Installation Instructions · Publication 5069-IN013 · Rockwell Automation

CompactLogix 5380 Controllers Installation Instructions

This document is the Rockwell Automation installation instructions for CompactLogix 5380 controllers. It covers DIN rail mounting, MOD power and SA power RTB wiring, Compact 5000 I/O module installation, end cap installation, and EtherNet/IP network connection. The publication applies to standard controller catalog numbers 5069-L306ER through 5069-L3100ERM and process controller catalog numbers 5069-L320ERP and 5069-L340ERP. Configuration is performed using the Studio 5000 Logix Designer application.

Download PDF
10 A @ 18…32V DC MOD Power Bus Max Current
10 A @ 18…32V DC or 10… SA Power Bus Max Current
0…60 Operating Temperature
Dual embedded 1 Gb Eth… Ethernet Ports

Document Preview

Open the full PDF in a new tab  · Publication 5069-IN013

Specifications

MOD Power Specifications

Voltage range 18…32V DC
Current, max 450 mA
Inrush 850 mA for 125 ms
Passthrough current 9.55 A @ 18…32V DC
Current rating, max (bus) 10 A

SA Field Power Specifications

Voltage ranges 0…32V DC; 0…240V AC, 47…63 Hz; EX, 125V AC max
Current, max 10 mA (DC power), 25 mA (AC power)
Passthrough current (DC) 9.95 A @ 0…32V DC
Passthrough current (AC) 9.975 A @ 0…240V AC, 47…63 Hz; EX, 125V AC max
Current rating, max (bus) 10 A

Wiring Specifications

Wire type (screw RTB) 0.5…1.5 mm² (22…16 AWG) solid or stranded copper, rated 105 °C or greater, 3.5 mm max diameter, single wire only
Wire type (spring RTB) 0.5…1.5 mm² (22…16 AWG) solid or stranded copper, rated 105 °C or greater, 2.9 mm max diameter, single wire only
Insulation-stripping length (screw) 12 mm (0.47 in.)
Insulation-stripping length (spring) 10 mm (0.39 in.)
Terminal block torque (screw) 0.4 N•m (3.5 lb•in)
Ethernet connections IEC 61918 and IEC 61784-5-2

Environmental Specifications

Temperature, operating 0…60 °C (32…140 °F)
Temperature, surrounding air, max 60 °C (140 °F)
Enclosure type rating None (open-style)
Pollution Degree 2
Altitude (without derating) Up to 2000 m (6562 ft)
Overvoltage Category II (EN/IEC 60664-1)

Isolation Voltage

SA and MOD power to backplane 300V continuous, Basic Insulation Type
SA to MOD power 300V continuous, Basic Insulation Type
Ethernet to backplane 300V continuous, Basic Insulation Type
Ethernet to MOD power 300V continuous, Double Insulation Type
Ethernet to SA power 300V continuous, Double Insulation Type
Ethernet to USB 50V continuous, Functional Insulation Type
USB to backplane 300V continuous, Basic Insulation Type
USB to MOD power 300V continuous, Double Insulation Type
USB to SA power 300V continuous, Double Insulation Type
Between Ethernet ports No isolation
Type tested 1500V AC for 60 s

Controller Dimensions

Width 101.65 mm (4.00 in.)
Height 143.97 mm (5.67 in.)
Depth 123.00 mm (4.84 in.)

Minimum Enclosure Spacing

At 55 °C (131 °F) 50.8 mm (2.00 in.) on all sides
At 60 °C (140 °F) 101.6 mm (4.00 in.) on all sides

Communication Protocols

Supported industrial networks and field buses for the products covered by this publication.

EtherNet/IP Dual embedded 1 Gb Ethernet ports. Out-of-box default is Dual-IP mode with DHCP enabled on each port (requires Logix Designer v29.00.00 or later). Linear/DLR mode is also supported, requiring only one IP address.

Certifications & Compliance

North American Hazardous Location: Class I, Division 2, Groups A, B, C, D; Temperature Code T4 UKEX/ATEX: II 3 G, Ex ec IIC T4 Gc; EN IEC 60079-0:2018, CENELEC EN IEC 60079-7:2015+A1:2018; certificate DEMKO 15 ATEX 1455X and UL22UKEX2307X; Zone 2 IECEx: Ex eC IIC T4 Gc; IEC 60079-0 Ed.7 (2017), IEC 60079-7 Ed.5.1 (2017); certificate IECExUL15.0007X; Zone 2

Document Contents

Full PDF covers the following topics in detail:

  • About the Controller
  • Before You Begin
  • Install the Controller onto the DIN Rail
  • Wire External Power Supplies to the Controller
  • Install Compact 5000 I/O Modules
  • Install the End Cap
  • Power the System
  • Set the Network Internet Protocol (IP) Addresses
  • Connect the Controller to an EtherNet/IP Network
  • Remove or Replace the Controller
  • Specifications
  • Additional Resources

In-Stock Products Covered by This Document

Every product below is in stock at our Charlotte, NC warehouse and covered by this publication. Ships same-day (orders before 4 PM ET) with 2.5-year warranty included.

Frequently Asked Questions

Which catalog numbers does this installation document cover?
The document covers standard CompactLogix 5380 controllers 5069-L306ER, 5069-L306ERM, 5069-L310ER, 5069-L310ER-NSE, 5069-L310ERM, 5069-L310ERMK, 5069-L320ER, 5069-L320ERM, 5069-L320ERMK, 5069-L330ER, 5069-L330ERM, 5069-L330ERMK, 5069-L340ER, 5069-L340ERM, 5069-L350ERM, 5069-L350ERMK, 5069-L380ERM, and 5069-L3100ERM, plus process controllers 5069-L320ERP and 5069-L340ERP.
Does the CompactLogix 5380 controller support Removal and Insertion Under Power (RIUP)?
No. The controller does not support RIUP. Power must be removed before inserting or removing the controller or its RTBs.
What external power supplies are required, and what are the maximum current limits?
The controller needs external power for MOD (system-side) power and SA (field-side) power. The total continuous current draw on the MOD power bus must not exceed 10 A at 18…32V DC. The total continuous current draw on the SA power bus must not exceed 10 A at 18…32V DC or 10 A at 18…240V AC. Rockwell Automation strongly recommends using separate external power supplies for MOD and SA power.
What RTBs are needed and are they included with the controller?
Two RTB types are needed: a 4-pin RTB for MOD power (5069-RTB4-SCREW or 5069-RTB4-SPRING) and a 6-pin RTB for SA power (5069-RTB6-SCREW or 5069-RTB6-SPRING). RTBs must be ordered separately; they are available in kits 5069-RTB64-SCREW or 5069-RTB64-SPRING, which contain both types.
What IP address modes does the CompactLogix 5380 controller support out of the box?
Out of the box, CompactLogix 5380 controllers are configured for Dual-IP mode with DHCP enabled on each Ethernet port. Dual-IP mode requires a unique IP address for each port and needs Logix Designer version 29.00.00 or later. Linear/DLR mode, which uses only one IP address, is also supported and can be configured using RSLinx Classic software.
What is the minimum Studio 5000 Logix Designer version required for each controller?
Version 28.00.00 or later is required for 5069-L320ER and 5069-L340ERM. Version 29.00.00 or later is required for 5069-L306ER, 5069-L306ERM, 5069-L310ER, 5069-L310ER-NSE, 5069-L310ERM, 5069-L310ERMK, 5069-L320ERM, 5069-L320ERMK, 5069-L330ER, 5069-L330ERM, 5069-L330ERMK, and 5069-L340ER. Version 30.00.00 or later is required for 5069-L350ERM, 5069-L350ERMK, 5069-L380ERM, and 5069-L3100ERM. Version 33.00.00 or later is required for 5069-L320ERP and 5069-L340ERP.
What DIN rail type is required and how must it be mounted?
An EN50022 - 35 x 7.5 mm (1.38 x 0.30 in.) zinc-plated chromate-passivated steel DIN rail is required. The DIN rail must be mounted horizontally and secured to the mounting surface approximately every 200 mm (7.8 in.) with end-anchors used appropriately. The controller must be the leftmost component on the rail.