Installation Instructions · Publication 5069-IN006 · Rockwell Automation

5069-IB6F-3W Compact 5000 Digital 3-Wire Sinking Input Module Installation

This document is the installation instructions for the Allen-Bradley 5069-IB6F-3W Compact 5000 Digital 3-Wire Sinking Input Module. It covers DIN rail mounting, RTB installation and wiring, end cap installation, module removal, and electrical specifications. The module operates as local or remote I/O in CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 controller systems.

Download PDF
6 Input Channels
10…32V DC Input Voltage Range
0…60 Operating Temperature
9.95 A @ 10…32V DC SA Power Passthrough

Document Preview

Open the full PDF in a new tab  · Publication 5069-IN006

Specifications

Voltage and Current Ratings

Input ratings 4…7.4 mA per channel @ 10…32V DC
Output supply ratings 150 mA per channel @ 10…32V DC
MOD power 75 mA @ 18…32V DC
MOD power (passthrough) 9.55 A @ 18…32V DC
SA power 950 mA @ 10…32V DC
SA power (passthrough) 9.95 A @ 10…32V DC
Isolation voltage 300V (continuous), Basic Insulation Type; no isolation between SA power and input ports; no isolation between individual input ports

Wire and Termination Specifications

Wire size (screw RTB) 0.5…1.5 mm2 (22…16 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F) or greater, 3.5 mm (0.14 in.) max diameter including insulation
Wire size (spring RTB) 0.5…1.5 mm2 (22…16 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F) or greater, 2.9 mm (0.11 in.) max diameter including insulation
Insulation-stripping length (screw RTB) 12 mm (0.47 in.)
Insulation-stripping length (spring RTB) 10 mm (0.39 in.)
RTB screw torque 0.4 N•m (3.5 lb•in)

Environmental Ratings

Operating temperature 0…60 °C (32…140 °F)
Surrounding air temperature, max 60 °C (140 °F)
Enclosure type rating None (open-style)
Pollution degree Pollution Degree 2
Altitude Up to 2000 m (6562 ft) without derating

Temperature Codes

North American temp code T4
UKEX/ATEX temp code T4
IECEx temp code T4

Module Dimensions

Width 25.56 mm (1.01 in.)
Depth 109.09 mm (4.29 in.)
Height 144.57 mm (5.69 in.)

DIN Rail

DIN rail type EN50022 - 35 x 7.5 mm (1.38 x 0.30 in.)
DIN rail material Zinc-plated chromate-passivated steel
DIN rail mounting interval Approximately every 200 mm (7.8 in.)

Communication Protocols

Supported industrial networks and field buses for the products covered by this publication.

EtherNet/IP Used when module is deployed as remote I/O via a Compact 5000 EtherNet/IP adapter Producer/Consumer Module uses the Producer/Consumer communication model; each module produces data without first being polled

Certifications & Compliance

CL I, DIV 2, GP A, B, C, D (North American Hazardous Location) II 3 G, Ex ec IIC T4 Gc — UKEX Regulation 2016 No. 1107 and ATEX Directive 2014/34/EU; certificate DEMKO 15 ATEX 1484X and UL22UKEX2379X IECEx: Ex ec IIC T4 Gc per IEC 60079-0 and IEC 60079-7; certificate IECEx UL 15.0055X

Document Contents

Full PDF covers the following topics in detail:

  • About the Module
  • Install a System
  • Install the RTB
  • Install the Module
  • Install the End Cap
  • Wire the RTB
  • Power the System
  • Remove the Module
  • Specifications
  • Additional Resources

Frequently Asked Questions

What controllers is the 5069-IB6F-3W compatible with?
The module can be used as local I/O in CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 controller systems. It can also be used as remote I/O with those same controllers and some other Logix 5000 controllers.
Does the RTB ship with the 5069-IB6F-3W module?
No. RTBs do not ship with Compact 5000 I/O modules and must be ordered separately. Compatible RTB types are the 5069-RTB18-SPRING and 5069-RTB18-SCREW.
Does the 5069-IB6F-3W support removal and insertion under power (RIUP)?
No. Neither the module nor the RTB supports RIUP. Power must be removed before connecting or disconnecting the module or RTB to avoid electric arc, which could cause an explosion in hazardous location installations.
What wire sizes are compatible with the RTBs for this module?
Both the screw and spring RTBs accept 0.5…1.5 mm2 (22…16 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F) or greater. The screw RTB allows a maximum wire diameter of 3.5 mm (0.14 in.) including insulation; the spring RTB allows 2.9 mm (0.11 in.) maximum.
What hazardous location certifications does the 5069-IB6F-3W carry?
The module is approved for North American Class I Division 2 Groups A, B, C, D hazardous locations, and holds UKEX/ATEX and IECEx Zone 2 certifications with protection type Ex ec IIC T4 Gc.
What type of SA power does this module use and how much does it draw?
The module uses DC SA power at 10…32V DC, drawing 950 mA. SA power passthrough capacity is 9.95 A at 10…32V DC. The maximum passthrough current for MOD or SA power must not exceed 10 A.
What enclosure is required for the 5069-IB6F-3W in Zone 2 environments?
When used in UKEX/ATEX/IECEx Zone 2 environments, the module must be mounted in a certified enclosure with a minimum ingress protection rating of IP54, used in an environment of not more than Pollution Degree 2.

Disclaimer