This installation guide covers the Compact 5000 Digital 8-point Safety Sourcing Output Modules, catalog numbers 5069-OBV8S and 5069-OBV8SK. It details DIN rail mounting, RTB wiring, end cap installation, system power considerations, and module removal procedures. The modules support safety networks rated up to SIL CL 3, PLe, Cat. 4 per IEC 61508, IEC 61511, IEC 62061, and ISO 13849-1. Compatible controllers include Compact GuardLogix 5380 and GuardLogix 5580 running firmware revision 32.011 or later.

Download PDF
8 Output Points
SIL CL 3, PLe, Cat. 4 Safety Rating
1 A per channel Output Rating (Horizontal)
0…60 Operating Temperature

Document Preview

Open the full PDF in a new tab  · Publication 5069-IN021

Specifications

Temperature Ratings

Operating temperature range 0 °C ≤ Ta ≤ +60 °C (+32 °F ≤ Ta ≤ +140 °F)
Max surrounding air, horizontal mount 60 °C (140 °F)
Max surrounding air, non-horizontal mount (derated) 50 °C (122 °F)

Voltage and Current, Horizontal Orientation

Output rating 1 A per channel
MOD power 75 mA @ 18…32V DC
MOD power (passthrough) 5 A @ 18…32V DC
LA power 1 A per channel @ 18…32V DC; 8 A module @ 18…32V DC
SA power (passthrough) 9.95 A @ 18…32V DC

Voltage and Current, Non-Horizontal Orientation (Derated)

Output rating 0.7 A per channel
MOD power 75 mA @ 18…32V DC
MOD power (passthrough) 5 A @ 18…32V DC
LA power 0.7 A per channel @ 18…32V DC; 5.6 A module @ 18…32V DC
SA power (passthrough) 5 A @ 18…32V DC

Wiring Specifications

Wire type Copper
Wire size, 5069-RTB18-SCREW 0.5…1.5 mm² (22…16 AWG) solid or stranded, rated 105 °C (221 °F) or greater, 3.5 mm max insulated diameter
Wire size, 5069-RTB18-SPRING 0.5…1.5 mm² (22…16 AWG) solid or stranded, rated 105 °C (221 °F) or greater, 2.9 mm max insulated diameter
Insulation-stripping length, 5069-RTB18-SCREW 12 mm (0.47 in.)
Insulation-stripping length, 5069-RTB18-SPRING 10 mm (0.39 in.)
RTB screw torque 0.4 N•m (3.5 lb•in)

General Specifications

Enclosure type rating None (open-style)
Isolation voltage 250V (continuous), Basic Insulation Type; no isolation between LA power and output ports or between individual output ports
North American temp code T4
UKEX/ATEX temp code T4
IECEx temp code T4
DIN rail EN50022 - 35 x 7.5 mm (1.38 x 0.30 in.)
Maximum altitude 2000 m (6562 ft) without derating
Pollution degree Pollution Degree 2
Overvoltage category Category II (EN/IEC 60664-1)

Catalog Number Format

How to read an Allen-Bradley 5069 catalog number. Each position encodes a specific configuration attribute.

Position
Meaning
Example
Base catalog number
8-point safety sourcing output module
5069-OBV8S
K suffix
Conformal coating for harsh environments
5069-OBV8SK

Communication Protocols

Supported industrial networks and field buses for the products covered by this publication.

Producer/Consumer Producer/Consumer communication model; module produces data without being polled

Certifications & Compliance

CL I, DIV 2, GP A, B, C, D (North American Hazardous Location) UKEX: Equipment Group II, Category 3G; Ex ec IIC T4 Gc per EN IEC 60079-0:2018 and EN IEC 60079-7:2015+A1:2018; certificate UL22UKEX2496X ATEX: Equipment Group II, Category 3G; Ex ec IIC T4 Gc; reference certificate DEMKO18 ATEX 2019X IECEx: Ex ec IIC T4 Gc per IEC 60079-0 and IEC 60079-7; certificate IECEx UL 18.0014X Safety I/O up to SIL CL 3 and PLe, Cat. 4 as defined in IEC 61508, IEC 61511, IEC 62061, and ISO 13849-1

Document Contents

Full PDF covers the following topics in detail:

  • About the Module
  • Install a System
  • Install the RTB
  • Install the Module
  • Install the End Cap
  • Power the System
  • Remove the Module
  • Specifications
  • Additional Resources

In-Stock Products Covered by This Document

Every product below is in stock at our Charlotte, NC warehouse and covered by this publication. Ships same-day (orders before 4 PM ET) with 2.5-year warranty included.

Frequently Asked Questions

What safety ratings do the 5069-OBV8S and 5069-OBV8SK modules meet?
The modules provide safety I/O rated up to SIL CL 3 and PLe, Cat. 4 as defined in IEC 61508, IEC 61511, IEC 62061, and ISO 13849-1.
What is the difference between the 5069-OBV8S and 5069-OBV8SK?
The 5069-OBV8SK offers the same functionality as the 5069-OBV8S but also has conformal coating to help protect it in harsh environments.
What controller firmware is required to use these safety modules?
The Compact GuardLogix 5380 and GuardLogix 5580 controllers must use firmware revision 32.011 or later to use Compact 5000 I/O safety modules.
What type of power supply is required for LA power on these modules?
Only a 24V DC SELV/PELV-rated power supply may be used to provide LA power. The modules do not use SA power; they use LA power and pass SA power to the next module in the system.
What output current is available and does it change with mounting orientation?
In horizontal orientation, the output rating is 1 A per channel. When the system is mounted in any other orientation (inverted horizontal, vertical, inverted vertical, upside down, or upside up), the module is derated to 0.7 A per channel.
Which removable terminal blocks (RTBs) are compatible with this module?
The module is compatible with the 5069-RTB18-SPRING and 5069-RTB18-SCREW RTBs. RTBs must be ordered separately as they do not ship with the module.
Does the module support removal and insertion under power (RIUP)?
No. Neither the module nor the RTB supports RIUP. Power must be removed before connecting or disconnecting the module or the RTB to avoid electric arc, which could cause an explosion in hazardous location installations.