Operating Instructions · Publication C79000-G8976-C284 · Siemens AG

SCALANCE X-200 Industrial Ethernet Switch Operating Instructions

This document is the operating instructions for the SIMATIC NET SCALANCE X-200 and X-200IRT product families of Industrial Ethernet switches. It covers installation, wiring, power supply connection, LED diagnostics, technical specifications, approvals, and network security recommendations. The instructions apply to more than 30 device variants including X-200, XF-200, X-200IRT, XF-200IRT, and PRO models. It is intended for qualified personnel commissioning Industrial Ethernet networks in bus, star, and ring topologies.

Download PDF
10/100 Mbps Transmission Rate
26 km Max Optical Range (Single Mode)
5 km Max Optical Range (Multimode)
02/2019 Edition

Document Preview

Open the full PDF in a new tab  · Publication C79000-G8976-C284

Specifications

Multimode Fiber-Optic Transmission

Transmission speed 100 Mbps
Transmission mode 100Base-FX according to IEEE 802.3
Connectors BFOC sockets
Wavelength 1300 nm
Core diameter 50 or 62.5 μm
Outer diameter 125 μm
Light source LED
Maximum segment length 5 km

Single Mode Fiber-Optic Transmission

Transmission speed 100 Mbps
Transmission mode 100Base LX
Connectors BFOC sockets
Wavelength 1310 nm
Core diameter 9 μm
Outer diameter 125 μm
Light source LED
Maximum segment length 26 km

Power Supply (X-200 Terminal Block)

Supply voltage 24 VDC (TS devices: 12 to 24 VDC)
Cable cross section (X-200) 2.5 mm²
Cable cross section (XF-200) 1.5 mm²
Redundant supply Yes (two isolated inputs; no load distribution)

Wiring Rules: Terminal Blocks

Flexible cable cross section (without ferrule) 0.25 to 2.5 mm² (AWG 24 to 13)
Flexible cable cross section (with ferrule) 0.25 to 2.5 mm² (AWG 24 to 13)
TWIN wire end ferrule 0.5 to 1 mm² (AWG 20 to 17)
Stripped length 8 to 10 mm

Signaling Contact

Maximum load 100 mA, SELV 24 VDC
Contact type Floating switch (relay contact)

Installation Clearance

Below device At least 10 cm
Above device At least 10 cm

IRT-PRO Power Supply Loop-Through Limits

Max current at +40 °C 16 A per feed (L1+/N1 and L2+/N2)
Max current at +50 °C 12 A per feed
Max current at +60 °C 8 A per feed
Max current at +70 °C (X204IRT PRO only) 6 A per feed

Communication Protocols

Supported industrial networks and field buses for the products covered by this publication.

PROFINET IO UDP/34964, UDP/1026, UDP/1027 (dynamic); TCP/84 for PROFINET IO Service. Open by default. SSH TCP/22. Open by default. Authenticated and encrypted. HTTPS TCP/443. Open by default. Authenticated and encrypted. HTTP TCP/80. Open by default. Authenticated, not encrypted. SNMP (SNMPv3) UDP/161. Configurable. SNMPv3 provides authentication and encryption. Telnet TCP/23. Configurable. Authenticated, not encrypted. SNTP / NTP (secure) UDP/123. Configurable. DHCP UDP/67, UDP/68. Configurable. Closed by default. TFTP UDP/69. Configurable. Closed by default. Not recommended for secure applications. HRP / MRP Ring redundancy protocols supported. Redundancy manager function configurable via SET button or WBM. LLDP Topology support (LLDP) supported on all product variants.

Certifications & Compliance

CE mark UL approval per UL 60950-1 CSA approval per CSA C22.2 No. 60950-1-03 CSA Certification for Industrial Control Equipment per CSA C22.2 No. 142-1987 FM approval (Class I, Division 2, Groups A, B, C and D; Class I, Zone 2, Group IIC) ATEX: II 3G Ex nA IIC T4 Gc; II 3 (2) G Ex nA [op is Gb] IIC T4 Gc for some devices IECEx: Ex nA IIC T4 Gc; Ex nA [op is Gb] IIC T4 Gc for some devices Railway standard EN 50155 (TS variants) Railway standard DIN EN 45545-2+A1 (X204-2 TS and X204-2LD TS) CLASS 1 LASER Product: FDA and IEC marking (listed optical devices) WEEE directive 2012/19/EU

Document Contents

Full PDF covers the following topics in detail:

  • Introduction
  • Safety notices
  • Recommendations on network security
  • Description of the device
  • Installation
  • Connecting up
  • Technical specifications
  • Approvals
  • Appendix A: Dimension drawings
  • Appendix B: Test of mechanical stability

Frequently Asked Questions

Which device variants are covered by this operating instructions document?
The instructions cover all devices of the SCALANCE X-200 and XF-200 product groups, including X204-2, X204-2TS, X204-2FM, X204-2LD, X204-2LD TS, X206-1, X206-1LD, X208, X208PRO, X212-2, X212-2LD, X216, X224, XF204, XF204-2, XF206-1, XF208, and all X-200IRT and XF-200IRT variants including PRO models.
What transmission rates and topologies do the SCALANCE X-200 switches support?
The X-200 IE switches support transmission rates of 10/100 Mbps and are suited for Industrial Ethernet networks in bus, star, and ring structures. X-200IRT variants additionally support isochronous real-time (IRT) communication using a combination of cut-through and store-and-forward switching methods.
How is the C-PLUG used and what does it store?
The C-PLUG is an exchangeable storage medium for configuration and project engineering data of the basic device. If an empty C-PLUG is inserted, all configuration data is saved to it at startup. When replacing a failed device, the C-PLUG from the old device is inserted into the replacement device, which then starts with the same configuration. The C-PLUG must be inserted and removed only when power is off.
What installation methods are available for the X-200 IE switches?
X-200 IE switches can be installed on a 35 mm DIN rail complying with DIN EN 60715, on a SIMATIC S7-300 standard rail, or by wall mounting. XF devices (flat design) can only be installed on a 35 mm DIN rail. A minimum clearance of 10 cm above and below the device must be maintained for convection ventilation.
What power supply voltage is required and is redundant supply supported?
The standard supply voltage is 24 VDC (TS devices accept 12 to 24 VDC). Most X-200 variants support redundant power supply via two isolated inputs with no load distribution; the supply with the higher output voltage supplies the device alone. IRT PRO variants (X201-3P IRT PRO, X202-2P IRT PRO, X204IRT PRO) do not have a redundant power supply.
What protocols are available for device management and which are recommended for secure use?
Available management protocols include SSH (TCP/22), HTTPS (TCP/443), HTTP (TCP/80), Telnet (TCP/23), SNMP (UDP/161), SNTP/NTP (UDP/123), DHCP, and TFTP. The document recommends using SSH instead of Telnet, HTTPS instead of HTTP, FTPS instead of TFTP, NTP instead of SNTP, and SNMPv3 instead of SNMPv1/v2c to ensure encrypted and authenticated communication.
What approvals do the SCALANCE X-200 switches hold?
The devices hold CE, UL (UL 60950-1), CSA (CSA C22.2 No. 60950-1-03 and No. 142-1987), FM (Class I Division 2 Groups A-D; Class I Zone 2 Group IIC), ATEX and IECEx approvals for selected optical variants, FDA and IEC CLASS 1 LASER Product certification for optical devices, and railway standard EN 50155 approval for TS variants. TS variants also meet DIN EN 45545-2+A1 fire protection requirements.