Installation Instructions · Publication 1734-IN016 · Rockwell Automation
POINT Guard I/O Safety Modules Installation Instructions
This document provides installation instructions for POINT Guard I/O safety modules, catalog numbers 1734-IB8S, 1734-IB8SK, 1734-IE4S, 1734-IE4SK, 1734-OB8S, 1734-OB8SK, 1734-OBV2S, and 1734-OBV2SK. It covers terminal base installation, module insertion, removable terminal block procedures, hazardous location approvals, and key electrical specifications. The modules support safety networks rated up to SIL CL 3 and PLe, Cat. 4 per IEC 61508, IEC 61511, IEC 62061, and ISO 13849-1. Compatible controllers include GuardLogix, Compact GuardLogix, and SmartGuard.
Download PDFDocument Preview
Open the full PDF in a new tab · Publication 1734-IN016
Specifications
General Specifications (All Modules)
| Operating Temperature | -20 °C < Ta < +55 °C (-4 °F < Ta < +131 °F) |
|---|---|
| Max Surrounding Air Temperature | 55 °C (131 °F) |
| Enclosure Type Rating | None (open-style) |
| Isolation Voltage | 50V (continuous), Basic Insulation Type between field side and system; no isolation between individual channels; tested per UL 61010-1 |
| Temp Code | T4 |
| Altitude | Up to 2000 m (6562 ft) without derating |
| Pollution Degree | Pollution Degree 2 |
| Overvoltage Category | Category II (EN/IEC 60664-1) |
1734-IB8S / 1734-IB8SK (Digital Input)
| Field Power | 19.2...28.8V DC, 25 mA (no load), SELV/PELV 150VA max |
|---|---|
| Input Voltage Range @ 40 °C | 11...30V DC, 3.5 mA, SELV/PELV 150VA max |
| Input Voltage Range @ 55 °C | 11...28.8V DC, 3.5 mA, SELV/PELV 150VA max |
| Test Output per Output @ 40 °C | 0.7 A max |
| Test Output per Output @ 55 °C | 0.5 A max |
| Test Output per Module @ 40 °C | 2.8 A max |
| Test Output per Module @ 55 °C | 0.55 A max |
| Backplane | 5V DC, 125 mA |
| Indicators | 1 yellow (lock status), 1 green/yellow (power status), 8 I/O channel status |
| Pilot Duty Rating | Test Outputs: Not rated |
1734-IE4S / 1734-IE4SK (Analog Input)
| Field Power | 19.2...28.8V DC, 65 mA, Class 2 |
|---|---|
| Input Voltage | +/-10V DC Voltage |
| Input Current | 0...20 mA |
| Tach Input | 0...24V DC |
| Sensor Output per Output @ 55 °C | 150 mA max |
| Backplane | 5V DC, 110 mA |
| Wire Type | Shielded on signal ports |
| Indicators | 1 yellow (lock status), 1 green/yellow (power status), 4 I/O channel status |
| Pilot Duty Rating | Sensor Outputs: Not rated |
1734-OB8S / 1734-OB8SK (Digital Output)
| Field Power | 19.2...28.8V DC, 50 mA (no load), SELV/PELV 150VA max |
|---|---|
| Output per Output @ 40 °C | 1.0 A max |
| Output per Output @ 55 °C | 0.5 A max |
| Output per Module @ 40 °C | 8.0 A max |
| Output per Module @ 55 °C | 2.0 A max |
| Backplane | 5V DC, 125 mA |
| Indicators | 1 yellow (lock status), 1 green/yellow (power status), 8 I/O channel status |
| Pilot Duty Rating | Outputs: Not rated |
1734-OBV2S / 1734-OBV2SK (Digital Output)
| Field Power | 19.2...28.8V DC, 65 mA (no load), SELV/PELV 150VA max |
|---|---|
| Output per Output @ 40 °C | 1.25 A max |
| Output per Module @ 40 °C | 2.0 A max |
| Backplane | 5V DC, 125 mA |
| Indicators | 1 yellow (lock status), 1 green/yellow (power status), 4 I/O channel status |
| Pilot Duty Rating | DC-13, DC-14, Inrush Electronically limited 1.8 A |
Catalog Number Format
How to read an Allen-Bradley 1734 catalog number. Each position encodes a specific configuration attribute.
Certifications & Compliance
Document Contents
Full PDF covers the following topics in detail:
- Summary of Changes
- North American Hazardous Location Approval
- UK and European Hazardous Location Approval
- IEC Hazardous Location Approval
- Special Conditions for Safe Use
- Environment and Enclosure
- Electrical Safety Considerations
- Prevent Electrostatic Discharge
- Install the Module (Install Terminal Bases, Insert the Module, Insert the Removable Terminal Block)
- Remove a Terminal Base
- Specifications
- Additional Resources
Frequently Asked Questions
What safety integrity levels do the POINT Guard I/O safety modules support?
Which controllers are compatible with these POINT Guard I/O safety modules?
How many terminal bases are needed to install each POINT Guard I/O module?
What is the operating temperature range for these modules?
What type of DIN rail is required for proper grounding?
What does the 'K' suffix in a catalog number indicate?
What isolation voltage is specified for these modules?
Disclaimer
Disclaimer: PLC Exchange is an independent reseller and is not an authorized distributor, affiliate, licensee, partner, or agent of Allen-Bradley / Rockwell Automation. All product information on this page is compiled from publicly-available manufacturer publications, technical data sheets, and catalog sources, each of which remains the copyright of its originating manufacturer. We make no representation or warranty, express or implied, regarding the accuracy, completeness, timeliness, or fitness for any particular purpose of the specifications or descriptions shown — content may contain errors, omissions, or out-of-date information. Product images are the property of their respective manufacturers, trademark owners, and source publications, and are displayed solely for identification purposes under the nominative fair use doctrine; images are representative and may depict a different configuration or catalog variant than the exact product listed. Purchasers should independently verify specifications against the current manufacturer publication before placing an order. All product names, trademarks, service marks, and registered trademarks are the property of their respective owners, and their use does not imply endorsement or affiliation.