This technical data publication covers specifications for the full 1769 Compact I/O module family, including digital, contact, analog, and specialty I/O modules. It provides environmental ratings, certifications, wiring diagrams, and per-module electrical specifications for catalog numbers such as 1769-IA8I, 1769-IQ32, 1769-OB16, 1769-IF8, 1769-OF4, 1769-HSC, and many others. The modules are compatible with CompactLogix controllers, MicroLogix 1500, the 1769-ADN DeviceNet adapter, and the 1769-AENTR Ethernet adapter. Modules mount on DIN rail or panel and connect via a tongue-and-groove assembly with an integrated communication bus.

Download PDF
0…60 Operating Temperature
Digital, Contact, Anal… Module Types
30 modules Max Local I/O (1769-L36ERM)
1769-TD006H-EN-P, Nove… Publication Revision

Document Preview

Open the full PDF in a new tab  · Publication 1769-TD006

Specifications

Environmental Specifications (most modules)

Operating temperature 0…60 °C (32…140 °F)
Non-operating temperature -40…+85 °C (-40…+185 °F)
Relative humidity 5…95% noncondensing
Vibration, operating 5 g @ 10…500 Hz
Shock, operating (panel mount) 30 g
Shock, operating (DIN rail mount) 20 g
Shock, non-operating (panel mount) 40 g
Shock, non-operating (DIN rail mount) 30 g

1769-IA8I / 1769-IA8IK – 120V AC Isolated Input

Inputs 8 individually isolated
Operating voltage range 79…132V AC, 47…63 Hz
Input delay, on/off 20 ms
On-state current, max 12 mA @ 120V AC
Isolation voltage 1517V AC for 1 s or 2145V DC for 1 s; 132V AC working voltage
Power supply distance rating 8 modules
Dimensions (HxWxD) 118 x 35 x 87 mm (4.65 x 1.38 x 3.43 in.)

1769-IA16 / 1769-IA16K – 120V AC Input

Inputs 16 (16 points/group, internally connected commons)
Operating voltage range 79…132V AC, 47…63 Hz
Input delay, on/off 20 ms
Current draw @ 5.1V 115 mA
Heat dissipation, max 3.30 W

1769-IM12 – 240V AC Input

Inputs 12 (12 points/group, internally connected commons)
Operating voltage range 159…265V AC, 47…63 Hz
Input delay, on/off 20 ms
Heat dissipation, max 3.65 W
Isolation voltage 1836V AC for 1 s or 2596V DC for 1 s; 132V AC working voltage

1769-OA8 – 100/240V AC Solid-State Output

Outputs 8 (4 points/group)
Operating voltage range 85…265V AC, 47…63 Hz
Current per point, max 0.25 A @ 60 °C; 0.5 A @ 30 °C
Current per module, max 2 A @ 60 °C; 4 A @ 30 °C
Surge current 10 A for 25 ms, repeatable every 2 s

1769-OA16 / 1769-OA16K – 120/240V AC Solid-State Output

Outputs 16 (8 points/group)
Operating voltage range 85…265V AC, 47…63 Hz
Current per point, max 0.25 A @ 60 °C; 0.5 A @ 30 °C
Current per module, max 2 A @ 60 °C; 4 A @ 30 °C
Slot width 1.5

1769-IQ16 / 1769-IQ16K – 24V DC Sink/Source Input

Inputs 16 (8 points/group)
Operating voltage range 10…30V DC @ 30 °C; 10…26.4V DC @ 60 °C
Input delay, on/off 8 ms
Input impedance, nom 3 kΩ
Isolation voltage 1200V AC for 1 s or 1697V DC for 1 s; 75V DC working voltage

1769-IQ32 / 1769-IQ32K – 32-Point 24V DC Sink/Source Input

Inputs 32 (8 points/group)
Operating voltage range 10…30V DC @ 30 °C; 10…26.4V DC @ 60 °C
Heat dissipation, max 4.6 W
Slot width 1.5
Power supply distance rating 8 modules

1769-OB8 / 1769-OB8K – 24V DC Source High-Current Output

Outputs 8 (4 points/group)
Operating voltage range 20.4…26.4V DC
Current per point, max 2.0 A @ 60 °C
Current per module, max 8.0 A @ 60 °C
Output delay, on 0.1 ms

1769-OB16 / 1769-OB16K – 24V DC Source Output

Outputs 16 (16 points/group)
Operating voltage range 20.4…26.4V DC
Current per point, max 0.5 A @ 60 °C; 1.0 A @ 30 °C
Current per module, max 4.0 A @ 60 °C; 8.0 A @ 30 °C
Output delay, on 0.1 ms

1769-OB32 / 1769-OB32K – 32-Point 24V DC Source Output

Outputs 32 (16 points/group)
Operating voltage range 20.4…26.4V DC
Current per point, max 0.5 A @ 60 °C; 1.0 A @ 30 °C
Current per module, max 4.0 A @ 60 °C; 8.0 A @ 30 °C
Slot width 1.5
Power supply distance rating 6 modules

1769-IQ6XOW4 – Combination 24V DC Input / Relay Output

Inputs 6 (24V DC sink/source)
Outputs 4 (AC/DC normally open relay contacts)
Output voltage range 5…265V AC, 5…125V DC
Current per point, max (output) 2.5 A
Current per module, max (output) 8 A

Expansion Cables (1769-CLLx, 1769-CRRx, 1769-CRLx)

Lengths available 305 mm (1 ft) and 1 m (3.28 ft)
Max cables per system 2 (allows 3 banks of I/O)
Weight (305 mm) 300 g (0.66 lb)
Weight (1 m) 350 g (0.77 lb)

Communication Protocols

Supported industrial networks and field buses for the products covered by this publication.

DeviceNet Used with 1769-ADN DeviceNet adapter in a Compact I/O assembly EtherNet/IP Used with 1769-AENTR Ethernet adapter in a Compact I/O assembly

Certifications & Compliance

c-UL-us: UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada (UL File E334470 for digital/contact and specialty modules; alternate UL files apply to select analog modules) UKCA and CE: Compliant with UK Statutory Instrument 2016 No. 1091 and EU 2014/30/EU EMC Directive (EN 61000-6-2 Industrial Immunity; EN 61000-6-4 Industrial Emissions); EU 2011/65/EU RoHS (EN IEC 63000); and for digital/contact modules also UK Statutory Instrument 2016 No. 1101 and EU 2014/35/EU LVD (EN 61131-2) RCM: Australian Radiocommunications Act, compliant with EN 61000-6-4 Industrial Emissions KC: Korean Registration of Broadcasting and Communications Equipment, compliant with Article 58-2 of Radio Waves Act, Clause 3 Morocco: Arrêté ministériel n° 6404-15 du 1er muharram 1437 and Arrêté ministériel n° 6404-15 du 29 ramadan 1436 EX (1769-ECR/ECRK only): EU 2014/34/EU ATEX Directive – EN 60079-0, EN 60079-7; II 3 G Ex ec IIC T4 Gc; DEMKO 12 ATEX 1116807X; UL22UKEX2516X IECEx (1769-ECR/ECRK only): IEC 60079-7, IEC 60079-0 Zone 2; IECEx UL 21.0112X CCC (1769-ECR/ECRK only): CNCA-C23-01 CCC Implementation Rule Explosion-Proof Electrical Products

Document Contents

Full PDF covers the following topics in detail:

  • Summary of Changes
  • I/O Module Overview
  • Environmental Specifications
  • Certifications (Digital/Contact, Analog, and Specialty modules)
  • Place Compact I/O Modules (controller compatibility and local I/O counts)
  • Digital I/O Modules (AC input, AC output, DC input, DC output, TTL)
  • Contact I/O Modules (relay output)
  • Analog I/O Modules (current/voltage input and output, RTD, thermocouple)
  • Specialty I/O Modules (1769-ARM, 1769-ASCII, 1769-BOOLEAN, 1769-HSC, 1769-SM2)
  • Compact I/O Mounting Dimensions
  • Compact I/O Accessories (end caps, expansion cables, terminal blocks)
  • Wiring Systems (RTBs, IFMs, AIFMs, module-ready cables)
  • Additional Resources

In-Stock Products Covered by This Document

Every product below is in stock at our Charlotte, NC warehouse and covered by this publication. Ships same-day (orders before 4 PM ET) with 2.5-year warranty included.

Frequently Asked Questions

Which controllers can use 1769 Compact I/O modules as local I/O?
The 1769 Compact I/O modules can be used with 1769 CompactLogix controllers, for expansion I/O in a MicroLogix 1500 controller assembly, in an assembly with a 1769-ADN DeviceNet adapter, or in an assembly with a 1769-AENTR Ethernet adapter. The number of supported local I/O modules depends on the specific controller; for example, the 1769-L36ERM supports 30 local modules across 3 separate banks.
What are the operating temperature limits for most 1769 Compact I/O modules?
The operating temperature range for most 1769 Compact I/O modules is 0…60 °C (32…140 °F), tested per IEC 60068-2-1, IEC 60068-2-2, and IEC 60068-2-14. The non-operating storage temperature range is -40…+85 °C (-40…+185 °F). Environmental specifications for the 1769-SM2 module are listed separately in the publication.
How are 1769 Compact I/O modules mounted and connected together?
Modules can be installed on a panel with two mounting screws or on a DIN rail. They mechanically lock together using a tongue-and-groove design, and an integrated communication bus is connected from module to module by a movable bus connector. Once locked together, the system forms a single assembly.
How many expansion cable segments can be used in a 1769 system?
A maximum of two expansion cables (1769-CLLx, 1769-CRRx, or 1769-CRLx) can be used in a 1769 system, which allows for up to three groups or banks of I/O modules. Each bank requires its own power supply. Cables are available in 305 mm (1 ft) and 1 m (3.28 ft) lengths.
What hazardous location rating do the 1769 Compact I/O digital modules carry?
The 1769 Compact I/O digital and contact modules are c-UL-us Listed for Class I, Division 2, Group A, B, C, D Hazardous Locations, certified for the U.S. and Canada under UL File E334470. The 1769-ECR/ECRK end caps also carry ATEX and IECEx Zone 2 certifications.
What is the maximum current output of the 1769-OB8 high-current output module?
The 1769-OB8 solid-state 24V DC source output module provides a maximum of 2.0 A per point and 8.0 A per module at 60 °C (140 °F). It supports a surge current of 4 A for 10 ms, repeatable every 2 s, and operates over a voltage range of 20.4…26.4V DC.
What wire sizes are compatible with 1769 Compact I/O terminal blocks?
Most 1769 Compact I/O modules accept 22…14 AWG solid wire or 22…16 AWG stranded wire. The wire type must be Cu-90 °C (194 °F). Terminal screw torque is 0.68 N•m (6 lb•in) and retaining screw torque is 0.46 N•m (4.1 lb•in).