Installation Instructions · Publication 5069-IN020 · Rockwell Automation

5069-IB8S / IB8SK Compact 5000 Safety Sinking Input Install Guide

This installation guide covers the Compact 5000 Digital 8-point Safety Sinking Input Modules, catalog numbers 5069-IB8S and 5069-IB8SK. It describes how to install the module on a DIN rail, wire the removable terminal block, and connect system power. The modules support safety ratings up to SIL CL 3 and PLe, Cat. 4 as defined in IEC 61508, IEC 61511, IEC 62061, and ISO 13849-1, and work with Compact GuardLogix 5380 and GuardLogix 5580 controllers running firmware revision 32.011 or later.

Download PDF
8 Input Points
SIL CL 3 Safety Rating
0…60 Operating Temperature
1.3 A @ 18…32V DC SA Power (horizontal)

Document Preview

Open the full PDF in a new tab  · Publication 5069-IN020

Specifications

Temperature Ratings

Operating range 0 °C ≤ Ta ≤ +60 °C (+32 °F ≤ Ta ≤ +140 °F)
Max surrounding air, horizontal mount 60 °C (140 °F)
Max surrounding air, non-horizontal mount (derated) 50 °C (122 °F)

Voltage and Current, Horizontal Mount

Input rating 2.5 mA/channel
Test output rating 300 mA/channel
MOD power 75 mA @ 18…32V DC
MOD power (passthrough) 5 A @ 18…32V DC
SA power 1.3 A @ 18…32V DC
SA power (passthrough) 9.95 A @ 18…32V DC

Voltage and Current, Non-Horizontal Mount (Derated)

Input rating 2.5 mA/channel
Test output rating 200 mA/channel
MOD power 75 mA @ 18…32V DC
MOD power (passthrough) 5 A @ 18…32V DC
SA power 100 mA @ 18…32V DC
SA power (passthrough) 5 A @ 18…32V DC

Wiring Specifications

Wire type Copper
Wire size, 5069-RTB18-SCREW 0.5…1.5 mm² (22…16 AWG) solid or stranded, rated 105 °C (221 °F) or greater, 3.5 mm max insulated diameter
Wire size, 5069-RTB18-SPRING 0.5…1.5 mm² (22…16 AWG) solid or stranded, rated 105 °C (221 °F) or greater, 2.9 mm max insulated diameter
Strip length, 5069-RTB18-SCREW 12 mm (0.47 in.)
Strip length, 5069-RTB18-SPRING 10 mm (0.39 in.)
RTB screw torque 0.4 N•m (3.5 lb•in)

General Specifications

Enclosure type rating None (open-style)
Isolation voltage 250V (continuous), Basic Insulation Type
North American temp code T4
UKEX/ATEX temp code T4
IECEx temp code T4
DIN rail EN50022, 35 x 7.5 mm (1.38 x 0.30 in.)
Altitude Up to 2000 m (6562 ft) without derating
Pollution degree Pollution Degree 2

Catalog Number Format

How to read an Allen-Bradley 5069 catalog number. Each position encodes a specific configuration attribute.

Position
Meaning
Example
Base catalog number
8-point safety sinking digital input module
5069-IB8S
Suffix K
Conformal coating for harsh environments
5069-IB8SK

Communication Protocols

Supported industrial networks and field buses for the products covered by this publication.

Producer/Consumer Modules use the Producer/Consumer communication model; each module produces data without first being polled. Used as local or remote I/O with Compact GuardLogix 5380 controllers and as remote I/O with GuardLogix 5580 controllers.

Certifications & Compliance

CL I, DIV 2, GP A, B, C, D (North American Hazardous Location) UKEX: Equipment Group II, Category 3 G; Ex ec IIC T4 Gc per EN IEC 60079-0:2018 and EN IEC 60079-7:2015+A1:2018; certificate UL22UKEX2496X ATEX: Equipment Group II, Category 3 G; Ex ec IIC T4 Gc; certificate DEMKO 18 ATEX 2019X IECEx: Ex ec IIC T4 Gc per IEC 60079-0 and IEC 60079-7; certificate IECEx UL 18.0014X Safety I/O up to SIL CL 3 and PLe, Cat. 4 as defined in IEC 61508, IEC 61511, IEC 62061, and ISO 13849-1

Document Contents

Full PDF covers the following topics in detail:

  • About the Module
  • Install a System
  • Install the RTB
  • Install the Module
  • Install the End Cap
  • Wire the RTB
  • Power the System
  • Remove the Module
  • Specifications
  • Additional Resources

In-Stock Products Covered by This Document

Every product below is in stock at our Charlotte, NC warehouse and covered by this publication. Ships same-day (orders before 4 PM ET) with 2.5-year warranty included.

Frequently Asked Questions

Which controllers are compatible with the 5069-IB8S and 5069-IB8SK modules?
The modules can be used as local and remote I/O with Compact GuardLogix 5380 controllers, and as remote I/O with GuardLogix 5580 controllers. Both controller types must run firmware revision 32.011 or later.
What is the difference between the 5069-IB8S and the 5069-IB8SK?
The 5069-IB8SK offers the same functionality as the 5069-IB8S but adds conformal coating to help protect the module in harsh environments.
What mounting orientations are supported?
The modules support horizontal, inverted horizontal, vertical, inverted vertical, upside down, and upside up orientations. When mounted in any orientation other than horizontal, the module is derated: maximum surrounding air temperature drops to 50 °C and the test output rating drops to 200 mA/channel.
What type of power supply is required for functional safety applications?
For functional safety applications, SELV/PELV power supplies are required for both MOD power and SA power. When a Compact 5000 I/O safety module is installed on any SA power bus, only a 24V DC SELV/PELV-rated power supply may be used to provide SA power.
Which removable terminal blocks (RTBs) are compatible with this module?
The module accepts either the 5069-RTB18-SPRING or the 5069-RTB18-SCREW RTB. RTBs do not ship with the module and must be ordered separately.
Does the module support removal and insertion under power (RIUP)?
No. Neither the module nor the RTB supports RIUP. Power must be removed before inserting or removing the module or connecting and disconnecting the RTB.
What software is used to configure the 5069-IB8S and 5069-IB8SK modules?
The modules are configured using the Studio 5000 Logix Designer application.

Disclaimer