Installation Instructions · Publication 1734-IN042 · Rockwell Automation
1734-AENT / AENTK POINT I/O EtherNet/IP Adapter Install Guide
This document is installation instructions for the 1734-AENT and 1734-AENTK POINT I/O EtherNet/IP adapter, series C. It covers DIN rail mounting, thumbwheel configuration for network address and chassis size, wiring, and status indicator interpretation. Specifications for power, Ethernet communication, environmental ratings, and certifications are also included. The adapter provides an EtherNet/IP interface for up to 63 POINT I/O modules.
Download PDFDocument Preview
Open the full PDF in a new tab · Publication 1734-IN042
Specifications
General Specifications
| Expansion I/O capacity, max | 63 modules |
|---|---|
| Direct connections, max | 31 (standard I/O); 20 if any safety I/O module is in the backplane |
| Rack-optimization connections, max | Up to 5 rack-optimization (digital modules only) and/or enhanced rack-optimization (digital, analog, and specialty modules) |
| Backplane current output | 1.0 A (1734-AENT and 1734-AENTK) |
| Power consumption, max | 10.4 W @ 28.8V DC |
| Power dissipation, max | 5.2 W @ 28.8V DC |
| Thermal dissipation, max | 17.75 BTU/hr @ 28.8V DC |
| Isolation voltage | 50V continuous, Reinforced Insulation; type tested at 500V AC for 60 s |
| Field power supply | 10...28.8V DC @ 10 A |
| Field power output | 10...28.8V DC @ 9 A |
| Module input | 10...28V DC @ 1000 mA |
| POINTBus output, max | 5V DC @ 1.0 A |
| Dimensions (H x W x D), approx. | 76.2 x 54.9 x 133.4 mm (3.0 x 2.16 x 5.25 in.) |
| Weight, approx. | 255 g (0.56 lb) |
| Enclosure type rating | None (open-style) |
| Terminal base screw torque | 0.8 N•m (7 lb•in) |
| Wire size (power) | 0.34...2.1 mm2 (22...14 AWG) solid or stranded copper, rated 75 °C or greater |
| Wire size (Ethernet) | RJ45 per IEC 60603-7; Category 5e min per TIA 568-B.1 or Category 5 per ISO/IEC 24702 |
| North American temp code | T4A |
| UKEX/ATEX temp code | T4 |
| IECEx temp code | T4 |
Power Supply
| Input voltage rating | 24V DC @ 10 A |
|---|---|
| Input voltage range | 10...28.8V DC |
| Field side power requirements, max | 24V DC @ 400 mA |
| Inrush current, max | 6.0 A for 10 ms |
| Input overvoltage protection | Reverse polarity protected |
| POINTBus output current, max | 5V DC @ 1.0 A |
| Interruption | Output stays within spec when input drops out for 10 ms @ 10V with maximum load |
Ethernet Communication
| Ethernet communication rate | 10/100 Mbits/s, half or full-duplex |
|---|---|
| Ethernet ports | 1 |
| Ethernet network topologies supported | Star or Tree |
| Ethernet connector | RJ45, Category 5 |
| Ethernet cable | Category 5: shielded or unshielded |
Environmental Specifications
| Temperature, operating | -20...+55 °C (-4...+131 °F) |
|---|---|
| Temperature, surrounding air, max | 55 °C (131 °F) |
| Temperature, nonoperating | -40...85 °C (-40...185 °F) |
| Relative humidity | 5...95% noncondensing |
| Vibration | 5 g @ 10...500 Hz (IEC 60068-2-6) |
| Shock, operating | 30 g (IEC 60068-2-27) |
| Shock, nonoperating | 50 g (IEC 60068-2-27) |
| ESD immunity | 6 kV contact discharges; 8 kV air discharges (IEC 61000-4-2) |
| Radiated RF immunity | 10V/m with 1 kHz sine wave 80% AM from 80...6000 MHz (IEC 61000-4-3) |
| EFT/B immunity | +/-4 kV @ 5 kHz on power ports; +/-3 kV @ 5 kHz on communications ports (IEC 61000-4-4) |
| Surge transient immunity | +/-1 kV line-line (DM) and +/-2 kV line-earth (CM) on power ports; +/-2 kV line-earth on comms ports (IEC 61000-4-5) |
| Conducted RF immunity | 10V rms with 1 kHz sine wave 80% AM from 150 kHz...80 MHz (IEC 61000-4-6) |
| Emissions | IEC 61000-6-4 |
Catalog Number Format
How to read an Allen-Bradley 1734 catalog number. Each position encodes a specific configuration attribute.
Communication Protocols
Supported industrial networks and field buses for the products covered by this publication.
Certifications & Compliance
Document Contents
Full PDF covers the following topics in detail:
- Summary of Changes
- About the Adapter
- Before You Begin
- Install the Adapter
- Thumbwheel Settings
- Set the Chassis Size
- Set the Network Address
- Replace the Adapter
- Wire the Adapter
- Interpret Status Indicators
- Specifications
- Certifications
- Additional Resources
Frequently Asked Questions
What catalog numbers does this installation document cover?
How many POINT I/O modules can the 1734-AENT adapter support?
How do I set the IP address on the 1734-AENT adapter?
How do I set the chassis size on the 1734-AENT adapter?
What does a steady red Network Status indicator mean?
What type of DIN rail is required to mount the 1734-AENT adapter?
What are the hazardous location approvals for the 1734-AENT?
Disclaimer
Disclaimer: PLC Exchange is an independent reseller and is not an authorized distributor, affiliate, licensee, partner, or agent of Allen-Bradley / Rockwell Automation. All product information on this page is compiled from publicly-available manufacturer publications, technical data sheets, and catalog sources, each of which remains the copyright of its originating manufacturer. We make no representation or warranty, express or implied, regarding the accuracy, completeness, timeliness, or fitness for any particular purpose of the specifications or descriptions shown — content may contain errors, omissions, or out-of-date information. Product images are the property of their respective manufacturers, trademark owners, and source publications, and are displayed solely for identification purposes under the nominative fair use doctrine; images are representative and may depict a different configuration or catalog variant than the exact product listed. Purchasers should independently verify specifications against the current manufacturer publication before placing an order. All product names, trademarks, service marks, and registered trademarks are the property of their respective owners, and their use does not imply endorsement or affiliation.