Installation Instructions · Publication 5069-IN013 · Rockwell Automation
CompactLogix 5380 Controllers Installation Instructions
This document is the Rockwell Automation installation instructions for CompactLogix 5380 controllers. It covers DIN rail mounting, MOD power and SA power RTB wiring, Compact 5000 I/O module installation, end cap installation, and EtherNet/IP network connection. The publication applies to standard controller catalog numbers 5069-L306ER through 5069-L3100ERM and process controller catalog numbers 5069-L320ERP and 5069-L340ERP. Configuration is performed using the Studio 5000 Logix Designer application.
Download PDFDocument Preview
Open the full PDF in a new tab · Publication 5069-IN013
Specifications
MOD Power Specifications
| Voltage range | 18…32V DC |
|---|---|
| Current, max | 450 mA |
| Inrush | 850 mA for 125 ms |
| Passthrough current | 9.55 A @ 18…32V DC |
| Current rating, max (bus) | 10 A |
SA Field Power Specifications
| Voltage ranges | 0…32V DC; 0…240V AC, 47…63 Hz; EX, 125V AC max |
|---|---|
| Current, max | 10 mA (DC power), 25 mA (AC power) |
| Passthrough current (DC) | 9.95 A @ 0…32V DC |
| Passthrough current (AC) | 9.975 A @ 0…240V AC, 47…63 Hz; EX, 125V AC max |
| Current rating, max (bus) | 10 A |
Wiring Specifications
| Wire type (screw RTB) | 0.5…1.5 mm² (22…16 AWG) solid or stranded copper, rated 105 °C or greater, 3.5 mm max diameter, single wire only |
|---|---|
| Wire type (spring RTB) | 0.5…1.5 mm² (22…16 AWG) solid or stranded copper, rated 105 °C or greater, 2.9 mm max diameter, single wire only |
| Insulation-stripping length (screw) | 12 mm (0.47 in.) |
| Insulation-stripping length (spring) | 10 mm (0.39 in.) |
| Terminal block torque (screw) | 0.4 N•m (3.5 lb•in) |
| Ethernet connections | IEC 61918 and IEC 61784-5-2 |
Environmental Specifications
| Temperature, operating | 0…60 °C (32…140 °F) |
|---|---|
| Temperature, surrounding air, max | 60 °C (140 °F) |
| Enclosure type rating | None (open-style) |
| Pollution Degree | 2 |
| Altitude (without derating) | Up to 2000 m (6562 ft) |
| Overvoltage Category | II (EN/IEC 60664-1) |
Isolation Voltage
| SA and MOD power to backplane | 300V continuous, Basic Insulation Type |
|---|---|
| SA to MOD power | 300V continuous, Basic Insulation Type |
| Ethernet to backplane | 300V continuous, Basic Insulation Type |
| Ethernet to MOD power | 300V continuous, Double Insulation Type |
| Ethernet to SA power | 300V continuous, Double Insulation Type |
| Ethernet to USB | 50V continuous, Functional Insulation Type |
| USB to backplane | 300V continuous, Basic Insulation Type |
| USB to MOD power | 300V continuous, Double Insulation Type |
| USB to SA power | 300V continuous, Double Insulation Type |
| Between Ethernet ports | No isolation |
| Type tested | 1500V AC for 60 s |
Controller Dimensions
| Width | 101.65 mm (4.00 in.) |
|---|---|
| Height | 143.97 mm (5.67 in.) |
| Depth | 123.00 mm (4.84 in.) |
Minimum Enclosure Spacing
| At 55 °C (131 °F) | 50.8 mm (2.00 in.) on all sides |
|---|---|
| At 60 °C (140 °F) | 101.6 mm (4.00 in.) on all sides |
Communication Protocols
Supported industrial networks and field buses for the products covered by this publication.
Certifications & Compliance
Document Contents
Full PDF covers the following topics in detail:
- About the Controller
- Before You Begin
- Install the Controller onto the DIN Rail
- Wire External Power Supplies to the Controller
- Install Compact 5000 I/O Modules
- Install the End Cap
- Power the System
- Set the Network Internet Protocol (IP) Addresses
- Connect the Controller to an EtherNet/IP Network
- Remove or Replace the Controller
- Specifications
- Additional Resources
In-Stock Products Covered by This Document
Every product below is in stock at our Charlotte, NC warehouse and covered by this publication. Ships same-day (orders before 4 PM ET) with 2.5-year warranty included.
Frequently Asked Questions
Which catalog numbers does this installation document cover?
Does the CompactLogix 5380 controller support Removal and Insertion Under Power (RIUP)?
What external power supplies are required, and what are the maximum current limits?
What RTBs are needed and are they included with the controller?
What IP address modes does the CompactLogix 5380 controller support out of the box?
What is the minimum Studio 5000 Logix Designer version required for each controller?
What DIN rail type is required and how must it be mounted?
Disclaimer
Disclaimer: PLC Exchange is an independent reseller and is not an authorized distributor, affiliate, licensee, partner, or agent of Allen-Bradley / Rockwell Automation. All product information on this page is compiled from publicly-available manufacturer publications, technical data sheets, and catalog sources, each of which remains the copyright of its originating manufacturer. We make no representation or warranty, express or implied, regarding the accuracy, completeness, timeliness, or fitness for any particular purpose of the specifications or descriptions shown — content may contain errors, omissions, or out-of-date information. Product images are the property of their respective manufacturers, trademark owners, and source publications, and are displayed solely for identification purposes under the nominative fair use doctrine; images are representative and may depict a different configuration or catalog variant than the exact product listed. Purchasers should independently verify specifications against the current manufacturer publication before placing an order. All product names, trademarks, service marks, and registered trademarks are the property of their respective owners, and their use does not imply endorsement or affiliation.