This technical data sheet covers the Allen-Bradley E1 Plus Electronic Overload Relay for Bulletin 193 and 592. It details product specifications, catalog number explanations, product selection tables, and accessory options. The document applies to both IEC and NEMA devices. Rated current is 0.1 to 45 A for 193-ED devices and 0.1 to 800 A for 193/592-EE devices. It also covers the side-mount expansion modules for ground fault, jam, PTC, remote reset, DeviceNet, EtherNet/IP and PROFIBUS.
Download PDFDocument Preview
Open the full PDF in a new tab · Publication 193-TD011
Specifications
Main Circuit Ratings
| Rated Insulation Voltage (Ui), 193-ED1_B, 193-EE_B/_D/_E, 592-EE_T/_C/_D | 690V AC |
|---|---|
| Rated Insulation Voltage (Ui), 193-EE_F/_G/_H | 1000V AC |
| Rated Impulse Strength (Uimp) | 6 kV AC |
| Rated Operating Voltage (Ue) IEC/UL, 193-ED1_B, 193-EE_B/_D/_E, 592-EE_T/_C/_D | 690V AC / 600V AC |
| Rated Operating Voltage (Ue) IEC/UL, 193-EE_F/_G/_H | 1000V AC / 600V AC |
| Rated Operating Frequency | 50/60 Hz (sinusoidal) |
Control Circuit Ratings
| Rated Insulation Voltage (Ui) | 690V AC |
|---|---|
| Rated Impulse Strength (Uimp) | 6 kV AC |
| Rated Operating Voltage (Ue) IEC/UL | 690V AC / 600V AC |
| Rating Designation | B600 |
| AC-15 Ie N.O./N.C. at 12…120V | 3 A / 2 A |
| AC-15 Ie N.O./N.C. at 220…240V | 1.5 A / 1.5 A |
| AC-15 Ie N.O./N.C. at 380…480V | 0.75 A / 0.75 A |
| AC-15 Ie N.O./N.C. at 500…600V | 0.6 A / 0.6 A |
| Thermal Current (Ithe) | 5 A |
| Contact Reliability | 17V, 5 mA |
Environmental Specifications
| Storage Temperature | -40…+85 °C (-40…+185 °F) |
|---|---|
| Operating Temperature | -20…+60 °C (-4…+140 °F) |
| Humidity (Operating) | 5…95% Non-condensing |
| Vibration (per IEC 68-2-6) | 3G |
| Shock (per IEC 68-2-27) | 30G |
| Maximum Altitude | 2000 m |
| Pollution Environment | Pollution Degree 3 |
| Degree of Protection | IP20 |
Protection Characteristics
| Type of Relay | Ambient Compensated, Time Delay, Phase Loss Sensitive |
|---|---|
| Nature of Relay | Solid-state |
| Trip Rating | 120% FLA |
| Trip Class: Type ED | 10 (fixed) |
| Trip Class: Type EE | 10, 15, 20, 30 (selectable) |
| Reset Mode: Type ED | Manual |
| Reset Mode: Type EE | Automatic or Manual |
Electromagnetic Compatibility
| Electrostatic Discharge Immunity: Test Level | 8 kV Air Discharge, 6 kV Contact Discharge |
|---|---|
| RF Immunity: Test Level | 10 V/m |
| Electrical Fast Transient/Burst Immunity: Test Level | 4 kV |
| Surge Immunity: Test Level | 2 kV (L-E), 1 kV (L-L) |
Standards Compliance
| Standards (specifications table) | UL 508, CSA C22.2 No. 14, NEMA ICS 2-1993 Part 4, EN 60947-4-1, EN 60947-5-1 |
|---|
Approximate Weights (unpackaged)
| 193-ED1_B, 193-EE_B | 0.25 kg (0.55 lb) |
|---|---|
| 193-EE_D | 0.25 kg (0.55 lb) |
| 193-EE_E | 0.52 kg (1.06 lb) |
Catalog Number Format
How to read an Allen-Bradley 193 catalog number. Each position encodes a specific configuration attribute.
Communication Protocols
Supported industrial networks and field buses for the products covered by this publication.
Certifications & Compliance
Document Contents
Full PDF covers the following topics in detail:
- Product Overview: Bulletin 193-ED and 193/592-EE comparison table
- Features: accurate current measurement-based protection, electronic thermal modeling, thermal memory, phase loss detection
- Features: rugged construction: over-molded power connections, current transformers, latching relay
- Features: application flexibility: isolated contacts, DIP switch settings, Pass-thru option
- Side-mount Expansion Modules: DeviceNet (193-EDN), Remote Reset (193-ERR), Jam (193-EJM), Ground Fault (193-EGF), Ground Fault/Jam (193-EGJ), PTC (193-EPT), EtherNet/IP (193-ETN), PROFIBUS (193-EPRB)
- Catalog Number Explanation: four-position code decoder with tables
- Product Selection: Bulletin 193-ED, 193-EE, 193S-EE, 592-EE, 592S-EE, and panel mount with external CTs
- Accessories: DIN Rail/panel adapters, current adjustment shields, external reset adapters, terminal lugs, core balanced ground fault sensors, remote reset solenoids, marking systems
- Specifications: main circuit, control circuit, environmental, protection, and EMC tables
- Certifications table with approximate weights
- Accessory Specifications: expansion module function comparison table, terminal block and lug kit specs
- Wiring Schematics: 1-phase IEC, 3-phase IEC, NEMA applications
- Trip Curves: Class 10, 15, 20, 30 (cold and hot)
- Approximate Dimensions: Pass-thru style, 100-C contactor mounted, 100-D contactor mounted, panel adapter mounted, 100-E116/E146 and 100-E190/E205 contactors
Frequently Asked Questions
What current range does the E1 Plus Overload Relay cover?
What trip classes are available on the 193-EE devices?
How quickly does the E1 Plus respond to a phase loss condition?
What expansion modules can be added to the E1 Plus EE devices?
What is the typical automatic reset time for 193-EE devices?
What ground fault trip levels are available with the 193-EGF module?
What is the Pass-thru option and how does it save panel space?
Disclaimer
Disclaimer: PLC Exchange is an independent reseller and is not an authorized distributor, affiliate, licensee, partner, or agent of Allen-Bradley / Rockwell Automation. All product information on this page is compiled from publicly-available manufacturer publications, technical data sheets, and catalog sources, each of which remains the copyright of its originating manufacturer. We make no representation or warranty, express or implied, regarding the accuracy, completeness, timeliness, or fitness for any particular purpose of the specifications or descriptions shown — content may contain errors, omissions, or out-of-date information. Product images are the property of their respective manufacturers, trademark owners, and source publications, and are displayed solely for identification purposes under the nominative fair use doctrine; images are representative and may depict a different configuration or catalog variant than the exact product listed. Purchasers should independently verify specifications against the current manufacturer publication before placing an order. All product names, trademarks, service marks, and registered trademarks are the property of their respective owners, and their use does not imply endorsement or affiliation.