives without built-in inductors: add line impedance when | Transformer kVA > 10x drive kVA, or percent source impedance per drive < 0.5% |
|---|---|
| Drives with built-in inductors: add line impedance when | Transformer kVA > 20x drive kVA, or percent source impedance per drive < 0.25% |
| Voltage imbalance threshold | Use input line reactor when line voltage imbalances exceed 2% |
Communication Protocols
Supported industrial networks and field buses for the products covered by this publication.
Document Contents
Full PDF covers the following topics in detail:
- Preface
- Chapter 1: Wire/Cable Types
- Chapter 2: Power Distribution
- Chapter 3: Grounding
- Chapter 4: Best Practices
- Chapter 5: Reflected Wave
- Chapter 6: Electromagnetic Interference
- Appendix A: Motor Cable Length Restrictions
Frequently Asked Questions
Which Allen-Bradley drive families does this publication cover?
What wire material is required for Allen-Bradley drive terminal connections?
When should shielded motor cable be used instead of unshielded cable?
What is the minimum wire insulation thickness required for drive installations?
When is a line reactor or additional transformer recommended in front of a PWM drive?
What grounding system is recommended for PWM AC drive installations?
How should control wires be separated from power wires?
Disclaimer
Disclaimer: PLC Exchange is an independent reseller and is not an authorized distributor, affiliate, licensee, partner, or agent of Allen-Bradley / Rockwell Automation. All product information on this page is compiled from publicly-available manufacturer publications, technical data sheets, and catalog sources, each of which remains the copyright of its originating manufacturer. We make no representation or warranty, express or implied, regarding the accuracy, completeness, timeliness, or fitness for any particular purpose of the specifications or descriptions shown — content may contain errors, omissions, or out-of-date information. Product images are the property of their respective manufacturers, trademark owners, and source publications, and are displayed solely for identification purposes under the nominative fair use doctrine; images are representative and may depict a different configuration or catalog variant than the exact product listed. Purchasers should independently verify specifications against the current manufacturer publication before placing an order. All product names, trademarks, service marks, and registered trademarks are the property of their respective owners, and their use does not imply endorsement or affiliation.