Reference Manual · Publication 1756-RM012 · Rockwell Automation
GuardLogix 5580 & Compact GuardLogix 5380 Safety Reference Manual
This reference manual covers safety application development, operation, and maintenance for GuardLogix 5580 (Bulletin 1756) and Compact GuardLogix 5380 (Bulletin 5069) controllers. It addresses SIL 2 and SIL 3 requirements under IEC 61508, IEC 62061, IEC 61511, and ISO 13849-1, including safety signatures, CIP Safety networking, safety I/O configuration, and system reaction time calculations. TUV Rheinland has approved both controller families for safety-related applications where the de-energized state is the safe state.
Download PDFDocument Preview
Open the full PDF in a new tab · Publication 1756-RM012
Specifications
Safety Ratings by Controller Configuration
| GuardLogix 5580 primary controller only | SIL 2 / SIL CL 2 / PLd (Cat. 3) per IEC 61508, IEC 62061, IEC 61511, ISO 13849-1 |
|---|---|
| GuardLogix 5580 primary controller with safety partner | SIL 3 / SIL CL 3 / PLe (Cat. 4) per IEC 61508, IEC 62061, IEC 61511, ISO 13849-1 |
| Compact GuardLogix 5380 (cat. no. ends in S2) | SIL 2 / SIL CL 2 / PLd (Cat. 3) |
| Compact GuardLogix 5380 (cat. no. ends in S3) | SIL 3 / SIL CL 3 / PLe (Cat. 4) |
| Approving body | TUV Rheinland |
| Safe state | De-energized state |
Safety Parameters: GuardLogix 5580 with Safety Partner (1oo2, SIL 3)
| Hardware Fault Tolerance (HFT) | 1 |
|---|---|
| Dangerous Undetected Failure Rate (λDU) | 7.38E-11 failures/hr |
| PFDave (Mission Time 20 yr) | 6.46E-06 |
| PFH | 7.38E-11 |
| MTTFd | 160.82 yr |
| Systematic Capability (SC) | 3 |
| Useful Life | 20 years |
Safety Parameters: GuardLogix 5580 Primary Controller Only (1oo1, SIL 2)
| Hardware Fault Tolerance (HFT) | 0 |
|---|---|
| Dangerous Undetected Failure Rate (λDU) | 6.40E-09 failures/hr |
| PFDave (Mission Time 20 yr) | 5.61E-04 |
| PFH | 6.40E-09 |
| MTTFd | 172.74 yr |
| Systematic Capability (SC) | 3 |
Safety Parameters: Compact GuardLogix 5380 SIL 2
| Hardware Fault Tolerance (HFT) | 0 |
|---|---|
| Dangerous Undetected Failure Rate (λDU) | 7.23E-09 failures/hr |
| PFDave (Mission Time 20 yr) | 6.33E-04 |
| PFH | 7.23E-09 |
| MTTFd | 155.66 yr |
Safety Parameters: Compact GuardLogix 5380 SIL 3
| Hardware Fault Tolerance (HFT) | 1 |
|---|---|
| Dangerous Undetected Failure Rate (λDU) | 6.45E-11 failures/hr |
| PFDave (Mission Time 20 yr) | 6.26E-06 |
| PFH | 6.45E-11 |
| MTTFd | 186.08 yr |
Safety Task Parameters
| Period | 2…500 ms |
|---|---|
| Watchdog | 2…500 ms |
| Programming language | Ladder diagram only |
EtherNet/IP Communication
| Onboard Ethernet speed | 10/100/1000 Mbps |
|---|---|
| Minimum firmware of a remote GuardLogix consuming 5580/5380 data | Revision 28 (or use a separate EtherNet/IP module bridging the backplane) |
Catalog Number Format
How to read an Allen-Bradley 1756 catalog number. Each position encodes a specific configuration attribute.
Communication Protocols
Supported industrial networks and field buses for the products covered by this publication.
Certifications & Compliance
Document Contents
Full PDF covers the following topics in detail:
- GuardLogix Safety Concept: SIL/PL ratings table, GuardLogix architecture diagrams, safety application requirements, controller useful life, and safety data (PFD, PFH, MTTFd, λDU tables)
- Safety Signature: signature hierarchy, viewing signature elements, signature states (blue/black/gray), archiving reports for audit, signature authentication, and programmatic changes
- GuardLogix and Compact GuardLogix Controller Systems: hardware catalog numbers, primary controller and safety partner roles, chassis and power supply considerations, EtherNet/IP and DeviceNet communication, HMI considerations
- Safety I/O: SIL 2 and SIL 3 wiring considerations, ownership, input/output point operation types, safety I/O configuration signature, device replacement procedures, electronic keying settings, automatic configuration options
- CIP Safety Systems and Safety Network Numbers: SNNs, routable CIP Safety system topology, SNN assignment (time-based and manual formats), UNID concept
- Safety Programming Considerations: safety task parameters, safety programs and routines, safety tags, tag mapping (standard-to-safety), custom tag initialization during prescan, programming restrictions
- Safety Add-On Instructions: instruction signatures, qualification tests, export/import, qualification and verification
- Safety Applications: application development and testing, commissioning lifecycle (specification, project creation, signature generation, validation, confirmation, locking, access restriction), download/upload, memory card, force data, inhibit device, online edits
- Monitor Safety Status and Handle Faults: system status, safety fault types, fault routines, GSV/SSV instructions, safety partner faults
- Safety Application Instructions: safety instructions list, Metal Form instructions, Ladder Diagram safety instructions, Drive Safety instructions
- Safety Reaction Times: connection reaction time limit, system reaction time, Logix system reaction time, factors affecting reaction time, configuring input module delay time, configuring RPI limits, configuring safety task period and watchdog, produced/consumed tag data timing
- Checklists for Safety Applications: controller system checklist, safety inputs checklist, safety outputs checklist, safety application program development checklist
- History of Changes: revision-by-revision change log from 1756-RM012C through 1756-RM012J
Frequently Asked Questions
What SIL and Performance Level ratings do GuardLogix 5580 controllers support?
What is the purpose of the safety signature and when is it required?
What are the hardware fault tolerance (HFT) values for each controller configuration?
What programming language is supported in the safety task?
How does safety I/O device replacement work when a safety signature exists?
How are Safety Network Numbers (SNNs) assigned in a CIP Safety system?
What proof test interval is required for GuardLogix controllers within their useful life?
Disclaimer
Disclaimer: PLC Exchange is an independent reseller and is not an authorized distributor, affiliate, licensee, partner, or agent of Allen-Bradley / Rockwell Automation. All product information on this page is compiled from publicly-available manufacturer publications, technical data sheets, and catalog sources, each of which remains the copyright of its originating manufacturer. We make no representation or warranty, express or implied, regarding the accuracy, completeness, timeliness, or fitness for any particular purpose of the specifications or descriptions shown — content may contain errors, omissions, or out-of-date information. Product images are the property of their respective manufacturers, trademark owners, and source publications, and are displayed solely for identification purposes under the nominative fair use doctrine; images are representative and may depict a different configuration or catalog variant than the exact product listed. Purchasers should independently verify specifications against the current manufacturer publication before placing an order. All product names, trademarks, service marks, and registered trademarks are the property of their respective owners, and their use does not imply endorsement or affiliation.