Installation Instructions · Publication 1734-IN016 · Rockwell Automation

POINT Guard I/O Safety Modules Installation Instructions

This document provides installation instructions for POINT Guard I/O safety modules, catalog numbers 1734-IB8S, 1734-IB8SK, 1734-IE4S, 1734-IE4SK, 1734-OB8S, 1734-OB8SK, 1734-OBV2S, and 1734-OBV2SK. It covers terminal base installation, module insertion, removable terminal block procedures, hazardous location approvals, and key electrical specifications. The modules support safety networks rated up to SIL CL 3 and PLe, Cat. 4 per IEC 61508, IEC 61511, IEC 62061, and ISO 13849-1. Compatible controllers include GuardLogix, Compact GuardLogix, and SmartGuard.

Download PDF
SIL CL 3 Safety Rating
-20...+55 Operating Temperature
19.2...28.8V DC Field Power
50V continuous, Basic … Isolation Voltage

Document Preview

Open the full PDF in a new tab  · Publication 1734-IN016

Specifications

General Specifications (All Modules)

Operating Temperature -20 °C < Ta < +55 °C (-4 °F < Ta < +131 °F)
Max Surrounding Air Temperature 55 °C (131 °F)
Enclosure Type Rating None (open-style)
Isolation Voltage 50V (continuous), Basic Insulation Type between field side and system; no isolation between individual channels; tested per UL 61010-1
Temp Code T4
Altitude Up to 2000 m (6562 ft) without derating
Pollution Degree Pollution Degree 2
Overvoltage Category Category II (EN/IEC 60664-1)

1734-IB8S / 1734-IB8SK (Digital Input)

Field Power 19.2...28.8V DC, 25 mA (no load), SELV/PELV 150VA max
Input Voltage Range @ 40 °C 11...30V DC, 3.5 mA, SELV/PELV 150VA max
Input Voltage Range @ 55 °C 11...28.8V DC, 3.5 mA, SELV/PELV 150VA max
Test Output per Output @ 40 °C 0.7 A max
Test Output per Output @ 55 °C 0.5 A max
Test Output per Module @ 40 °C 2.8 A max
Test Output per Module @ 55 °C 0.55 A max
Backplane 5V DC, 125 mA
Indicators 1 yellow (lock status), 1 green/yellow (power status), 8 I/O channel status
Pilot Duty Rating Test Outputs: Not rated

1734-IE4S / 1734-IE4SK (Analog Input)

Field Power 19.2...28.8V DC, 65 mA, Class 2
Input Voltage +/-10V DC Voltage
Input Current 0...20 mA
Tach Input 0...24V DC
Sensor Output per Output @ 55 °C 150 mA max
Backplane 5V DC, 110 mA
Wire Type Shielded on signal ports
Indicators 1 yellow (lock status), 1 green/yellow (power status), 4 I/O channel status
Pilot Duty Rating Sensor Outputs: Not rated

1734-OB8S / 1734-OB8SK (Digital Output)

Field Power 19.2...28.8V DC, 50 mA (no load), SELV/PELV 150VA max
Output per Output @ 40 °C 1.0 A max
Output per Output @ 55 °C 0.5 A max
Output per Module @ 40 °C 8.0 A max
Output per Module @ 55 °C 2.0 A max
Backplane 5V DC, 125 mA
Indicators 1 yellow (lock status), 1 green/yellow (power status), 8 I/O channel status
Pilot Duty Rating Outputs: Not rated

1734-OBV2S / 1734-OBV2SK (Digital Output)

Field Power 19.2...28.8V DC, 65 mA (no load), SELV/PELV 150VA max
Output per Output @ 40 °C 1.25 A max
Output per Module @ 40 °C 2.0 A max
Backplane 5V DC, 125 mA
Indicators 1 yellow (lock status), 1 green/yellow (power status), 4 I/O channel status
Pilot Duty Rating DC-13, DC-14, Inrush Electronically limited 1.8 A

Catalog Number Format

How to read an Allen-Bradley 1734 catalog number. Each position encodes a specific configuration attribute.

Position
Meaning
Example
Suffix K
Conformal coating option
1734-IB8SK

Certifications & Compliance

Class I, Division 2, Groups A, B, C, D (North American Hazardous Location) ATEX II 3 G, Ex ec IIC T4 Gc (EU Directive 2014/34/EU), certificate DEMKO 09 ATEX 0919970X UKEX II 3 G, Ex ec IIC T4 Gc (UKEX Regulation 2016 No. 1107), certificate UL23UKEX2774X IECEx Ex ec IIC T4 Gc, certificate IECEx UL 20.0093X

Document Contents

Full PDF covers the following topics in detail:

  • Summary of Changes
  • North American Hazardous Location Approval
  • UK and European Hazardous Location Approval
  • IEC Hazardous Location Approval
  • Special Conditions for Safe Use
  • Environment and Enclosure
  • Electrical Safety Considerations
  • Prevent Electrostatic Discharge
  • Install the Module (Install Terminal Bases, Insert the Module, Insert the Removable Terminal Block)
  • Remove a Terminal Base
  • Specifications
  • Additional Resources

Frequently Asked Questions

What safety integrity levels do the POINT Guard I/O safety modules support?
The modules meet requirements up to and including SIL CL 3 and PLe, Cat. 4 as defined in IEC 61508, IEC 61511, IEC 62061, and ISO 13849-1.
Which controllers are compatible with these POINT Guard I/O safety modules?
The modules can be used with GuardLogix, Compact GuardLogix, and SmartGuard controllers.
How many terminal bases are needed to install each POINT Guard I/O module?
Each POINT Guard I/O module requires two terminal bases. Acceptable catalog numbers are 1734-TB or 1734-TBS (two assemblies) or 1734-TOP, 1734-TOPS, 1734-TOP3, or 1734-TOP3S (one-piece bases). The 1734-TB3 and 1734-TB3S must not be used.
What is the operating temperature range for these modules?
The operating temperature range is -20 °C to +55 °C (-4 °F to +131 °F), tested per IEC 60068-2-1, IEC 60068-2-2, and IEC 60068-2-14.
What type of DIN rail is required for proper grounding?
The product must be mounted on 35 mm (1.38 in.) wide zinc-plated yellow-chromate steel DIN rail to help assure proper grounding. DIN rail must be secured to the mounting surface approximately every 200 mm (7.8 in.) with end-anchors used appropriately.
What does the 'K' suffix in a catalog number indicate?
A catalog number ending in 'K' indicates the conformal coating option, for example 1734-IB8SK.
What isolation voltage is specified for these modules?
The isolation voltage is 50V continuous, Basic Insulation Type between the field side and the system. There is no isolation between individual channels. This is tested according to UL 61010-1.