Equipment Manual · Publication A5E03915895 · Siemens AG

SIMATIC ET 200SP IM 155-6 PN/2 HF Interface Module Manual

This equipment manual covers the SIMATIC ET 200SP interface module IM 155-6 PN/2 HF (order number 6ES7155-6AU01-0CN0). It describes module properties, wiring, parameters, address space, diagnostics, and technical specifications. The manual also covers PROFINET IO functions including IRT, MRP, shared device, system redundancy S2, and Module-to-Module Communication. Engineers commissioning or maintaining ET 200SP distributed I/O systems with STEP 7 or TIA Portal will find this document the primary reference for the IM 155-6 PN/2 HF.

Download PDF
6ES7155-6AU01-0CN0 Article Number
Up to 4 Shared Device IO Controllers
64 ET 200SP + 16 ET 20… Max I/O Modules
10/2018 Edition

Document Preview

Open the full PDF in a new tab  · Publication A5E03915895

Specifications

Supply Voltage

Rated value (DC) 24 V
Permissible range, lower limit (DC) 19.2 V
Permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Mains/voltage failure stored energy time 10 ms

Input Current and Power

Current consumption, max. 700 mA
Inrush current, max. 4.5 A
I²t 0.25 A²·s
Power loss, typ. 2.4 W

Address Space

Address space per module, max. 288 bytes (input and output data respectively)
Gross data length, max. (without S2) 1440 bytes
Gross data length, max. (with S2) 1000 bytes
Net data length, min. (without S2) 933 bytes
Net data length, min. (with S2) 493 bytes

PROFINET Interface

Number of PROFINET interfaces 1 (2-port integrated switch)
Transmission procedure 100 Mbit/s full duplex (100BASE-TX)
Autonegotiation Yes
Autocrossing Yes
Minimum update time 250 µs
IRT bus cycle time 250 µs to 4 ms in 125 µs steps (high performance)
Isochronous mode jitter, max. 1 µs
Max. IO controllers with shared device 4

Hardware Configuration

Modules per rack, max. 64 ET 200SP I/O modules + 16 ET 200AL modules
Backplane bus length, max. 1 m (without interface and server module)
Submodules per station, max. 256

Ambient Conditions

Operating temperature, horizontal, min. -30 °C (no condensation)
Operating temperature, horizontal, max. 60 °C
Operating temperature, vertical, max. 50 °C
Installation altitude, max. 2000 m (greater altitudes on request)

Mechanical

Width 50 mm
Height 117 mm
Depth 74 mm
Weight (approx., without BusAdapter) 120 g

Isolation

Isolation tested with 707 V DC (type test)
Between PROFINET and all other circuits Yes
Between backplane bus and electronics No

Communication Protocols

Supported industrial networks and field buses for the products covered by this publication.

PROFINET IO (RT) Cyclic real-time data exchange using provider-consumer model PROFINET IO (IRT) Isochronous real-time communication; reserved bandwidth within send clock; bus cycle time min. 250 µs; requires topology configuration PROFINET MRP Media Redundancy Protocol; ring topology for alternative communication path on link failure PROFINET System Redundancy S2 Supports redundant ARs; compatible with S7-400H (from FW V3.0) and S7-1500R/H (from FW V4.2) Open IE (TCP/IP) Yes SNMP Supported Ethernet service LLDP Supported; required for device replacement with topological configuration

Certifications & Compliance

Security Level according to Security Level 1 Test Cases V1.1.1 Network loading class 3

Document Contents

Full PDF covers the following topics in detail:

  • Preface
  • Chapter 1: Guide
  • Chapter 2: Product overview
  • Chapter 3: Wiring
  • Chapter 4: Parameters/address space
  • Chapter 5: Interrupts, error messages, diagnostics and system alarms
  • Chapter 6: Compatibility
  • Chapter 7: Technical specifications
  • Appendix A: Dimension drawing

In-Stock Products Covered by This Document

Every product below is in stock at our Charlotte, NC warehouse and covered by this publication. Ships same-day (orders before 4 PM ET) with 2.5-year warranty included.

Frequently Asked Questions

What is the article number for the IM 155-6 PN/2 HF interface module covered in this manual?
The article number is 6ES7155-6AU01-0CN0.
How many I/O modules can be connected to the IM 155-6 PN/2 HF?
The interface module supports a maximum configuration of 64 ET 200SP I/O modules plus 16 ET 200AL modules, with a maximum backplane bus length of 1 m (excluding the interface and server modules).
What PROFINET IO functions does the IM 155-6 PN/2 HF support?
The module supports real-time (RT) and isochronous real-time (IRT) communication, prioritized startup, device replacement without a programming device, media redundancy (MRP), shared device (up to 4 IO controllers), MSI/MSO, isochronous mode (min. 250 µs), system redundancy S2, PROFIenergy, configuration control, fail-safe modules, Multi Hot Swap, and Module-to-Module Communication (MtM).
What BusAdapters are compatible with the IM 155-6 PN/2 HF?
Compatible BusAdapters are: BA 2xRJ45, BA 2xFC, BA 2xLC, BA 2xSCRJ, BA SCRJ/RJ45, BA SCRJ/FC, BA LC/RJ45, and BA LC/FC. These support copper RJ45, direct bus cable connection (FC), glass fiber-optic (LC), and POF/PCF fiber-optic (SCRJ) connections.
What is the maximum I/O data length for the IM 155-6 PN/2 HF without system redundancy S2?
Without system redundancy S2, the maximum gross data length is 1440 bytes each for input and output data. The minimum guaranteed net data length without shared device is 933 bytes. For shared device with 2 IO controllers the gross limit is 1440 bytes in total; with more than 2 IO controllers it is 360 bytes per IO controller.
Which configuration software versions are required to use the IM 155-6 PN/2 HF?
The module can be configured via a GSD file (GSDML V2.3), via STEP 7 V5.5 SP4 with HSP 250/255, or via STEP 7 TIA Portal V15.1 or higher. Some functions such as Module-to-Module Communication (MtM) and system redundancy S2 to S7-1500R/H require TIA Portal as of V15.1.
What happens when the supply voltage falls below 19.2 V DC on the IM 155-6 PN/2 HF?
If the supply voltage falls below 19.2 V DC, an undervoltage diagnostics alarm is reported as incoming (Maintenance demanded). When the voltage subsequently rises above 20.4 V DC, the diagnostics alarm is reported as outgoing. This event also triggers the yellow MAINT LED on the interface module.