Installation Instructions · Publication 1734-IN042 · Rockwell Automation

1734-AENT / AENTK POINT I/O EtherNet/IP Adapter Install Guide

This document is installation instructions for the 1734-AENT and 1734-AENTK POINT I/O EtherNet/IP adapter, series C. It covers DIN rail mounting, thumbwheel configuration for network address and chassis size, wiring, and status indicator interpretation. Specifications for power, Ethernet communication, environmental ratings, and certifications are also included. The adapter provides an EtherNet/IP interface for up to 63 POINT I/O modules.

Download PDF
63 Max I/O Modules
5V DC @ 1.0 A POINTBus Output
10/100 Mbits/s Ethernet Rate
-20...+55 Operating Temp

Document Preview

Open the full PDF in a new tab  · Publication 1734-IN042

Specifications

General Specifications

Expansion I/O capacity, max 63 modules
Direct connections, max 31 (standard I/O); 20 if any safety I/O module is in the backplane
Rack-optimization connections, max Up to 5 rack-optimization (digital modules only) and/or enhanced rack-optimization (digital, analog, and specialty modules)
Backplane current output 1.0 A (1734-AENT and 1734-AENTK)
Power consumption, max 10.4 W @ 28.8V DC
Power dissipation, max 5.2 W @ 28.8V DC
Thermal dissipation, max 17.75 BTU/hr @ 28.8V DC
Isolation voltage 50V continuous, Reinforced Insulation; type tested at 500V AC for 60 s
Field power supply 10...28.8V DC @ 10 A
Field power output 10...28.8V DC @ 9 A
Module input 10...28V DC @ 1000 mA
POINTBus output, max 5V DC @ 1.0 A
Dimensions (H x W x D), approx. 76.2 x 54.9 x 133.4 mm (3.0 x 2.16 x 5.25 in.)
Weight, approx. 255 g (0.56 lb)
Enclosure type rating None (open-style)
Terminal base screw torque 0.8 N•m (7 lb•in)
Wire size (power) 0.34...2.1 mm2 (22...14 AWG) solid or stranded copper, rated 75 °C or greater
Wire size (Ethernet) RJ45 per IEC 60603-7; Category 5e min per TIA 568-B.1 or Category 5 per ISO/IEC 24702
North American temp code T4A
UKEX/ATEX temp code T4
IECEx temp code T4

Power Supply

Input voltage rating 24V DC @ 10 A
Input voltage range 10...28.8V DC
Field side power requirements, max 24V DC @ 400 mA
Inrush current, max 6.0 A for 10 ms
Input overvoltage protection Reverse polarity protected
POINTBus output current, max 5V DC @ 1.0 A
Interruption Output stays within spec when input drops out for 10 ms @ 10V with maximum load

Ethernet Communication

Ethernet communication rate 10/100 Mbits/s, half or full-duplex
Ethernet ports 1
Ethernet network topologies supported Star or Tree
Ethernet connector RJ45, Category 5
Ethernet cable Category 5: shielded or unshielded

Environmental Specifications

Temperature, operating -20...+55 °C (-4...+131 °F)
Temperature, surrounding air, max 55 °C (131 °F)
Temperature, nonoperating -40...85 °C (-40...185 °F)
Relative humidity 5...95% noncondensing
Vibration 5 g @ 10...500 Hz (IEC 60068-2-6)
Shock, operating 30 g (IEC 60068-2-27)
Shock, nonoperating 50 g (IEC 60068-2-27)
ESD immunity 6 kV contact discharges; 8 kV air discharges (IEC 61000-4-2)
Radiated RF immunity 10V/m with 1 kHz sine wave 80% AM from 80...6000 MHz (IEC 61000-4-3)
EFT/B immunity +/-4 kV @ 5 kHz on power ports; +/-3 kV @ 5 kHz on communications ports (IEC 61000-4-4)
Surge transient immunity +/-1 kV line-line (DM) and +/-2 kV line-earth (CM) on power ports; +/-2 kV line-earth on comms ports (IEC 61000-4-5)
Conducted RF immunity 10V rms with 1 kHz sine wave 80% AM from 150 kHz...80 MHz (IEC 61000-4-6)
Emissions IEC 61000-6-4

Catalog Number Format

How to read an Allen-Bradley 1734 catalog number. Each position encodes a specific configuration attribute.

Position
Meaning
Example
Base catalog number
POINT I/O EtherNet/IP adapter
1734-AENT
Suffix K
Conformal coating option
1734-AENTK

Communication Protocols

Supported industrial networks and field buses for the products covered by this publication.

EtherNet/IP ODVA conformance tested; 10/100 Mbits/s half or full-duplex via single RJ45 port; Star or Tree topologies

Certifications & Compliance

c-UL-us: UL Listed Industrial Control Equipment for US and Canada (UL File E65584); UL Listed Class I Division 2 Group A,B,C,D Hazardous Locations (UL File E194810) UK and CE: UK SI 2016 No. 1091 and EU 2014/30/EU EMC Directive; EN 61326-1, EN 61000-6-2, EN 61000-6-4, EN 61131-2; RoHS UK SI 2012 No. 3032 and EU 2011/65/EU, EN IEC 63000 RCM: Australian Radiocommunications Act, AS/NZS CISPR11 Industrial Emissions Ex: UK SI 2016 No. 1107 and EU 2014/34/EU ATEX Directive; EN IEC 60079-0, EN IEC 60079-7; II 3 G Ex ec IIC T4 Gc; DEMKO 04 ATEX 0330347X; UL22UKEX2478X IECEx: IEC 60079-0, IEC 60079-7; II 3 G Ex ec IIC T4 Gc; IECEx UL 20.0072X KC: Korean Registration of Broadcasting and Communications Equipment, Article 58-2 of Radio Waves Act, Clause 3 EtherNet/IP: ODVA conformance tested to EtherNet/IP specifications Morocco: Arrêté ministériel n° 6404-15 du 29 ramadan 1436 CCC: CNCA-C23-01; CNCA-C23-01 CCC Implementation Rule Explosion-Proof Electrical Products; CCC: 2020122309111607

Document Contents

Full PDF covers the following topics in detail:

  • Summary of Changes
  • About the Adapter
  • Before You Begin
  • Install the Adapter
  • Thumbwheel Settings
  • Set the Chassis Size
  • Set the Network Address
  • Replace the Adapter
  • Wire the Adapter
  • Interpret Status Indicators
  • Specifications
  • Certifications
  • Additional Resources

Frequently Asked Questions

What catalog numbers does this installation document cover?
This publication covers the 1734-AENT and 1734-AENTK POINT I/O EtherNet/IP adapters, series C. The suffix K indicates a conformal coating option.
How many POINT I/O modules can the 1734-AENT adapter support?
The adapter supports a maximum of 63 modules. The backplane current output is 1.0 A. You can extend backplane current beyond 1.0 A by adding 1734-EP24DC or 1734-EPAC backplane extension power supplies to reach the 63-module maximum.
How do I set the IP address on the 1734-AENT adapter?
You can set the IP address in three ways: use the 3-position pen push thumbwheel switches on the adapter (valid settings 001...254), use a DHCP server such as Rockwell Automation BootP/DHCP, or retrieve the IP address from nonvolatile memory. The adapter reads the thumbwheel switches first to determine whether they are set to a valid number.
How do I set the chassis size on the 1734-AENT adapter?
Set the thumbwheel to a value between 801 and 864 (requires firmware revision 5.015 or later). The chassis size must equal one slot for the adapter plus one slot for each I/O module in the backplane. For example, one adapter with four I/O modules requires a chassis size of 5. The factory default setting is one slot.
What does a steady red Network Status indicator mean?
A steady red Network Status indicator means a duplicate IP address has been detected. You should verify the IP address setting and correct it as needed.
What type of DIN rail is required to mount the 1734-AENT adapter?
The adapter requires an IEC standard 35 x 7.5 x 1 mm top-hat DIN rail. Allen-Bradley part numbers 199-DR1, 46277-3, and EN50022 are cited. Zinc-plated chromate-passivated steel DIN rail must be used to assure proper grounding. Secure the DIN rail to the mounting surface approximately every 200 mm (7.8 in.).
What are the hazardous location approvals for the 1734-AENT?
The adapter is UL Listed for Class I Division 2 Groups A, B, C, D Hazardous Locations for the US and Canada (UL File E194810). It also holds ATEX approval (II 3 G Ex ec IIC T4 Gc, DEMKO 04 ATEX 0330347X) for Zone 2 potentially explosive atmospheres, UKEX approval (UL22UKEX2478X), and IECEx certification (IECEx UL 20.0072X) per IEC 60079-0 and IEC 60079-7.