This selection guide covers the Allen-Bradley POINT I/O modular I/O system, Bulletin 1734. It documents communication adapter options for EtherNet/IP, ControlNet, DeviceNet, and PROFIBUS DP networks, along with specifications for digital, analog, POINT Guard safety, and specialty I/O modules. The guide also covers terminal bases, expansion power supplies, accessories, and mounting requirements to help engineers configure a complete POINT I/O system.
Download PDF
Specifications
EtherNet/IP Adapter – 1734-AENT / 1734-AENTK
| Communication rate |
10/100 Mbits/s, half or full-duplex |
| Ethernet ports |
1 |
| Supported topologies |
Star, Tree |
| Field power supply |
10…28.8V DC @ 10 A |
| POINTBus output, max |
5V DC @ 1.0 A |
| Power consumption, max |
10.4 W @ 28.8V DC |
| Isolation voltage |
50V continuous, Reinforced insulation; type tested at 500V AC for 60 s |
EtherNet/IP Adapter – 1734-AENTR / 1734-AENTRK
| Ethernet ports |
2, configured as embedded switches |
| Supported topologies |
Star, Tree, Daisy-chain/Linear, Ring |
| POINTBus output, max |
5V DC @ 0.8 A |
| Power dissipation, max |
6.3 W @ 28.8V DC |
ControlNet Adapter – 1734-ACNR / 1734-ACNRK
| Communication rate, max |
128K bit/s @ 500 m; 250K bit/s @ 250 m; 500K bit/s @ 100 m |
| Input byte capacity |
248 |
| Output byte capacity |
248 |
| Direct connections supported |
25 |
| Rack connections supported |
5 |
| Power consumption, max |
8.1 W @ 28.8V DC |
| Scheduled transmit memory |
586 bytes |
DeviceNet Adapter – 1734-ADN / 1734-ADNK / 1734-ADNX
| Communication rate, max |
125K bit/s @ 500 m; 250K bit/s @ 250 m; 500K bit/s @ 100 m |
| Input byte capacity |
248 |
| Output byte capacity |
248 |
| Power consumption, max |
8.1 W @ 28.8V DC |
PROFIBUS DP Adapter – 1734-APB
| Field power bus supply voltage range |
10…28.8V DC |
| Field power bus supply current, max |
10 A |
| Isolation voltage |
1250V rms/V AC |
| Power consumption, max |
8.1 W @ 28.8V DC |
Environmental Specifications – Communication and I/O Modules
| Temperature, operating |
-20…+55 °C (-4…+131 °F) |
| Temperature, nonoperating |
-40…+85 °C (-40…+185 °F) |
| Relative humidity |
5…95% noncondensing |
| Vibration |
5 g @ 10…500 Hz (IEC 60068-2-6) |
| Shock, operating |
30 g (IEC 60068-2-27) |
| Shock, nonoperating |
50 g (IEC 60068-2-27) |
| Enclosure type rating |
None (open-style) |
| Mounting type |
DIN rail |
Digital AC Input Modules
| Catalog numbers |
1734-IA2, 1734-IA4, 1734-IA4K, 1734-IM2, 1734-IM4 |
| Voltage, on-state nom (IA) |
120V AC |
| Voltage, on-state range (IA) |
65…132V AC |
| Voltage, on-state nom (IM) |
220V AC |
| Input filter time |
20 ms hardware + 1…65 ms digital filter (programmable in 1 ms increments) |
| Isolation voltage |
240V continuous; type tested at 3250V DC for 60 s |
Digital DC Input Modules
| Catalog numbers |
1734-IB2, 1734-IB4, 1734-IB4K, 1734-IB8, 1734-IB8K, 1734-IV2, 1734-IV4, 1734-IV8, 1734-IV8K, 1734-IB4D |
| Voltage, on-state nom |
24V DC |
| Voltage, on-state range |
10…28.8V DC |
| Voltage, off-state, max |
5V DC |
| Input filter time |
0.5 ms hardware + 0…65 ms selectable |
Digital DC Output Modules
| Catalog numbers |
1734-OB2, 1734-OB2E, 1734-OB2EP, 1734-OB4, 1734-OB4K, 1734-OB4E, 1734-OB8, 1734-OB8E, 1734-OB8K, 1734-OB8EK, 1734-OV2E, 1734-OV4E, 1734-OV8E, 1734-OV8EK |
| Voltage, on-state nom |
24V DC |
| Voltage, on-state range |
10…28.8V DC |
| Output current rating (OB2) |
1.0 A per channel, 2.0 A max per module |
| Output filter time |
0.1 ms Off-to-On and On-to-Off |
Analog Input Modules
| Catalog numbers |
1734-IE2C, 1734-IE2CK, 1734-IE2V, 1734-IE2VK, 1734-IE4C, 1734-IE4CK, 1734-IE8C, 1734-IE8CK |
| Input range (current) |
4…20 mA or 0…20 mA |
| Input range (voltage) |
0…10V or ±10V user configurable |
| Absolute accuracy |
±0.1% Full Scale @ 25 °C (77 °F) |
| Conversion type |
Delta Sigma |
| Data format |
Signed integer |
Analog Output Modules
| Catalog numbers |
1734-OE2C, 1734-OE2CK, 1734-OE2V, 1734-OE2VK, 1734-OE4C, 1734-OE4CK |
| Output range (current) |
4…20 mA or 0…20 mA |
| Output range (voltage) |
0…10V or ±10V user configurable |
| Absolute accuracy |
±0.1% Full Scale @ 25 °C (77 °F) |
| Resistive load on current output |
0…750 Ω |
POINT Guard Safety I/O Modules
| Safety digital input |
1734-IB8S, 1734-IB8SK – 8 inputs, current sinking, 11…28.8V DC |
| Safety analog input |
1734-IE4S, 1734-IE4SK – 4 single-ended; voltage, current, or tachometer |
| Safety digital output |
1734-OB8S, 1734-OB8SK, 1734-OBV2S, 1734-OBV2SK |
| Safety rating |
SIL CL 3 (IEC 61508, IEC 62061); PLe/Cat. 4 (ISO 13849-1), certified by TÜV Rheinland |
| Input filter time (IB8S) |
0…126 ms in 6 ms increments |
Communication Protocols
Supported industrial networks and field buses for the products covered by this publication.
EtherNet/IP Supported via 1734-AENT, 1734-AENTK (single port) and 1734-AENTR, 1734-AENTRK (dual port with embedded switch). Supports direct, rack-optimized, and enhanced rack-optimized connections. Up to 63 I/O modules per node.
ControlNet Supported via 1734-ACNR, 1734-ACNRK. Deterministic and repeatable data delivery. Supports 25 direct connections and 5 rack connections. Up to 63 I/O modules per node. Requires Series C POINT I/O modules or later.
DeviceNet Supported via 1734-ADN, 1734-ADNK, 1734-ADNX, 1734-PDN, 1734-PDNK. Uses CIP for control, configuration, and data collection. Up to 63 I/O modules per node. 1734-ADNX provides an extended subnet connector.
PROFIBUS DP Supported via 1734-APB. Connects to existing PROFIBUS DP 5 m (16.4 ft) bus, 12 MB network. Up to 63 I/O modules per node.
OPC/DDE Listed as supported network connectivity for data monitoring.
Certifications & Compliance
c-UL-us: UL Listed Industrial Control Equipment, certified for US and Canada (UL File E65584); UL Listed Class I Division 2, Group A, B, C, D Hazardous Locations (UL File E194810)
UKCA and CE: EN 61326-1, EN 61000-6-2, EN 61000-6-4, EN 61131-2 (EMC Directive 2014/30/EU)
RoHS: UK SI 2012 No. 3032 and EU 2011/65/EU, compliant with EN IEC 63000
Ex (ATEX): EU 2014/34/EU, EN IEC 60079-0, EN IEC 60079-7; II 3G Ex ec IIC T4 Gc; DEMKO 04 ATEX 0330347X; UL 22 UKEX 2478X
IECEx: IEC 60079-0, IEC 60079-7; II 3G Ex ec IIC T4 Gc; IECEx UL 20.0072X
RCM: Australian Radiocommunications Act, AS/NZS CISPR 11
KC: Korean Registration of Broadcasting and Communications Equipment, Article 58-2 of Radio Waves Act, Clause 3
CCC: 2020122309111607; CNCA-C23-01; CNCA-C23-01 CCC Implementation Rule Explosion-Proof Electrical Products
ODVA: EtherNet/IP, DeviceNet, and ControlNet conformance tested per respective ODVA/ControlNet International specifications
TÜV Functional Safety (POINT Guard I/O): SIL CL 3 per IEC 61508 / IEC 62061; PLe/Cat. 4 per ISO 13849-1
CIP Safety: ODVA conformance tested to CIP Safety on DeviceNet specifications (POINT Guard I/O)
Document Contents
Full PDF covers the following topics in detail:
- POINT I/O Family Overview
- The POINT I/O System – components, module density, and system features
- Select a POINT I/O System – six-step selection process
- Select POINT I/O Communication – NetLinx architecture; EtherNet/IP, ControlNet, DeviceNet, and PROFIBUS DP network considerations and specifications
- Select POINT I/O Modules – Digital I/O (AC input/output, DC input/output, contact, relay, self-configurable)
- Select POINT I/O Modules – Analog I/O (current input/output, voltage input/output, temperature/RTD/thermocouple input)
- Select POINT I/O Modules – POINT Guard I/O safety modules (safety digital input/output, safety analog input)
- Select POINT I/O Modules – Specialty modules (ASCII/serial, SSI encoder, IO-Link master, high-speed counter, address reserve, common/voltage terminal)
- Select Terminal Bases – terminal base assembly and one-piece terminal bases; screw-clamp and spring-clamp options; wiring tables
- Select Power Components – communication adapter power, expansion power supplies, field power distributor
- Select POINT I/O Accessories – marker cards and POINTBus extension cables
- Mount a POINT I/O System – dimensions, weights, and mounting orientation
In-Stock Products Covered by This Document
Every product below is in stock at our Charlotte, NC warehouse and covered by this publication. Ships same-day (orders before 4 PM ET) with 2.5-year warranty included.
Frequently Asked Questions
How many I/O modules can be connected to a single POINT I/O communication adapter?
Each communication adapter supports a maximum of 63 I/O modules per node when expansion power supplies are used. Without expansion power, a single adapter directly supports 13 to 17 I/O modules with a maximum of 10 A field power.
What network protocols does the POINT I/O system support?
POINT I/O supports EtherNet/IP (via 1734-AENT/AENTR adapters), ControlNet (via 1734-ACNR), DeviceNet (via 1734-ADN, 1734-ADNX, 1734-PDN), PROFIBUS DP (via 1734-APB), and OPC/DDE data monitoring. All three NetLinx networks use the Common Industrial Protocol (CIP).
What is the maximum number of points per POINT I/O module?
POINT I/O modules offer 1 to 8 points per module, providing granularity to reduce system cost and size.
Do POINT I/O safety modules support SIL 3 applications?
Yes. POINT Guard I/O modules are certified by TÜV Rheinland as capable of SIL CL 3 per IEC 61508 and IEC 62061, and PLe/Category 4 per ISO 13849-1. They are used in GuardLogix, Compact GuardLogix, or SmartGuard systems.
Can POINT I/O modules be removed and inserted while the system is powered?
Yes. POINT I/O modules support Removal and Insertion Under Power (RIUP), and the system follows a No Tools design approach for assembly of the terminal base, RTB, and I/O module.
What is the absolute accuracy of the POINT I/O analog modules?
Analog input and output modules share a high accuracy rating of ±0.1% of full-scale accuracy at 25 °C (77 °F). This includes offset, gain, non-linearity, and repeatability error terms.
Can POINT I/O modules be mounted vertically without derating?
Yes. POINT I/O modules support both horizontal and vertical mounting without thermal derating, as stated in the module features table.
Disclaimer
Disclaimer: PLC Exchange is an independent reseller and is not an authorized distributor, affiliate, licensee, partner, or agent of Allen-Bradley / Rockwell Automation. All product information on this page is compiled from publicly-available manufacturer publications, technical data sheets, and catalog sources, each of which remains the copyright of its originating manufacturer. We make no representation or warranty, express or implied, regarding the accuracy, completeness, timeliness, or fitness for any particular purpose of the specifications or descriptions shown — content may contain errors, omissions, or out-of-date information. Product images are the property of their respective manufacturers, trademark owners, and source publications, and are displayed solely for identification purposes under the nominative fair use doctrine; images are representative and may depict a different configuration or catalog variant than the exact product listed. Purchasers should independently verify specifications against the current manufacturer publication before placing an order. All product names, trademarks, service marks, and registered trademarks are the property of their respective owners, and their use does not imply endorsement or affiliation.