Installation Instructions · Publication 1734-IN059 · Rockwell Automation

1734-FPD Field Potential Distributor Module Installation Guide

This document is the installation instructions for the Allen-Bradley POINT I/O Field Potential Distributor Module, catalog numbers 1734-FPD and 1734-FPDK (Series B). It covers DIN rail installation, module removal and replacement, wiring for 12/24V DC and 120/240V AC field power, and electrical and environmental specifications. The module is used between I/O modules in a POINT I/O system to break and re-source the internal field power bus for modules to its right.

Download PDF
10 A Max Input/Field Bus Current
10…28.8V DC; 120/240V … Input Voltage Range
-20…+55 Operating Temperature
50V continuous; tested… Isolation Voltage

Document Preview

Open the full PDF in a new tab  · Publication 1734-IN059

Specifications

Electrical Specifications

Input voltage rating (DC nominal) 12V DC, 24V DC nom; 10…28.8V DC range
Input voltage rating (AC nominal) 120V AC, 240V AC nom
Input current, max 10 A
Field power bus supply voltage 264V AC max; 12V DC, 24V DC (10…28.8V DC range); 120V AC, 240V AC, 50/60 Hz
Field power bus supply current, max 10 A
Isolation voltage (continuous) 50V continuous; tested at 2600V DC for 60 s
POINTBus current Pass through
Power consumption None
Power dissipation None
Indicators None
Terminal base screw torque 0.6 N•m (7 lb•in)
Wire size 0.25…2.5 mm² (24…14 AWG) solid or stranded copper, rated 75 °C (167 °F) or greater; 1.2 mm (3/64 in.) insulation max
Wiring category 1, on power ports
North American temp code T4A
UKEX/ATEX temp code T4
IECEx temp code T4

Mechanical Specifications

Dimensions (H x W x D) 79.8 x 25.3 x 133.1 mm (3.14 x 1.00 x 5.24 in.)
Weight 0.12 kg (0.27 lb)
Enclosure type rating None (open-style)
Module location Between I/O modules in POINT I/O system; breaks power bus

Environmental Specifications

Operating temperature -20…+55 °C (-4…+131 °F)
Surrounding air temperature, max 55 °C (131 °F)
Non-operating temperature -40…+85 °C (-40…+185 °F)
Relative humidity 5…95% noncondensing
Vibration 5 g @ 10…500 Hz (IEC 60068-2-6)
Shock, operating 30 g (IEC 60068-2-27)
Shock, nonoperating 50 g (IEC 60068-2-27)
ESD immunity 6 kV contact discharges; 8 kV air discharges (IEC 61000-4-2)
Radiated RF immunity 10 V/m with 1 kHz sine-wave 80% AM from 80…6000 MHz (IEC 61000-4-3)
EFT/B immunity ±4 kV @ 2.5 kHz on power ports (IEC 61000-4-4)
Surge transient immunity ±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports (IEC 61000-4-5)
Conducted RF immunity 10 V rms with 1 kHz sine-wave 80% AM @ 150 kHz…80 MHz (IEC 61000-4-6)
Emissions IEC 61000-6-4

Catalog Number Format

How to read an Allen-Bradley 1734 catalog number. Each position encodes a specific configuration attribute.

Position
Meaning
Example
Base catalog number
POINT I/O Field Potential Distributor Module
1734-FPD
Suffix K
Conformal coated version; specifications are the same as non-conformal coated
1734-FPDK

Certifications & Compliance

c-UL-us: UL-listed Industrial Control Equipment, certified for U.S. and Canada (UL File E65584); UL-listed for Class I Division 2, Group A,B,C,D Hazardous Locations (UL File E194810) UK and CE: UK SI 2016 No. 1091 and EU 2014/30/EU EMC Directive: EN 61326-1, EN 61000-6-2, EN 61000-6-4, EN 61131-2; UK SI 2016 No. 1101 and EU 2014/35/EU LVD: EN 61131-2; UK SI 2012 No. 3032 and EU 2011/65/EU RoHS: EN IEC 63000 RCM: Australian Radiocommunications Act, compliant with EN 61000-6-4 Ex (UKEX/ATEX): UK SI 2016 No. 1107 and EU 2014/34/EU ATEX Directive: EN IEC 60079-0, EN IEC 60079-7; II 3 G Ex ec IIC T4 Gc; DEMKO 04 ATEX 0330347X (at or below 120V AC); UL22UKEX2478X IECEx: IEC 60079-0, IEC 60079-7; II 3 G Ex ec IIC T4 Gc; IECEx UL 20.0072X KC: Korean Registration of Broadcasting and Communications Equipment, Article 58-2 of Radio Waves Act, Clause 3 Morocco: Arrêté ministériel n° 6404-15 du 1er muharram 1437 and n° 6404-15 du 29 ramadan 1436 CCC: CNCA-C23-01; CCC: 2020122309111607

Document Contents

Full PDF covers the following topics in detail:

  • Summary of Changes
  • Before You Begin
  • Install the Module
  • Remove the Module
  • Replace the Module
  • Wire the Module
  • Specifications
  • Environmental Specifications
  • Certifications
  • Additional Resources

Frequently Asked Questions

What does the 1734-FPD module do in a POINT I/O system?
The 1734-FPD breaks the field power distribution bus. It allows you to change the field power distribution source for I/O modules to the right of the module, enabling logical or functional partitioning of low-channel-count, high I/O-mix applications. It passes through all POINT I/O backplane signals except the internal field power bus for field devices.
What voltage ranges does the 1734-FPD support?
The module supports 12V DC and 24V DC nominal (10…28.8V DC range) for DC applications, and 120V AC and 240V AC nominal (50/60 Hz) for AC applications. The field power bus supply voltage maximum is 264V AC.
What is the maximum current the 1734-FPD can handle?
Both the input current maximum and the field power bus supply current maximum are rated at 10 A.
Is the 1734-FPDK different from the 1734-FPD?
The 1734-FPDK is the conformal coated version of the 1734-FPD. Its specifications are identical to the non-conformal coated catalog number.
What hazardous location approvals does the 1734-FPD carry?
The module is UL-listed for Class I Division 2, Group A, B, C, D hazardous locations (UL File E194810). It also carries UKEX/ATEX and IECEx approvals for Zone 2 (II 3 G Ex ec IIC T4 Gc), and CCC certification for explosion-proof electrical products.
What DIN rail is specified for mounting the 1734-FPD?
The publication specifies Allen-Bradley part number 199-DR1 (also 46277-3, EN50022). Zinc-plated chromate-passivated steel DIN rail must be used to assure proper grounding. The DIN rail should be secured to the mounting surface approximately every 200 mm (7.8 in.).
What wire sizes are compatible with the 1734-FPD terminal block?
The module accepts 0.25…2.5 mm² (24…14 AWG) solid or stranded copper wire rated at 75 °C (167 °F) or greater, with a maximum insulation diameter of 1.2 mm (3/64 in.).

Disclaimer