Technical Data · Publication 1783-TD002 · Rockwell Automation

Stratix Ethernet Device Specifications: 1783 Series Technical Data

This technical data publication covers electrical, environmental, and certification specifications for the full Stratix Ethernet device family under bulletin 1783. It addresses unmanaged switches (Stratix 2000, 2100, 2500), managed switches (Stratix 5200, 5400, 5410, 5700, 5800, 6000, 8000, 8300, ArmorStratix 5700), and networking appliances including the Stratix 4300 Remote Access Router, Stratix 5900 Services Router, Stratix 5950 Security Appliance, Stratix 5100 Wireless Access Point, Embedded Switch Technology, Configurable NAT Router, and CIP Security Proxy. Specification tables include power input, power consumption, operating temperature ranges, EMC immunity levels, dimensions, SFP module compatibility, and global certifications. Engineers selecting or installing any 1783-series Ethernet device will use this document to verify ratings and clearance requirements.

Download PDF
20+ Product Families Covered
75 Max Operating Temp (Series B Extended)
1783-TD002G-EN-P, Apri… Publication Revision
ODVA conformance tested EtherNet/IP Conformance

Document Preview

Open the full PDF in a new tab  · Publication 1783-TD002

Specifications

Stratix 2000 Series B — Power Specifications

Power input 24V (12…48V DC, 18…30V AC, 50/60 Hz), SELV
Power consumption, max (1783-US5T/B) 3.4 W
Power consumption, max (1783-US8TG2GX/B) 10 W
Wire size, DC power connection 4…0.25 mm² (12…24 AWG) twisted-pair copper, rated 86 °C above ambient
Screw torque, power terminals 0.50…0.56 N•m (4.5…5.0 in•lb)
Enclosure type rating None (open-style)

Stratix 2000 Series B — Environmental Specifications

Operating temperature (1783-US5T/B, 1783-US8T/B) -10 °C < Ta < +60 °C (14 °F < Ta < 140 °F)
Operating temperature (extended-range models) -40 °C < Ta < +75 °C (-40 °F < Ta < 167 °F)
Non-operating temperature -40…+85 °C (-40…+185 °F)
Relative humidity 5…95% noncondensing
Vibration (IEC 60068-2-6) 2 g @ 10…500 Hz
Shock, operating 15 g
Shock, nonoperating 30 g
ESD immunity (IEC 61000-4-2) 6 kV contact / 8 kV air discharges
Environmental rating IP30

Stratix 2100 Unmanaged Switches — Technical Specifications

Power input 12/24/48V DC; 24V AC, 50/60 Hz
Power consumption, max (1783-USP5T) 1.1 W
Power consumption, max (1783-USP16TG) 11.5 W
Temp code T4
MAC addresses, max supported 2K (most models); 8K (1783-USP16T)
Packet buffer size 768 kBit (5/8-port); 4 MBit (1783-USP16T)
Operating temperature -40 °C < Ta < +75 °C (-40 °F < Ta < 167 °F)
Environmental rating IP30

Stratix 2500 Lightly Managed Switches — Technical Specifications

Catalog numbers 1783-LMS5 (5-port), 1783-LMS8 (8-port)
Power input 12…24V DC, SELV
Power consumption (1783-LMS5) 4.2 W
Power consumption (1783-LMS8) 5.3 W
Operating temperature -20 °C < Ta < +60 °C (-4 °F < Ta < 140 °F)
Environmental rating IP30
North American temp code T4

Stratix 4300 Remote Access Routers — Technical Specifications

Power input 24V DC (9…34V DC), 0.6 A (SELV)
Power dissipation 15.8 W max
Inrush current 10 A max
Isolation voltage 500V
Wi-Fi standard (wireless models) IEEE 802.11a/b/g/n/ac, 2.4 GHz/5 GHz, Bluetooth 5.1, up to 1.73 Gbps
Cellular standard (cellular models) 2G/3G/4G LTE CAT 4 Multi-Band, up to 50 Mbps upload / 150 Mbps download
Operating temperature (1783-RA2TGB, 1783-RA5TGB) -20 °C ≤ Ta ≤ +65 °C (-4 °F ≤ Ta ≤ 149 °F)
Operating temperature (wireless/cellular models) -20 °C ≤ Ta ≤ +60 °C (-4 °F ≤ Ta ≤ 140 °F)
Environmental rating IP20

Stratix 5200 Managed Switches — Technical Specifications

Voltage nominal 12…48V DC
Power consumption (1783-CMS6B/6P) 14 W
Power consumption (1783-CMS20DB/DP/DN) 36.7 W
Alarm relay 30V DC, 1.0 A; 60V DC, 0.5 A
Operating temperature -40 °C < Ta < +60 °C (-40 °F < Ta < 140 °F)
North American temp code T4
Environmental rating IP30
Industry standards IEEE 1613, IEC 61850-3

Stratix 5400 Managed Switches — Technical Specifications

Power input 12…54V DC
Power dissipation, max 35…42 W (non-PoE configurations)
PoE power input 44…54V DC for PoE; 50…54V DC for PoE+
Operating temperature -40…+70 °C (-40…+158 °F)
Relative humidity 5…90% noncondensing
North American temp code T3
Industry standards IEEE 1613, IEC 61850-3

Stratix 5410 Managed Switches — Technical Specifications

Power input (DC models) 24…60V DC, 10 A
Power input (AC models) 100…240V AC, 2 A, 50…60 Hz per slot; or 100…250V DC, 2 A per slot
PoE output 54V DC, 15.4 W max
PoE+ output 54V DC, 30 W max
Power dissipation 100 W
Weight (switch with power supply) 7.30 kg (16.1 lb)
Operating temperature -40…+60 °C (-40…+140 °F)
North American temp code T4
Environmental rating IP30

Preinstalled SFP Module Specifications (Stratix 2000)

Multimode central wavelength 1310 nm
Multimode transmission distance 2 km (100Base-FX)
Singlemode central wavelength 1310 nm
Singlemode transmission distance 20 km (100Base-LX)
Receiving sensitivity, multimode -31 dBm
Receiving sensitivity, singlemode -34 dBm

Catalog Number Format

How to read an Allen-Bradley 1783 catalog number. Each position encodes a specific configuration attribute.

Position
Meaning
Example
1783
Bulletin — Stratix Ethernet Devices
1783
Product family code (e.g., US, USP, LMS, RA, CMS, HMS, IMS, BMS, MMS)
Identifies product family: US = Stratix 2000 unmanaged, USP = Stratix 2100 unmanaged, LMS = Stratix 2500 lightly managed, RA = Stratix 4300 remote access router, CMS = Stratix 5200 managed, HMS = Stratix 5400 managed, IMS = Stratix 5410 managed, BMS = Stratix 5700 managed, MMS/MMX = Stratix 5800 managed
HMS (Stratix 5400)
Port count and type suffix
Encodes port quantity and type: digits indicate port count; T = copper Fast Ethernet, TG = copper Gigabit Ethernet, F = multimode fiber SFP, H = singlemode fiber SFP, CG = combo Gigabit, S = SFP slot, E = PoE port, GX = GE SFP slot
8TG4CGN = 8 GE copper + 4 GE combo, Layer 2
Series suffix (/A, /B)
Hardware series designation for Stratix 2000 switches
1783-US5T/B = Series B

Communication Protocols

Supported industrial networks and field buses for the products covered by this publication.

EtherNet/IP ODVA conformance tested to EtherNet/IP specifications on Stratix 2000 Series B, Stratix 2500, Stratix 5200, Stratix 5400, Stratix 5410, and other managed switch families. IEEE 802.11a/b/g/n/ac Wi-Fi Supported on Stratix 4300 wireless models (1783-RA2TGW, 1783-RA2TGWC4G, 1783-RA5TGW, 1783-RA5TGWC4G); 2.4 GHz and 5 GHz bands; data rate up to 1.73 Gbps. 2G/3G/4G LTE CAT 4 Supported on Stratix 4300 cellular models (1783-RA2TGC4G, 1783-RA2TGWC4G, 1783-RA5TGC4G, 1783-RA5TGWC4G); multi-band all regions; up to 50 Mbps upload / 150 Mbps download. CIP Sync (IEEE 1588) Supported on Stratix 5200, 5400, and 5410 Full firmware models. EtherNet/IP DLR (Device Level Ring) Supported on select Stratix 5200, 5400, and 5410 models.

Certifications & Compliance

c-UL-us: UL Listed Industrial Control Equipment for US and Canada (UL File E65584); UL Listed Class I, Division 2 Group A,B,C,D Hazardous Locations (UL File E194810) — applicable across Stratix 2000, 2500, 4300, 5200, 5400, 5410 families. CE (EMC): European Union 2014/30/EU EMC Directive — EN 61326-1, EN 61000-6-2, EN 61000-6-4, EN 61131-2 (select models also EU 2004/108/EC). CE (RoHS): European Union 2011/65/EU RoHS — EN 50581 Technical Documentation. Ex (ATEX): European Union 2014/34/EU ATEX Directive — EN 60079-0, EN 60079-15, II 3 G Ex nA IIC; temperature code varies by product family (T3 or T4). IECEx: IEC 60079-0, IEC 60079-15, II 3 G Ex nA IIC — Stratix 2000 Series B (IECEx UL 16.0169X). RCM: Australian Radiocommunications Act — AS/NZS CISPR 11 Industrial Emissions. KC/KCC: Korean Registration of Broadcasting and Communications Equipment — Article 58-2 of Radio Waves Act (select models KN11 Group 1, Class A). EtherNet/IP: ODVA conformance tested (Stratix 2000 Series B, 2500, 5200, 5400, 5410). BSMI: CNS 13438 (95); CNS14336-1 (99) Taiwan — Stratix 2000 Series B, 5400. FCC / IC: Stratix 4300 cellular and Wi-Fi models — FCC ID XMR201903EG25G / IC 10224A-201903EG25G (cellular); FCC ID PD99260NG / IC 1000M-9260NG (Wi-Fi). UKCA/UKEX: UK Statutory Instruments 2016 — Stratix 4300 and Stratix 2100 families. China CCC Ex: GB/T 3836.1-2021; GB/T 3836.3-2021; GB/T 3836.8-2021 — Stratix 2100. TEC: As per TEC essential requirements TEC37942410 — Stratix 2100. IEEE 1613 / IEC 61850-3: Electric power station and substation networking — Stratix 5200, 5400, 5410.

Document Contents

Full PDF covers the following topics in detail:

  • Summary of Changes
  • Stratix 2000 Ethernet Unmanaged Switches — Series B (catalog numbers, technical specs, SFP specs, environmental specs, certifications, dimensions)
  • Stratix 2000 Ethernet Unmanaged Switches — Series A (catalog numbers, technical specs, SFP specs, environmental specs, certifications, dimensions, series change table)
  • Stratix 2100 Ethernet Unmanaged Switches (port specs, technical specs, environmental specs, certifications, dimensions)
  • Stratix 2500 Ethernet Lightly Managed Switches (technical specs, environmental specs, certifications, dimensions)
  • Stratix 4300 Remote Access Routers (technical specs, environmental specs, certifications, cellular/Wi-Fi connectivity, antenna gain tables, dimensions)
  • Stratix 5200 Ethernet Managed Switches (technical specs, environmental specs, certifications, dimensions)
  • Stratix 5400 Ethernet Managed Switches (technical specs, environmental specs, certifications, dimensions)
  • Stratix 5410 Ethernet Managed Switches (technical specs, environmental specs, certifications, dimensions)
  • Stratix 5700 Ethernet Managed Switches and PoE Switches
  • ArmorStratix 5700 Ethernet Managed Switches
  • Stratix 5800 Ethernet Managed Switches and Expansion Modules
  • Stratix 6000 Ethernet Managed Switches
  • Stratix 8000 and 8300 Ethernet Managed Switches
  • Stratix 5100 Wireless Access Point/Workgroup Bridge
  • Stratix 5900 Services Router
  • Stratix 5950 Security Appliance
  • Embedded Switch Technology (1783-ETAP)
  • Configurable NAT Router (1783-NATR)
  • CIP Security Proxy (1783-CSP)
  • Accessories — SFP modules (Table 76–78), memory cards, Ethernet cables, antenna options and mounting specifications
  • Additional Resources

Frequently Asked Questions

What is the operating temperature range for Stratix 2000 Series B extended-range models?
Extended-range Stratix 2000 Series B switches (such as 1783-US5TG/B, 1783-US4T1F/B, and 1783-US8TG2GX/B) operate from -40 °C to +75 °C (-40 °F to +167 °F) per IEC 60068-2-1, IEC 60068-2-2, and IEC 60068-2-14. The base models 1783-US5T/B and 1783-US8T/B are rated -10 °C to +60 °C.
Which Stratix 5400 and 5410 switches meet IEC 61850-3 for electric substation use?
All Stratix 5400 and Stratix 5410 switch models are tested to IEC 61850-3 (Electric Substations Communications Networking) and IEEE 1613 (Electric Power Stations). However, the switches meet IEC 61850-3 requirements only when powered by a redundant power supply configuration.
What cellular and Wi-Fi standards do Stratix 4300 routers with wireless options support?
Wireless Stratix 4300 models support IEEE 802.11a/b/g/n/ac at 2.4 GHz and 5 GHz with Bluetooth 5.1 and data rates up to 1.73 Gbps. Cellular models support 2G/3G/4G LTE CAT 4 across multi-band all regions, with data rates up to 50 Mbps upload and 150 Mbps download.
What SFP modules are compatible with Stratix 5410 switches but not available for Stratix 5700 or 8000?
The 1783-SFP10GSRI and 1783-SFP10GLRE (10 Gigabit Ethernet SFP modules) are supported only on the Stratix 5410. They are listed as Not Supported on Stratix 2000, 5400, 5700, 5800, 5950, 6000, 8000, and 8300 per Table 78.
What is the power input range and maximum power consumption for the Stratix 5410 DC models?
Stratix 5410 DC models (1783-IMS28NDC, 1783-IMS28RDC, 1783-IMS28GNDC, 1783-IMS28GRDC) accept 24…60V DC at 10 A. With one power supply and no PoE ports active, consumption is 74 W at 24V DC at 40 °C. With two power supplies and 12 PoE ports active, total system power reaches 291 W max.
What hazardous location certifications apply to the Stratix 2500 switches?
The Stratix 2500 switches (1783-LMS5, 1783-LMS8) are UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations (UL File E194810) and UL Listed for Class I, Zone 2 Hazardous Locations (UL File E194810). They are also ATEX-certified under EU 2014/34/EU with classification II 3 G Ex nA IIC T4 Gc (DEMKO 16 ATEX 1731).
What minimum clearances are required for Stratix 2000 Series B switches to prevent overheating?
To prevent overheating, Stratix 2000 Series B switches require a minimum clearance of 51 mm (2.0 in.) on the top, bottom, and sides, and 64 mm (2.5 in.) at the front.

Disclaimer