Technical Data · Publication 5094-TD001 · Rockwell Automation
FLEX 5000 I/O Module Specifications
Complete specifications for the Allen-Bradley FLEX 5000 distributed I/O platform on Bulletin 5094. Covers digital, analog, HART, and safety I/O modules plus EtherNet/IP adapters (RJ45 and SFP variants), terminal base assemblies, and XT (extended-temperature) variants. FLEX 5000 modules are used as remote I/O for ControlLogix 5580, CompactLogix 5380, and CompactLogix 5480 controllers and configured with Studio 5000 Logix Designer.
Download PDFDocument Preview
Open the full PDF in a new tab · Publication 5094-TD001
Specifications
I/O Performance & Capacity
| Digital input channels | 8 (5094-IM8) / 16 (IA16, IB16, OW8I relay) / 32 (IB32) |
|---|---|
| Digital output channels | 8 (OB8, OW8I) / 16 (OA16, OB16) / 32 (OB32) |
| Analog input channels | 8 (IF8 current/voltage, IY8 current/voltage/RTD/TC, IF8IH 8-ch isolated HART) |
| Analog output channels | 8 (OF8 current/voltage, OF8IH 8-ch isolated HART) |
| Analog resolution | 16 bits at 10 Hz notch filter (IF8/IY8/OF8); Sigma-Delta dual 24-bit multiplexed ADC |
| Analog accuracy | 0.05% full scale at 25 °C (voltage and current modes) |
| Max local I/O modules per adapter | Up to 8 FLEX 5000 I/O modules per 5094-AENTR/AEN2TR adapter (limited by backplane current and slot count) |
| Data format | IEEE 754 32-bit floating point (analog) |
| Producer/Consumer architecture | Supported — input and output data shared among multiple Logix 5000 controllers |
Communication
| Network protocol | EtherNet/IP (CIP on Ethernet), ODVA conformance tested |
|---|---|
| Adapter ports (RJ45) | 2 copper RJ45 on 5094-AENTR, -AENTRXT, -AEN2TR, -AEN2TRXT |
| Adapter ports (SFP) | 2 SFP cages on 5094-AENSFPR, -AENSFPRXT, -AEN2SFPR, -AEN2SFPRXT; 3.3V/1W slots, 0.3 W/m² optical power |
| Supported SFP modules | 1783-SFP100FX/100LX/100DEXC, 1783-SFP1GSX/1GLX/1GEXE/1GZX/1GTE, 11783-SFP100DEXC, 1783-SFP100ZXC |
| Network topology | Linear, Star, Device-Level Ring (DLR) with beacon-based ring protocol |
| CIP Sync | Supported — transport clock and slave-only ordinary clock (time-stamping + scheduled outputs) |
| Removal/insertion under power (RIUP) | Supported, up to 4 consecutive empty slots permitted |
| Module keying | Mechanical keying + electronic keying via Studio 5000 Logix Designer |
Physical & Mounting
| Mounting | EN 60715 DIN rail, 35 × 7.5 mm (199-DR1 / 46277-4 zinc-plated chromate-passivated) |
|---|---|
| Mounting orientations | Horizontal, horizontal-inverted, vertical, vertical-inverted (all four supported) |
| System architecture | EtherNet/IP adapter + I/O modules on individual mounting bases (MB) and removable terminal blocks (RTB), ordered separately |
| Minimum clearance | 25.4 mm (1.00 in.) on all sides for ventilation |
| DIN rail end anchors | 1492-EAJ35 or 1492-EAHJ35 required at both ends under vibration/shock |
| I/O module dimensions (H×W×D) | 54.0 × 94.0 × 87.0 mm (2.13 × 3.70 × 3.43 in.) — digital/analog modules |
| Mounting base (5094-MB/MBXT) dimensions | 85.0 × 94.0 × 37.5 mm (3.35 × 3.70 × 1.48 in.); 71 g (0.16 lb) |
| EtherNet/IP adapter dimensions | 92.7 × 94.0 × 96.5 mm (3.65 × 3.70 × 3.80 in.); 400 g (0.88 lb) |
| Wire size — signal | 0.34–2.5 mm² (22–14 AWG) solid/stranded copper, 105 °C rated, 1.2 mm (3/64 in.) max insulation |
| Wire size — power RTB | 2.5 mm² (14 AWG) Cu multi-strand |
| Screw RTB torque | 0.4 N·m (3.5 lb·in) |
| Functional earth torque | 0.5 N·m (4.4 lb·in) |
| Enclosure rating | None (open-style) — installation inside enclosure required |
Power
| MOD Power input range | 18–32V DC (24V DC nominal) |
|---|---|
| MOD Power — 5094-AENTR/AENTRXT | 1,250 mA @ 18-32V DC; 3,200 mA inrush for 100 ms |
| MOD Power — 5094-AEN2TR/AEN2TRXT | 1,880 mA @ 18-32V DC; 5,700 mA inrush for 100 ms |
| Backplane current — adapter | 15V DC @ 1,130 mA (AENTR) / 1,800 mA (AEN2TR) / 1,730 mA (AEN2SFPR) |
| SA Power range (DC modules) | 18–32V DC |
| SA Power range (AC modules) | 74–132V AC @ 47-63 Hz (IA16) / 159–264V AC (IM8) / 85–264V AC (OA16) |
| SA Power passthrough | 10 A max per terminal base assembly |
| External overcurrent protection | MOD power: 10-12A @ 22.5-43.2 A²t fast-acting; SA power: 20 A @ 250V AC |
| Power dissipation, typical | 2.8–3.5 W per digital module; 4.0–7.0 W per adapter; 3.5 W per IF8 analog |
| Thermal dissipation, typical | 9.55–11.94 BTU/hr per I/O module; 17.4–23.9 BTU/hr per adapter |
| Recommended external overcurrent | MOD: 10-12A @ 22.5-43.2 A²t fast-acting fuse |
| Field power loss detection | Supported on most DC input modules (5094-IB16, IB32, IB16XT, IB32XT) and AC input modules |
Environmental
| Operating temperature (non-XT) | -40 to +70 °C (-40 to +158 °F), IEC 60068-2-1/-2/-14 |
|---|---|
| Operating temperature (XT) | -40 to +70 °C (-40 to +158 °F) with ISA-S71.04 G3 corrosive atmosphere (vs G2 for non-XT) |
| Surrounding air, max | +70 °C (+158 °F) |
| Storage temperature | -40 to +85 °C (-40 to +185 °F) |
| Relative humidity | 5–95% non-condensing (IEC 60068-2-30) |
| Vibration (operating) | 4 g or 5 g @ 10-500 Hz depending on catalog (IB16/IB16XT/OB16/OB16XT/OW8I = 5 g; others = 4 g) |
| Shock (operating / non-operating) | 25 g or 30 g operating; 30 g non-operating (IEC 60068-2-27) |
| ESD immunity | 6 kV contact / 8 kV air (IEC 61000-4-2) |
| Radiated RF immunity | 10 V/m, 1 kHz sine 80% AM, 80-6000 MHz (IEC 61000-4-3) |
| EFT/B immunity | ±4 kV @ 5 kHz on power and signal ports (IEC 61000-4-4) |
| Surge transient immunity | ±1 kV line-line / ±2 kV line-earth on power and signal (IEC 61000-4-5) |
| Conducted RF immunity | 10 V rms, 150 kHz–80 MHz (IEC 61000-4-6) |
| Emissions | IEC 61000-6-4 (industrial emissions) |
| Corrosive resistance | ISA S71.04 G2 (non-XT) / G3 (XT) |
| Enclosure type | None (open-style) |
| Temperature code | T4 (North American, UKEx/ATEX, IECEx) |
Catalog Number Format
How to read an Allen-Bradley 5094 catalog number. Each position encodes a specific configuration attribute.
Communication Protocols
Supported industrial networks and field buses for the products covered by this publication.
Certifications & Compliance
Document Contents
Full PDF covers the following topics in detail:
- Catalog number breakdown and product matrix — digital, analog, safety, specialty, EtherNet/IP adapter, terminal base, accessory (60+ catalog numbers)
- System mounting orientations (horizontal, horizontal-inverted, vertical, vertical-inverted) and 25.4 mm minimum clearance rules
- Digital I/O module specifications — wiring diagrams, functional block diagrams, technical and general specs per catalog
- Analog I/O module specifications — voltage/current ranges, 16-bit resolution, notch filters (5 Hz to 62.5 kHz), CIP Sync timestamping
- Safety I/O module specifications — SIL-rated digital, analog, and IO-Link safety modules
- EtherNet/IP adapter specifications — AENTR/AEN2TR (RJ45) and AENSFPR/AEN2SFPR (SFP) variants, compatible SFP modules, DLR topology
- Terminal base assemblies — 5094-MB/MBXT mounting bases + compatible screw and spring RTB kits (RTB3, RTB3T, RTB3W, RTB3I, RTB32V, RTB32C, RTB3AC)
- Environmental specifications and certifications — ISA G2 vs G3 corrosive, XT extended temperature, Class I Div 2, ATEX/IECEx
- Accessories — 5094-STB shield bar, 5094-SAJMPR SA jumper, 5094-N2 DIN end anchor, 5094-CE05/07/10/30 interconnect cables
- FLEX 5000 module and terminal base compatibility matrix (non-XT vs XT)
Frequently Asked Questions
Which controllers can a FLEX 5000 (5094) system connect to?
Do I need to order the terminal base and RTB separately?
What's the difference between the 5094-AENTR and 5094-AEN2TR adapters?
What's the XT suffix on FLEX 5000 modules?
Can FLEX 5000 modules be removed under power?
What network topologies does FLEX 5000 EtherNet/IP support?
Does FLEX 5000 support HART and IO-Link?
Disclaimer
Disclaimer: PLC Exchange is an independent reseller and is not an authorized distributor, affiliate, licensee, partner, or agent of Allen-Bradley / Rockwell Automation. All product information on this page is compiled from publicly-available manufacturer publications, technical data sheets, and catalog sources, each of which remains the copyright of its originating manufacturer. We make no representation or warranty, express or implied, regarding the accuracy, completeness, timeliness, or fitness for any particular purpose of the specifications or descriptions shown — content may contain errors, omissions, or out-of-date information. Product images are the property of their respective manufacturers, trademark owners, and source publications, and are displayed solely for identification purposes under the nominative fair use doctrine; images are representative and may depict a different configuration or catalog variant than the exact product listed. Purchasers should independently verify specifications against the current manufacturer publication before placing an order. All product names, trademarks, service marks, and registered trademarks are the property of their respective owners, and their use does not imply endorsement or affiliation.