Technical Data · Publication 193-TD006 · Rockwell Automation

E300/E200 Overload Relay Specifications, Bulletin 193/592

This technical data sheet covers the Allen-Bradley E300 and E200 Electronic Overload Relays under Bulletins 193 and 592. It details the modular three-part architecture of sensing, control, and communications modules, along with protection features, electrical specifications, catalog number explanations, and product selection tables. The document also includes wiring diagrams, environmental ratings, EMC specifications, and functional safety information for SIL 2 applications. Product selection tables and approximate dimensions cover IEC and NEMA contactor mounting.

Download PDF
0.5…200 A sensing modu… Current Range
5…30 Trip Class Range
EtherNet/IP Communication Options
10 to 15 years or 5,00… Useful Life

Document Preview

Open the full PDF in a new tab  · Publication 193-TD006

Specifications

Motor/Load Ratings

Rated Insulation Voltage Ui (Terminal Style) 690V AC
Rated Operating Voltage Ue, IEC/UL (Terminal Style) 690V AC
Rated Insulation Voltage Ui (Pass-thru Style) 1000V AC
Rated Operating Voltage Ue, IEC/UL (Pass-thru Style) 1000V AC
Rated Impulse Voltage (Uimp) 6 kV
Rated Frequency 45…65 Hz

Control Module Power Supply Ratings

Rated Supply Voltage Options 24V DC, 110…120V AC, 220…240V AC
Operating Range (24V DC) 11…30V DC
Operating Range (120V AC) 85…132V AC
Operating Range (240V AC) 159…265V AC
Maximum Power Consumption (E300/E200) 6 W
Maximum Power Consumption (E300/E200 with expansion) 8 W

Output Relay Ratings (Control and Expansion Digital Module)

Type of Contacts Form A SPST - NO
Rated Thermal Current (Ithe) 5 A
Rated Insulation Voltage (Ui) 300V AC
Rated Operating Voltage (Ue) 250V AC
Rated Operating Current (Ie) 3 A @ 120V AC; 1.5 A @ 240V AC; 0.25 A @ 110V DC; 0.1 A @ 220V DC
Resistive Load Rating (p.f. = 1.0) 5 A, 250V AC / 5 A, 30V DC
Inductive Load Rating (p.f. = 0.4, L/R = 7 ms) 2 A, 250V AC / 2 A, 30V DC
Short Circuit Current Rating 1,000 A
Recommended Control Circuit Fuse KTK-R-6 (6 A, 600 V)

Input Ratings (Control and Expansion Digital Module)

Type of Inputs Current Sinking
On-State Voltage (24V DC) 11V DC
On-State Voltage (120V AC) 74V AC
On-State Voltage (240V AC) 159V AC
On-State Current (turn-on) 2 mA (24V DC); 5 mA (120V AC); 5 mA (240V AC)

Environmental Specifications

Storage Temperature -40…+85 °C (-40…+185 °F)
Operating Temperature (open) -20…+55 °C (-4…+131 °F)
Operating Temperature (enclosed) -20…+40 °C (-4…+104 °F)
Operating Humidity 5…95% non-condensing
Vibration (IEC 68-2-6) 2.5 G operating, 5 G non-operating
Shock (IEC 68-2-27) 30 G
Maximum Altitude 2000 m
Pollution Degree 3
Degree of Protection IP20

Ground Fault Protection

Type Core Balanced (zero sequence)
Intended Use Equipment Protection
External Protection Range 20…100 mA; 100…500 mA; 200 mA…1.0 A; 1.0…5.0 A
Internal Protection Range 0.5…5.0 A
Trip & Warning Time Delay 0.1…25.0 s
Protection Inhibit Time 0…250 s

Standards Compliance (Table 1)

Standards CSA22.2 No. 60947-4-1, EN 60947-4-1, UL 60947-4-1, GB/T 14048.4-2010, IEC 61508, IEC 61511, SJ/T 11364, GB/T 26572, SJ/Z 11388

Metering Accuracy

Current ±2% of Sensing Module Current Range
Ground Fault Current ±5% of Full Scale
Voltage ±2% of Sensing Module Voltage Range
Power ±5% of Sensing Module Current and Voltage Range

Overload Protection

Type of Relay Ambient Compensated Time-Delay Phase Loss Sensitive
Nature of Relay Solid-State
Trip Rating 120% FLA
Trip Class 5…30
Reset Mode Automatic or Manual
Overload Reset Level 1…100% TCU

Analog Expansion Module (193-EXP-AIO-31)

Bus to In/Out Isolation 1000V AC = 1415V DC (1 min.)
Input Channel Types 0…20 mA, 4…20 mA; 0…10V, 1…5V, 0…5V; RTD (PT385, PT3916, Ni618, Ni672, Cu 426, NiFe 518); Resistance 0…150 Ω, 0…750 Ω, 0…3000 Ω, 0…6000 Ω
Input Resolution 12 bits
Output Channel Types 0…20 mA, 4…20 mA; 0…10V, 0…5V, 1…5V
Output Resolution 12 bits
Max Current Draw 85 mA at 24V

Catalog Number Format

How to read an Allen-Bradley 193 catalog number. Each position encodes a specific configuration attribute.

Position
Meaning
Example
a: Bulletin Number
IEC or NEMA overload relay family
193 = IEC Overload Relay; 592 = NEMA Overload Relay
b: Module Type (Sensing)
Module function identifier
ESM = Sensing Module
c: Sensing Module Type
Measured quantities
VIG = Current, Ground Fault Current, Voltage, and Power; IG = Current and Ground Fault Current; I = Current
d: Sensing Current Range
Current range of the sensing module
30A = 0.5…30 A; 60A = 6…60 A; 100A = 10…100 A; 200A = 20…200 A
e: Sensing Module Mounting Style
Contactor or panel mount compatibility
C23 = 100-C09…-C23; C55 = 100-C30…-C55; C97 = 100-C60…-C97; D180 = 100-D115…-D180; E146 = 100-E116…-E146; E205 = 100-E190…-E205; S2/S3/S4 = Bulletin 500 NEMA Size 0…2 / 3 / 4; T = DIN Rail/Panel Mount with Power Terminals; E3T = replacement for an E3 Plus panel mount adapter; P = DIN Rail/Panel Mount with Pass-thru Power Conductors; CT = Pass-thru with Voltage Sensing
b: Module Type (Control)
Control module function
EIO = I/O Only Control Module; EIOGP = I/O and Protection Control Module (External Ground Fault Sensing, and PTC)
c: I/O Count (Control)
Number of inputs and relay outputs
63 = 6 Inputs / 3 Relay Outputs; 43 = 4 Inputs / 3 Relay Outputs; 42 = 4 Inputs / 2 Relay Outputs; 22 = 2 Inputs / 2 Relay Outputs
d: Control Voltage
Rated control supply voltage
24D = 24V DC; 120 = 110…120V AC, 50/60 Hz; 240 = 220…240V AC, 50/60 Hz
c: Communication Module Type (193-ECM-___)
Communication protocol or configuration interface
ETR = EtherNet/IP with Dual Ethernet Ports; DNT = DeviceNet; PCM = Parameter Configuration Module (E200)

Communication Protocols

Supported industrial networks and field buses for the products covered by this publication.

EtherNet/IP Embedded dual-port RJ45; supports star, linear, and ring topology; 2 concurrent Class 1 connections; 6 simultaneous Class 3 connections; embedded web server; SMTP for trip/warning events; embedded EDS file; Studio 5000 Add-on Profile. DeviceNet Single 5-pin connector; data rates 125 kb, 250 kb, and 500 kb; 16 bytes of I/O (implicit) messaging; E3 Plus emulation mode (Series B control module only). USB Type B (E200 PCM) Stand-alone non-networked applications; configurable with Connected Components Workbench software; three rotary dials for FLA setting; 8-position DIP switch for trip class and feature selection.

Certifications & Compliance

cULus Listed - File No. E14840; Guide Nos. NKCR, NKCR7 CE Marked RCM (formerly C-tick) ABS CCC KCC Suitable for use with IE3 Motors (IEC 60034-30) SIL 2 Capable - IEC 61508:2010 Parts 1-7 (with Series B Control Module Only) Environmental Protection Use Period 25 (China RoHS)

Document Contents

Full PDF covers the following topics in detail:

  • Product Overview
  • Features: modular design, communication options, diagnostic information
  • Single/Three-Phase Operation and 54 operating modes
  • Thermal Overload Features (thermal memory, adjustable settings, reset modes)
  • Current Monitoring Functions (phase currents, imbalance, ground fault)
  • Control Module Features (I/O, DeviceLogix, PTC thermistor)
  • Sensing Module Features (voltage, current, ground fault, power protection)
  • Communication Modules (EtherNet/IP, DeviceNet, PCM/E200)
  • Expansion Digital I/O Modules
  • Expansion Analog I/O Module
  • Expansion Power Supply Features
  • Expansion Operator Station Features (CopyCat, control/diagnostic stations)
  • External Current Transformer Options (UL: 300 A, 600 A; CE: 300 A, 400 A)
  • Catalog Number Explanation (sensing, control, communications, expansion, accessories)
  • Product Selection Tables
  • Wiring Diagrams (control module, expansion I/O, analog, power supply, CTs)
  • Electrical Specifications (motor/load ratings, relay ratings, input ratings)
  • Environmental and EMC Specifications
  • Protection Summary Table (overload, ground fault, voltage, power)
  • Product Safety Information (SIL 2, proof test, useful life)
  • Approximate Dimensions (all mounting configurations)

Frequently Asked Questions

What is the difference between the E300 and E200 overload relay?
The communication module determines whether the assembled device is an E300 or E200. An overload system configured with the 193-ECM-PCM communication option is an E200 assembly. The E200 is targeted for non-networked (remote) applications and is configured using Connected Components Workbench software via a USB Type B port, three rotary dials for FLA, and an 8-position DIP switch for trip class and feature selection. The E300 supports EtherNet/IP (dual-port) and DeviceNet (single-port) network communication.
What protection functions does the E300/E200 relay provide?
The relay provides overload, phase loss, ground fault, current imbalance, jam (overcurrent), underload (undercurrent), stall, thermistor (PTC), remote trip, blocked start/start inhibit, under/over voltage, voltage unbalance, phase rotation, under/over frequency, under/over real power (kW), reactive power (kVAR), apparent power (kVA), power factor, and over analog. Both trip and warning outputs are available for most protection types.
What current ranges do the E300/E200 sensing modules cover?
Sensing modules are available in four current ranges: 0.5…30 A, 6…60 A, 10…100 A, and 20…200 A. For motor overload protection applications greater than 200 A, external current transformers (CTs) can be used. UL-compliant CTs are available at 300 A and 600 A ratios; CE-compliant CTs are available at 300 A and 400 A ratios.
What are the operating temperature limits for the E300/E200 relay?
The operating temperature range is -20…+55 °C (-4…+131 °F) for open installations and -20…+40 °C (-4…+104 °F) for enclosed installations. Storage temperature is -40…+85 °C (-40…+185 °F). The expansion power supplies (193-EXP-PS-AC and 193-EXP-PS-DC) must not exceed a surrounding air temperature of 55 °C (131 °F).
Is the E300/E200 relay suitable for functional safety (SIL) applications?
Yes. The E300/E200 relay is SIL 2 Capable per IEC 61508:2010 Parts 1-7 when used with a Series B Control Module. It is a Type B device and, in a low demand application as the only component in a final element subassembly, a design can meet SIL 2 at HFT=0 per Route 2H requirements. All automatic diagnostics detect product faults within a diagnostic test interval of 300 ms. The useful life is 10 to 15 years or 5,000,000 operations, whichever results in a shorter useful life.
How many expansion modules can be added to the E300/E200 relay?
Up to four additional expansion digital modules and up to four additional expansion analog modules can be added to the E300/E200 relay expansion bus. One operator station can also be added. When more than one expansion digital module and one operator station are used, an expansion power supply is required to supplement power for the additional modules.
What EtherNet/IP connection types does the E300 communication module support?
The EtherNet/IP communication module supports 2 concurrent Class 1 connections (1 exclusive owner plus 1 input only or 1 listen only) and 6 simultaneous Class 3 connections (explicit messaging). It also includes an embedded web server, SMTP server for trip and warning events (email and text messaging), an embedded EDS file, and a Studio 5000 Add-on Profile. The module has two RJ45 ports supporting star, linear, and ring topology.