Installation Instructions · Publication 5069-IN027 · Rockwell Automation

5069-IB32 Compact 5000 32-Point Sinking Input Install Guide

This publication gives installation instructions for the Allen-Bradley 5069-IB32 Compact 5000 Digital 32-point Sinking Input Module. It covers DIN rail mounting, RTB installation and wiring, end cap installation, system power considerations, and module removal. The module operates as local or remote I/O with CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 controller systems.

Download PDF
32 Input Points
10…32V DC Input Voltage Range
0…60 Operating Temperature
2…2.9 mA per channel Input Current

Document Preview

Open the full PDF in a new tab  · Publication 5069-IN027

Specifications

Voltage and Current Ratings

Input ratings 2…2.9 mA per channel @ 10…32V DC
MOD power 75 mA @ 18…32V DC
MOD power (passthrough) 9.55 A @ 18…32V DC
SA power 120 mA @ 10…32V DC
SA power (passthrough) 9.95 A @ 10…32V DC
Maximum MOD or SA passthrough current 10 A

Isolation Voltage

Isolation voltage 250V (continuous), Basic Insulation Type
SA power to input ports No isolation
Between individual input ports No isolation
Between Group A and Group B No isolation

Wire Specifications

5069-RTB18-SCREW wire size 0.5…1.5 mm² (22…16 AWG) solid or stranded shielded copper, rated 105 °C (221 °F) or greater, 3.5 mm (0.14 in.) max diameter including insulation
5069-RTB18-SPRING wire size 0.5…1.5 mm² (22…16 AWG) solid or stranded shielded copper, rated 105 °C (221 °F) or greater, 2.9 mm (0.11 in.) max diameter including insulation
5069-RTB18-SCREW insulation-stripping length 12 mm (0.47 in.)
5069-RTB18-SPRING insulation-stripping length 10 mm (0.39 in.)
5069-RTB18-SCREW torque 0.4 N•m (3.5 lb•in)

Temperature and Environment

Operating temperature 0 °C ≤ Ta ≤ +60 °C (+32 °F ≤ Ta ≤ +140 °F)
Surrounding air temperature, max 60 °C (140 °F)
Enclosure type rating None (open-style)
North American temp code T4
UKEX/ATEX temp code T4
IECEx temp code T4

Physical

DIN rail type EN50022 - 35 x 7.5 mm (1.38 x 0.30 in.)

Communication Protocols

Supported industrial networks and field buses for the products covered by this publication.

Producer/Consumer Uses the Producer/Consumer communication model; modules produce data without first being polled.

Certifications & Compliance

CL I, DIV 2, GP A, B, C, D (North American Hazardous Location) UKEX/ATEX: Equipment Group II, Category 3G; Ex ec IIC T4 Gc (DEMKO 15 ATEX 1484X, UL22UKEX2379X) IECEx: Ex ec IIC T4 Gc (IECEx UL 15.0055X)

Document Contents

Full PDF covers the following topics in detail:

  • About the Module
  • Install a System
  • Install the RTBs
  • Install the Module
  • Install the End Cap
  • Wire the RTBs
  • Power the System
  • Remove the Module
  • Specifications
  • Additional Resources

Frequently Asked Questions

What controllers are compatible with the 5069-IB32 module?
The 5069-IB32 can be used as local I/O with CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 controller systems. It can also be used as remote I/O with CompactLogix 5380, Compact GuardLogix 5380, CompactLogix 5480 controllers, and some other Logix 5000 controllers.
What RTB types are compatible with the 5069-IB32 module?
The module uses any combination of 2 of the following RTB types: 5069-RTB18-SPRING or 5069-RTB18-SCREW. RTBs do not ship with the module and must be ordered separately.
Does the 5069-IB32 support removal and insertion under power (RIUP)?
No. The module does not support RIUP capability. Power must be removed before connecting or disconnecting the module. The RTBs also do not support RIUP; power must be removed before connecting or disconnecting RTBs.
What is the input voltage and current rating for the 5069-IB32?
The input rating is 2…2.9 mA per channel at 10…32V DC.
What wire sizes are supported by the RTB connections?
Both the 5069-RTB18-SCREW and 5069-RTB18-SPRING RTBs accept 0.5…1.5 mm² (22…16 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F) or greater. Only a single wire connection per terminal is permitted. Maximum wire diameter including insulation is 3.5 mm for screw RTBs and 2.9 mm for spring RTBs.
How is the 5069-IB32 grounded?
The module is grounded through the DIN rail to chassis ground. Zinc-plated chromate-passivated steel DIN rail must be used to ensure proper grounding. The DIN rail should be secured to the mounting surface approximately every 200 mm (7.8 in.) with end-anchors used appropriately.
What are the hazardous location approvals for the 5069-IB32?
The module carries North American Class I, Division 2, Groups A, B, C, D approval with temperature code T4. It also holds UKEX/ATEX Equipment Group II, Category 3G approval (Ex ec IIC T4 Gc) per DEMKO 15 ATEX 1484X and UL22UKEX2379X, and IECEx approval (Ex ec IIC T4 Gc) per IECEx UL 15.0055X. In Zone 2 environments, the module must be mounted in a certified enclosure with a minimum IP54 ingress protection rating.

Disclaimer