Installation Instructions · Publication 5069-IN027 · Rockwell Automation
5069-IB32 Compact 5000 32-Point Sinking Input Install Guide
This publication gives installation instructions for the Allen-Bradley 5069-IB32 Compact 5000 Digital 32-point Sinking Input Module. It covers DIN rail mounting, RTB installation and wiring, end cap installation, system power considerations, and module removal. The module operates as local or remote I/O with CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 controller systems.
Download PDFDocument Preview
Open the full PDF in a new tab · Publication 5069-IN027
Specifications
Voltage and Current Ratings
| Input ratings | 2…2.9 mA per channel @ 10…32V DC |
|---|---|
| MOD power | 75 mA @ 18…32V DC |
| MOD power (passthrough) | 9.55 A @ 18…32V DC |
| SA power | 120 mA @ 10…32V DC |
| SA power (passthrough) | 9.95 A @ 10…32V DC |
| Maximum MOD or SA passthrough current | 10 A |
Isolation Voltage
| Isolation voltage | 250V (continuous), Basic Insulation Type |
|---|---|
| SA power to input ports | No isolation |
| Between individual input ports | No isolation |
| Between Group A and Group B | No isolation |
Wire Specifications
| 5069-RTB18-SCREW wire size | 0.5…1.5 mm² (22…16 AWG) solid or stranded shielded copper, rated 105 °C (221 °F) or greater, 3.5 mm (0.14 in.) max diameter including insulation |
|---|---|
| 5069-RTB18-SPRING wire size | 0.5…1.5 mm² (22…16 AWG) solid or stranded shielded copper, rated 105 °C (221 °F) or greater, 2.9 mm (0.11 in.) max diameter including insulation |
| 5069-RTB18-SCREW insulation-stripping length | 12 mm (0.47 in.) |
| 5069-RTB18-SPRING insulation-stripping length | 10 mm (0.39 in.) |
| 5069-RTB18-SCREW torque | 0.4 N•m (3.5 lb•in) |
Temperature and Environment
| Operating temperature | 0 °C ≤ Ta ≤ +60 °C (+32 °F ≤ Ta ≤ +140 °F) |
|---|---|
| Surrounding air temperature, max | 60 °C (140 °F) |
| Enclosure type rating | None (open-style) |
| North American temp code | T4 |
| UKEX/ATEX temp code | T4 |
| IECEx temp code | T4 |
Physical
| DIN rail type | EN50022 - 35 x 7.5 mm (1.38 x 0.30 in.) |
|---|
Communication Protocols
Supported industrial networks and field buses for the products covered by this publication.
Certifications & Compliance
Document Contents
Full PDF covers the following topics in detail:
- About the Module
- Install a System
- Install the RTBs
- Install the Module
- Install the End Cap
- Wire the RTBs
- Power the System
- Remove the Module
- Specifications
- Additional Resources
Frequently Asked Questions
What controllers are compatible with the 5069-IB32 module?
What RTB types are compatible with the 5069-IB32 module?
Does the 5069-IB32 support removal and insertion under power (RIUP)?
What is the input voltage and current rating for the 5069-IB32?
What wire sizes are supported by the RTB connections?
How is the 5069-IB32 grounded?
What are the hazardous location approvals for the 5069-IB32?
Disclaimer
Disclaimer: PLC Exchange is an independent reseller and is not an authorized distributor, affiliate, licensee, partner, or agent of Allen-Bradley / Rockwell Automation. All product information on this page is compiled from publicly-available manufacturer publications, technical data sheets, and catalog sources, each of which remains the copyright of its originating manufacturer. We make no representation or warranty, express or implied, regarding the accuracy, completeness, timeliness, or fitness for any particular purpose of the specifications or descriptions shown — content may contain errors, omissions, or out-of-date information. Product images are the property of their respective manufacturers, trademark owners, and source publications, and are displayed solely for identification purposes under the nominative fair use doctrine; images are representative and may depict a different configuration or catalog variant than the exact product listed. Purchasers should independently verify specifications against the current manufacturer publication before placing an order. All product names, trademarks, service marks, and registered trademarks are the property of their respective owners, and their use does not imply endorsement or affiliation.