5069-IA16 Compact 5000 16-Point 120/240V AC Input Module Install

This document provides installation instructions for the Allen-Bradley 5069-IA16 Compact 5000 digital 16-point 120/240V AC input module. It covers DIN rail mounting, RTB installation and wiring, end cap installation, system power considerations, and module removal. The module operates as local or remote I/O with CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 controller systems.

Download PDF
16 Input Points
79…264V AC Input Voltage Range
0…60 Operating Temperature
300V continuous; teste… Isolation Voltage

Document Preview

Open the full PDF in a new tab  · Publication 5069-IN015

Specifications

Voltage and Current Ratings

Input voltage range 79…264V AC
Input voltage frequency 47…63 Hz
Input current per channel, max 15 mA @ 264V AC
On-state current, max 15 mA @ 264V AC
On-state current, min 3 mA @ 164V AC; 2 mA @ 79V AC
Off-state current, max 2 mA
MOD power 75 mA @ 18…32V DC
MOD power (passthrough) 9.55 A @ 18…32V DC
SA power 240 mA @ 79…264V AC
SA power (passthrough) 9.975 A @ 79…264V AC

Isolation

Isolation voltage 300V continuous, Basic Insulation Type; type tested at 1800V AC for 60 s
Channel-to-channel isolation No isolation between individual channels

Wiring

Wire size (screw RTB) 0.5…1.5 mm² (22…16 AWG) solid or stranded shielded copper, rated 105 °C (221 °F) or greater; 3.5 mm max diameter including insulation
Wire size (spring RTB) 0.5…1.5 mm² (22…16 AWG) solid or stranded shielded copper, rated 105 °C (221 °F) or greater; 2.9 mm max diameter including insulation
Insulation-stripping length (screw RTB) 12 mm (0.47 in.)
Insulation-stripping length (spring RTB) 10 mm (0.39 in.)
RTB torque (screw RTB only) 0.4 N•m (3.5 lb•in)

Environmental

Temperature, operating 0…60 °C (32…140 °F)
Temperature, surrounding air, max 60 °C (140 °F)
Enclosure type rating None (open-style)

Temperature Codes

North American temp code T4
UKEX/ATEX temp code T4
IECEx temp code T4

IEC Input Compatibility

IEC Input Compatibility Type 1

Communication Protocols

Supported industrial networks and field buses for the products covered by this publication.

EtherNet/IP Used as remote I/O through a Compact 5000 I/O EtherNet/IP adapter; Producer/Consumer data model

Certifications & Compliance

CL I, DIV 2, GP A, B, C, D (North American Hazardous Location) UKEX: Equipment Group II, Category 3G; Ex ec IIC T4 Gc; certificate UL22UKEX2379X ATEX: II 3 G; Ex ec IIC T4 Gc; certificate DEMKO15ATEX 1484X IECEx: Ex ec IIC T4 Gc; certificate IECExUL15.0055X

Document Contents

Full PDF covers the following topics in detail:

  • About the Module
  • Install a System
  • Install the RTB
  • Install the Module
  • Install the End Cap
  • Wire the RTB
  • Power the System
  • Remove the Module
  • Specifications
  • Additional Resources

In-Stock Products Covered by This Document

Every product below is in stock at our Charlotte, NC warehouse and covered by this publication. Ships same-day (orders before 4 PM ET) with 2.5-year warranty included.

Frequently Asked Questions

What controllers support the 5069-IA16 as local I/O?
The 5069-IA16 can be used as local I/O in CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 controller systems. It can also be used as remote I/O with those controllers and some other Logix 5000 controllers.
What removable terminal blocks (RTBs) are compatible with the 5069-IA16?
The 5069-IA16 is compatible with the 5069-RTB18-SPRING and 5069-RTB18-SCREW RTBs. RTBs must be ordered separately; they do not ship with Compact 5000 I/O modules.
Does the 5069-IA16 support removal and insertion under power (RIUP)?
No. The 5069-IA16 module does not support RIUP capability. Power must be removed before connecting or disconnecting the module or the RTB.
What type of SA power does the 5069-IA16 require?
The 5069-IA16 uses AC SA power. AC power must be connected to the component (controller, adapter, or field potential distributor) that provides SA power to the module. Modules using AC SA power must be installed on a separate SA power bus from modules using DC SA power.
Can the 5069-IA16 be installed next to a Compact GuardLogix 5380 controller?
No. Compact GuardLogix 5380 controllers do not support AC power on their SA power RTBs. A field potential distributor with AC power connected must be installed, and the 5069-IA16 must be installed next to that field potential distributor.
What are the hazardous location ratings for the 5069-IA16?
The module is rated for Class I, Division 2, Groups A, B, C, D (North American), UKEX/ATEX Zone 2 (II 3 G; Ex ec IIC T4 Gc), and IECEx Zone 2 (Ex ec IIC T4 Gc). When used in Zone 2 environments, it must be mounted in a certified enclosure with a minimum IP54 ingress protection rating. The module complies with UKEX/ATEX/IECEx when used at or below 125V AC.
What DIN rail type is required for the 5069-IA16?
The module requires an EN50022 35 x 7.5 mm (1.38 x 0.30 in.) DIN rail. Zinc-plated chromate-passivated steel DIN rail is required to assure proper grounding. The DIN rail should be secured to the mounting surface approximately every 200 mm (7.8 in.).

Disclaimer