Allen-Bradley 1766-L32AWA — The 1766-L32AWA is an Allen-Bradley MicroLogix 1400 programmable controller rated for 120V AC input power with 20 digital inputs (120V AC), 12 relay outputs, and no embedded analog I/O, suitable for Class I Division 2 hazardous locations.

Input Power 120V AC (20 inputs)
Output Type 12 Relay Outputs
Embedded Analog I/O None
Power Consumption 100 VA
Operating Temperature -20…60 °C (-4…140 °F)
Hazardous Location Rating Class I, Division 2, Groups A, B, C, D
GUARANTEED SAFE CHECKOUT
  • Visa Card
  • MasterCard
  • American Express
  • Discover Card
  • PayPal
  • Apple Pay
SKU: 1766-L32AWA Categories: ,

Description

Allen-Bradley 1766-L32AWA

The 1766-L32AWA is an Allen-Bradley MicroLogix 1400 programmable controller rated for 120V AC input power with 20 digital inputs (120V AC), 12 relay outputs, and no embedded analog I/O, suitable for Class I Division 2 hazardous locations.

User Manual (1766-UM001)

Product Overview
Catalog Number 1766-L32AWA
Product Type MicroLogix 1400 Programmable Controller
Input Configuration 20 × 120V AC Inputs
Output Configuration 12 Relay Outputs
Analog Inputs None
Analog Outputs None
Electrical Specifications
Input Power Supply Voltage 120V AC
User Power Supply None
Power Consumption 100 VA
Power Supply Inrush Current 250 mA @ 120V AC
Input Voltage Range (On-State) 79…132 V AC
Input Voltage Range (Off-State) 0…20 V AC
Operating Frequency 47…63 Hz
Input On-State Current (Nominal) 12 mA @ 120 V AC
Input Off-State Leakage Current 2.5 mA max.
Nominal Input Impedance 10 kΩ @ 60 Hz
Relay Output Maximum Controlled Load 1440 VA
Relay Output Maximum Current per Channel 2.5 A per channel
Relay Output Maximum Current per Controller @ 150V 28 A or total of per-point loads, whichever is less
Relay Output Maximum Current per Controller @ 240V 20 A or total of per-point loads, whichever is less
Relay Output Turn On/Off Time 10 ms (maximum)
Relay Output Minimum Load Current 10 mA
Relay Output Electrical Life 2 × 10⁵ operations min (2.5 A, 250V AC / 30V DC)
Physical & Environmental Specifications
Dimensions (H × W × D) 90 × 180 × 87 mm (3.5 × 7.087 × 3.43 in.)
Shipping Weight 0.9 kg (2.0 lbs)
Enclosure Type Rating None (open-style)
Operating Temperature -20…60 °C (-4…140 °F)
Storage Temperature -40…85 °C (-40…185 °F)
Relative Humidity 5…95% non-condensing
Vibration (Operating) 3 g @ 10…500 Hz
Shock Operating 30 g
Shock Nonoperating (Panel Mount) 50 g
Shock Nonoperating (DIN Mount) 40 g
Wire Size 0.25…2.5 mm² (22…14 AWG) solid or stranded copper wire rated @ 90 °C (194 °F) or greater
Terminal Screw Torque 0.79 Nm (7.0 in-lb) rated
Wiring Category (Signal Ports) Category 2
Wiring Category (Power Ports) Category 2
Wiring Category (Communications Ports) Category 3
Safety & Compliance Certifications
UL Listing UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations (File E10314)
c-UL Listing UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for Canada (File E10314)
CE Marking (EMC) European Union 2014/30/EU; EN 61000-6-2 (Industrial Immunity); EN 61000-6-4 (Industrial Emissions); EN 61131-2 (Programmable Controllers, Clause 8, Zone A & B)
CE Marking (LVD) European Union 2014/35/EU; EN 61131-2 (Programmable Controllers, Clause 11)
RCM (Australia) Australian Radiocommunications Act; AS/NZS CISPR 11 (Industrial Emissions)
EAC (Russia) Russian Customs Union TR CU 020/2011 EMC Technical Regulation
KC (Korea) Korean Registration of Broadcasting and Communications Equipment; Article 58-2 of Radio Waves Act, Clause 3
North American Temperature Code T3C
Pilot Duty Rating R300, C300
Electromagnetic & Immunity Specifications
Emissions Standard CISPR 11 Group 1, Class A
ESD Immunity IEC 61000-4-2: 6 kV contact discharges; 8 kV air discharges
Radiated RF Immunity (80…1000 MHz) IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80% AM
Radiated RF Immunity (1.4…2.0 GHz) IEC 61000-4-3: 3 V/m with 1 kHz sine-wave 80% AM
Radiated RF Immunity (2.0…2.7 GHz) IEC 61000-4-3: 1 V/m with 1 kHz sine-wave 80% AM
EFT/B Immunity (Power Ports) IEC 61000-4-4: ±2 kV @ 5 kHz
EFT/B Immunity (Signal Ports) IEC 61000-4-4: ±2 kV @ 5 kHz
EFT/B Immunity (Communications Ports) IEC 61000-4-4: ±1 kV @ 5 kHz
Surge Transient Immunity (Line-Line DM) IEC 61000-4-5: ±1 kV on AC power ports
Surge Transient Immunity (Line-Earth CM) IEC 61000-4-5: ±2 kV on AC power ports
Conducted RF Immunity IEC 61000-4-6: 10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Voltage Variation Dips (AC Supply) IEC 6100-4-11: 60% dip for 10 periods; 30% dips for 25 periods @ 0° and 180°; 100% dip for 250 periods @ 0° and 180°; 100% dip for 0.5 periods, arbitrary angle
Communication & Expansion
Communication Ports Comm Port 0: 8-pin mini DIN RS-232C/RS-485 (isolated); Comm Port 1: RJ45 (Ethernet/IP); Comm Port 2: 9-pin D-Shell RS-232C (non-isolated)
Expansion Bus Supports up to seven 1762 I/O expansion modules; maximum 5V, 1500 mA (1300 mA for Series C); 24 V, 1500 mA (1300 mA for Series C only)
Hazardous Location Communication Cables (Class I, Div 2) 1761-CBL-AC00 Series C or later; 1761-CBL-AM00 Series C or later; 1761-CBL-AP00 Series C or later; 1761-CBL-PM02 Series C or later; 1761-CBL-HM02 Series C or later; 2707-NC9 Series C or later; 1763-NC01 Series A or later; 1747-CP3 Series
Working Voltage (Isolation & Safety)
Power Supply Input to Backplane Isolation 1836V AC for 1 second or 2596V DC for 1 second; 265V AC Working Voltage (IEC Class 2 reinforced insulation)
Input Group to Backplane Isolation 1517V AC for 1 second or 2145V DC for 1 second; 132V AC Working Voltage (IEC Class 2 reinforced insulation)
Input Group to Input Group Isolation 1517V AC for 1 second or 2145V DC for 1 second; 132V AC Working Voltage (basic insulation)
Output Group to Backplane Isolation 1836V AC for 1 second or 2596V DC for 1 second; 265V AC Working Voltage (IEC Class 2 reinforced insulation)
Output Group to Output Group Isolation 1836V AC for 1 second or 2596V DC for 1second; 265V AC Working Voltage (basic insulation), 150V AC Working Voltage (IEC Class 2 reinforced insulation)
Source: MicroLogix 1400 Programmable Controllers Installation Instructions, Publication 1766-IN001E-EN-P, April 2017

Technical Notes for 1766-L32AWA

  • Refer to the manufacturer's installation instructions for proper mounting, wiring, and configuration.
  • Ensure compatibility with your existing system architecture before ordering.
  • All 1766-L32AWA units sold by PLC Exchange are tested and ship in original factory packaging.
  • For application-specific questions or system compatibility verification, contact PLC Exchange technical support at [email protected] or 980-202-0882.

Alternative Part Numbers & Names for 1766-L32AWA

The 1766-L32AWA by Allen-Bradley may also be found under the following alternative names, catalog numbers, or common search variations:

  • 1766L32AWA
  • Allen Bradley 1766-L32AWA
  • Allen-Bradley 1766-L32AWA
  • 1766 L32AWA
  • 1766/L32AWA
  • MicroLogix 1400 1766-L32AWA
  • MicroLogix1400 1766-L32AWA

All variations refer to the same Allen-Bradley product. If you are unsure whether this is the correct part for your application, contact our team for assistance.

Additional information

Weight 1.98 lbs
Dimensions 7.1 × 3.4 × 3.5 in
warranty

2.5 Year PLC Exchange Warranty, 30 Days worry-free return from delivery

upc

612598518098

mpn

1766-L32AWA

manufacturer

Allen-Bradley

condition

Original Packaging

Dimensions & Weight for 1766-L32AWA

Shipping Dimensions
Weight1.98 lbs
Length7.1 in
Width3.4 in
Height3.5 in
Box Dimensions (L×W×H)7.1 × 3.4 × 3.5 in

Dimensions shown are for the shipping package. For module-level mechanical dimensions, refer to the manufacturer datasheet.

Reviews

There are no reviews yet.

Only logged in customers who have purchased this product may leave a review.

Frequently Asked Questions

Does the 1766-L32AWA include a warranty?

Yes. Every 1766-L32AWA sold by PLC Exchange includes a 2.5-year warranty (30 months, full replacement). Details: https://plcexchange.net/warranty-information/

What is the return policy for the 1766-L32AWA?

PLC Exchange offers a 30-day worry-free return policy. Eligibility and details: https://plcexchange.net/return-policy/

When will my 1766-L32AWA ship?

In-stock orders placed before 4 PM ET ship the same business day via free UPS Ground. Expedited options (Next Day Air, 2nd Day Air) are available at checkout.

Who manufactures the 1766-L32AWA?

The 1766-L32AWA is manufactured by Allen-Bradley. PLC Exchange is an independent reseller specializing in Allen-Bradley industrial automation products.

More MicroLogix 1400 Products

Need Help?

We're here Monday–Friday, 8AM–5PM ET